background image

• Indoor Units • FLOOR STANDING UNIT • FXLQ-MAVE

1

6

• VRV

®

 Systems • Indoor Units

12

6

Dimensional drawing & centre of gravity

6 - 1 Dimensional drawing

FXLQ50,63MA

3D038862B

Discharge

1,750 or more

Base

Suction

20 or more

100 or more

100 or more

Front face 

1,000 or more

Required installation space

Perforated hole for piping
(rear)

4-12x30 Slot hole
Hole for rear mounting

Level adjusting screw
as standard accessory
4-M6

2-12x18 slot hole
Hole for fixing
to the floor

Perforated hole for piping
(bottom)

Wiring hole
(bottom)

NOTES

1

Location of unit’s name plate: outside surface of right side plate.

Nr

Part name

Description

1

Liquid pipe connection port

flare connection

2

Gas pipe connection port

flare connection

3

Drain pipe connection port

O.D. 21

4

Switch box

5

Air filter

Piping size (Field supply)

Indoor unit

Gas side

Liquid side

FXLQ50MA

ø 12.7

ø 6.4

FXLQ63MA

ø 15.9

ø 9.5

Summary of Contents for FXLQ25MAVE

Page 1: ...technical data Floor Standing Unit FXLQ MAVE air conditioning systems...

Page 2: ...air conditioning systems technical data Floor Standing Unit FXLQ MAVE...

Page 3: ...Indoor Units FLOOR STANDING UNIT FXLQ MAVE VRV Systems Indoor Units 2...

Page 4: ...ons 60Hz 4 2 Safety device settings 5 3 Options 5 4 Control systems 6 5 Capacity tables 7 Cooling capacity tables 7 Heating capacity tables 9 6 Dimensional drawing centre of gravity 11 Dimensional dra...

Page 5: ...Indoor Units FLOOR STANDING UNIT FXLQ MAVE VRV Systems Indoor Units 2...

Page 6: ...13 2D14B13 2D14B20 2D14B20 Output high W 15 15 25 25 35 35 Drive Direct drive Refrigerant Name R 410A Cooling Sound Pressure High dBA 35 0 35 0 35 0 38 0 39 0 40 0 Low dBA 32 0 32 0 32 0 33 0 34 0 35...

Page 7: ...ller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse use a circuit breaker 1 3 ELECTRICAL SPECIFICATIONS 60HZ FXLQ20MAVE FXLQ25...

Page 8: ...ptions 3D034529C FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA PC BOARD FUSE 250V 10A FAN MOTOR THERMAL PROTECTOR C OFF 135 10 ON 120 or less FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ6...

Page 9: ...A FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA CENTRALISED REMOTE CONTROL DCS302C51 UNIFIED ON OFF CONTROL DCS301C51 SCHEDULE TIMER DST301C51 FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA WIRI...

Page 10: ...0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 1 2 0 3 2 1 9 33 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 1 2 0 3 1 1 9 35 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 0 2 0 3 1 1 9 37 0 1 9 1 6 2 3 1 8...

Page 11: ...3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 2 3 8 6 4 3 7 33 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 1 3 8 6 3 3 6 35 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 5 9 4 0 6 0 3 8 6 2 3 6 37 0 3 8 3 0 4 5 3 4...

Page 12: ...3 0 2 8 3 0 2 2 3 1 3 1 3 1 3 1 3 0 2 8 5 0 4 1 3 3 3 2 3 2 3 1 3 0 2 8 7 0 6 0 3 4 3 4 3 2 3 1 3 0 2 8 9 0 7 9 3 5 3 4 3 2 3 1 3 0 2 8 11 0 9 8 3 6 3 4 3 2 3 1 3 0 2 8 13 0 11 8 3 6 3 4 3 2 3 1 3 0 2...

Page 13: ...5 8 5 5 3 0 2 2 6 2 6 2 6 2 6 1 5 9 5 5 5 0 4 1 6 4 6 4 6 3 6 1 5 9 5 5 7 0 6 0 6 6 6 6 6 3 6 1 5 9 5 5 9 0 7 9 6 8 6 7 6 3 6 1 5 9 5 5 11 0 9 8 7 0 6 7 6 3 6 1 5 9 5 5 13 0 11 8 7 1 6 7 6 3 6 1 5 9 5...

Page 14: ...cription 1 Liquid pipe connection port 6 4 flare connection 2 Gas pipe connection port 12 7 flare connection 3 Drain pipe connection port O D 21 4 Switch box 5 Air filter FXLQ32 40MA 3D038861B Dischar...

Page 15: ...Slot hole Hole for rear mounting Level adjusting screw as standard accessory 4 M6 2 12x18 slot hole Hole for fixing to the floor Perforated hole for piping bottom Wiring hole bottom NOTES 1 Location o...

Page 16: ...oor Units 13 Indoor Units FLOOR STANDING UNIT FXLQ MAVE 6 Dimensional drawing centre of gravity 6 2 Centre of gravity FXLQ MA 4D034527C Model A FXLQ20MA 500 FXLQ25MA 500 FXLQ32MA 570 FXLQ40MA 570 FXLQ...

Page 17: ...s FLOOR STANDING UNIT FXLQ MAVE 1 7 VRV Systems Indoor Units 14 7 Piping diagram FXLQ MA 4D034245A Heat exchanger Fan Filter Filter Electronic expansion valve Liquid pipe connection port Gas pipe conn...

Page 18: ...ol In details refer to the installation manual attached to the unit 3 Use copper conductors only Indoor unit R2T R3T Thermistor Coil A1P Printed circuit board T1R Transformer 220 240V 22V C1 Capacitor...

Page 19: ...band center frequency Hz Octave band sound pressure level dB 0 dB 0 0002 bar Scale 230V 240V H L H L A 35 32 37 34 C 39 37 41 39 220V 240V 1 5m 1 5m Microphone NOTES 1 Over all dB B G N is already rec...

Page 20: ...3 Operating conditons Power source 220 240V 220V 50 60Hz JIS standard 4 Location of microphone 5 Operating noise differs with operation and ambient conditions FXLQ63MA 4D034567A Approximate threshold...

Page 21: ...Open the lid of control panel both left and right 2 Remove screws both left and right 3 Push the knobs both left and right to the rear 4 Lift the front of the top plate 5 Lower the front panel toward...

Page 22: ...FXLQ MA 3P086154 1 4 Window Air flow direction 100 or more FXLQ 100 or more FXLQ 150 or more FXNQ 1 000 or more Front side 20 or more 1 750 or more Base Air inlet direction NOTE 1 Leave sufficient cle...

Page 23: ...Indoor Units FLOOR STANDING UNIT FXLQ MAVE 1 10 VRV Systems Indoor Units 20 10 Installation 10 2 Service space...

Page 24: ...ithout prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publicat...

Reviews: