Daikin FXKQ25MAVE Installation Manual Download Page 8

English

7

• If converging multiple drain pipes, install according to the 

procedure shown below.

Select converging drain pipes whose gauge is suitable for the 
operating capacity of the unit.

(2)

After piping work is finished, check drainage flows 
smoothly.
• Open the inspection opening, add approximately 1liter of 

water slowly into the drain pan and check drainage flow.

NOTE

• Use the drain outlet for maintenance to drain water from the 

drain pan.

WHEN ELECTRIC WIRING WORK IS FINISHED

• Check drainage flow during COOL running, explained under 

“TEST OPERATION”.

WHEN ELECTRIC WIRING WORK IS NOT FINISHED

• Remove the electric parts box lid, connect a power supply 

and remote controller to the terminals.
(Refer to the  

HOW TO CONNECT WIRINGS

 (P.8))

Be sure attach the electric parts box lid before turning on the 

power. 

Next, press the inspection/test operation button “

” on the 

remote controller.  The unit will engage the test operation mode. 

Press the operation mode selector button “

” until selecting 

FAN OPERATION “

”. Then, press the ON/OFF button 

”. The indoor unit fan and drain pump will start up.  Check 

that the water has drained from the unit. Press “

” to go 

back to the first mode.

CAUTION

• Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

• Keep in mind that it will become the cause of getting drain 

pipe blocked if water collects on drain pipe.

8.

ELECTRIC WIRING WORK

8-1

GENERAL INSTRUCTIONS

• All field supplied parts and materials and electric works must 

conform to local codes.

• Use copper wire only.
• For electric wiring work, refer to also “Wiring diagram label” 

attached to the electric parts box lid.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each indoor 

unit as unit A, unit B . . . , and be sure the terminal board wiring 
to the outdoor unit and BS unit are properly matched. If wiring 
and piping between the outdoor unit and an indoor unit are mis-
matched, the system may cause a malfunction.

• A circuit breaker capable of shutting down power supply to 

the entire system must be installed.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply electric wire connected to the 
outdoor unit, the capacity of the circuit breaker and switch, 
and wiring instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, light-

ning rods, or telephone ground wires.

• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is used.
• A circuit breaker capable of shutting down the power sup-

ply to the entire system must be installed.

≥100mm

T-joint converging drain pipes

Inspection opening

Portable pump

Bucket

Drain outlet for maintenance  
(with rubber plug)

TEST

TEST

PC board

Copper wire

Electric parts box lid.

Power supply 
terminal board

Power supply
1-220-240V

L N

01_EN_3P258319-8N.fm  Page 7  Tuesday, February 19, 2019  1:06 PM

Summary of Contents for FXKQ25MAVE

Page 1: ...RA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE IN...

Page 2: ...on that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chatter...

Page 3: ...ective plates together with a rope when lifting to avoid damage or scratches to the unit When selecting installation site refer to the paper pattern For the installation of an outdoor unit refer to th...

Page 4: ...least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise 2...

Page 5: ...lling the indoor unit is easier As for the parts to be used for installation work be sure to use the provided accessories and specified parts designated by our company 1 Install the unit temporarily F...

Page 6: ...iping take measures such as pinching or taping the pipings Do not mix substance other than the specified refriger ant such as air into the refrigeration circuit If the refrigerant leaks during the wor...

Page 7: ...Carry out the drain piping Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe The diameter of the drain pipe should be greater than or equal to...

Page 8: ...in pipe 8 ELECTRIC WIRING WORK 8 1 GENERAL INSTRUCTIONS All field supplied parts and materials and electric works must conform to local codes Use copper wire only For electric wiring work refer to als...

Page 9: ...electric parts box lid make sure no wires get caught in the edges Pass wiring through the wiring through holes to prevent damage to them Make sure the remote controller wiring the wiring between the u...

Page 10: ...control box lid can be securely fastened If the control box lid is not in place the wirings may come out or be sandwiched by the box and the lid and cause electric shocks or a fire 9 2 HIGH CEILING IN...

Page 11: ...Remote controller Indoor unit BS unit Only for Heat recovery system L N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1...

Page 12: ...to the field set mode For details refer to the HOW TO SET IN THE FIELD in the remote controller manual When in the field set mode select mode No 12 then set the first code switch No to 1 Then set sec...

Page 13: ...1904 HT 3P258319 8N EM02A082F 00_CV_3P258319 8N fm Page 2 Tuesday February 5 2019 11 42 AM...

Reviews: