16
|
Unit installation
Installer and user reference guide
56
FXMA-A
VRV system air conditioner
4P680920-1 – 2022.01
a
T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
a b
c
d
a
Drain pipe connection
b
Water inlet cover
c
Drain outlet for maintenance
d
Refrigerant pipes
Drain piping connection
1
Push the drain hose as far as possible over the drain pipe connection.
2
Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
3
Check for water leaks (see
4
Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps.
5
Connect the drain piping to the drain hose.
≤4 mm
A-A'
b
a
d
c
3
1
2~6
1
4
d
A
A'
A
A'
e
5
2
c
b
a
a
Drain pipe connection (attached to the unit)
b
Drain hose (accessory)
c
Metal clamp (accessory)
d
Large sealing pad (accessory)
e
Drain piping (field supply)
NOTICE
▪
Do NOT remove the drain pipe plug. Water might leak out.
▪
Use the drain outlet only to discharge the water if the drain pump is not used or
before maintenance.
▪
Insert and remove the drain plug gently. Excessive force may deform the drain
socket of the drain pan.