background image

17

English

8. ELECTRIC WIRING WORK

8-1 GENERAL INSTRUCTIONS

Make certain that all electric wiring work is carried out by qualified personnel according to the applicable 
legislation and this installation manual, using a separate circuit. Insufficient capacity of the power supply cir-
cuit or improper electrical construction may lead to electric shocks or a fire.

Make sure to install an earth leakage breaker. Failure to do so may cause electrical shocks and a fire.

For electric wiring work, refer to also the “WIRING DIAGRAM” attached to the control box lid.

Carry out wiring between the outdoor units, indoor units and the remote controllers according to the wiring 
diagram. Carry out installation and wiring of the remote controller according to the “installation manual” 
attached to the remote controller. 

Multiple number of indoor units are connected to one outdoor unit. Name each indoor unit as A-unit, B-unit 
….. and the like. When these indoor units are wired to the outdoor unit and the BS unit, always wiring the 
indoor unit to the terminal indicated with the same symbol on the terminal block. If the wiring and the piping 
are connected to the different indoor units and operated, it will result in malfunction. 

Make sure to earth the air conditioner.
Earthing resistance should be according to applicable legislation.

Do not connect the earth wiring to gas or water piping, lightning conductor or telephone earth wiring.

  • Gas piping ....... Ignition or explosion may occur if the gas leaks.
  • Water piping .... Hard vinyl tubes are not effective earths.
  • Lightning conductor or telephone earth wiring ... Electric potential may rise abnormally if struck by a

lightning bolt.

Do not turn on the power supply (branch switch, branch overcurrent breaker) until all the works are finished.

Carry out installation and wiring of the remote controller according to the “installation manual” attached to 
the remote controller.

Do not touch the Printed Circuit Board assembly. It may cause malfunction.

8-2 ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A) ;

MFA: Max. Fuse Amps (A)

kW: Fan Motor Rated Output (kW) ;

FLA: Full Load Amps (A)

8-3 SPECIFICATION FOR FIELD SUPPLY FUSES AND WIRING

The maximum allowable lengths of remote controller wiring and transmission wirings are as follows:
(1) Remote controller wiring (indoor unit - remote controller).......Max.500m
(2) Transmission wirings............Total wiring length 2000m

Outdoor unit - Indoor unit ...... Max.1000m

Outdoor unit - BS unit ........... Max.1000m

BS unit - Indoor unit .............. Max.1000m

Indoor unit - Indoor unit......... Max.1000m

NOTE

1.

Shows only in case of protected piping. Use H07RN-F in case of no protection.

2.

Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)

Indoor unit

Power supply

Fan motor

Model

Hz

Volts

Voltage range

MCA

MFA

kW

FLA

FXHQ32AVEB

50

220-240

Max. 264

Min. 198

0.8

16

0.060

0.6

FXHQ63AVEB

0.8

16

0.091

0.6

FXHQ100AVEB

1.6

16

0.150

1.3

Model

Power supply wiring

Remote controller wiring

Transmission wiring

Field fuses

Wiring

Size

Wiring

Size

FXHQ32AVEB

16A

H05VV-U3G

NOTE 1)

Wire size and 

length must 

comply with 
local codes.

Vinyl cord with 

sheath or cable 

(2 core)

NOTE 2)

0.75-1.25mm

2

FXHQ63AVEB

FXHQ100AVEB

01_EN_3P249378-8N.fm  Page 17  Saturday, September 29, 2012  3:02 PM

Summary of Contents for FXHQ32AVEB

Page 1: ...S CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERI MENTO FUTURO LEES DEZE INSTRUCTIES...

Page 2: ...ich if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert...

Page 3: ...ontrol box lid is not in place overheat of the terminals electric shocks or a fire may be caused If refrigerant gas leaks during installation work ventilate the area immediately Toxic gas may be produ...

Page 4: ...itioner while looking at the operation manual Instruct the customer how to operate the air conditioner particularly cleaning of the air filters operation pro cedures and temperature adjustment For sel...

Page 5: ...at stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring or piping or no loose wiring Does not operate burnout Is earthing compl...

Page 6: ...east 1 meter away from televisions or radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Install the indoor u...

Page 7: ...378 324 270 375 398 377 260 Type 63 1270 1230 533 479 425 530 553 532 415 Type 100 1590 1550 693 639 585 690 713 692 575 Fig 3 F 690 Unit dimension 210 D C A Unit dimension B Hanging bolt pitch View f...

Page 8: ...rface and install the attached resin bushing 10 3 Remove the hanger Loosen 2 bolts for installing the hanger at both sides M8 4 places at left and right within 10mm Refer to Fig 7 and 8 Remove the fix...

Page 9: ...d installation parts and specified parts 1 Fix the hanger to the hanging bolt Refer to Fig 10 CAUTION For safety make sure to use a washer for hanger 3 accessory and fix by double nuts firmly 2 Lift u...

Page 10: ...ecurely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than 120 C For use under high humidity strengthen the insulat...

Page 11: ...the angle shown in Table 2 After the work is finished check securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in mal function...

Page 12: ...ndoor unit side Do not leave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material field supply F...

Page 13: ...panel penetration cover as it was before removed put the horizontal blade motor and ther mistor lead through the clamp of the top panel penetration cover and fix Refer to Fig 16 and 19 When doing thi...

Page 14: ...it will be affected badly 3 When carrying out leakage test of refrigerant piping and the indoor unit after the installation of indoor unit is finished confirm the connecting outdoor unit installation...

Page 15: ...en to remove it Refer to Fig 22 Select the piping diameter equal to or larger than that of the drain hose 1 accessory polyvinyl chloride piping nominal diameter 20mm outside diameter 26mm Install the...

Page 16: ...ause abnormal noise such as bubbling noise If the drain hose 1 is deflected it may damage the suction grille Install supports at a distance of 1 to 1 5m so that the piping may not deflect Refer to Fig...

Page 17: ...in pump kit 2 After piping is finished check if the drain flows smoothly Gradually put about 0 6 liter of water for drain confirmation into the drain pan from the air outlet Refer to Fig 29 After the...

Page 18: ...r piping Hard vinyl tubes are not effective earths Lightning conductor or telephone earth wiring Electric potential may rise abnormally if struck by a lightning bolt Do not turn on the power supply br...

Page 19: ...ning the terminal screws If an improper screw driver is used it may damage the screw head and a proper tightening cannot be carried out If a terminal is over tightened it may be damaged Refer to the t...

Page 20: ...xture 11 and clamp 4 so that no tension will be given to the wiring transmission part Refer to Fig 32 WARNING When wiring form the wirings orderly so that the control box lid can be securely fastened...

Page 21: ...Keep the distance of 50mm or more between the low voltage wiring remote controller wiring and the high voltage wiring power supply wiring earth wiring at anywhere outside the indoor unit If both the w...

Page 22: ...ote controller Remote controller Remote controller L N L N L N option option option P1P2 P1P2 Outdoor unit Note It is not needed to set the indoor unit address when using group control It is automatic...

Page 23: ...he wiring connection method 2 Carry out additional wiring from the remote controller 2 Sub to the terminals P1 P2 for remote controller wiring on the terminal block X1M in the control box CAUTION When...

Page 24: ...ill be as the table shown below 3 How to choose FORCED OFF or ON OFF OPERATION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SETTING AND TEST O...

Page 25: ...ation state Carry out setting at 3 places Mode No FIRST CODE No and SECOND CODE No The settings shown by in the table indicate those when shipped from the factory The method of setting procedure and o...

Page 26: ...CODE No to the number shown in the Table 5 according to the amount of dust or pollution in the room Though the indoor unit is equipped with the long life filter it is necessary to periodically clean t...

Page 27: ...carrying out test operation After test operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In ad...

Page 28: ...OR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANC...

Page 29: ...1209 HT 3P249378 8N EM12A009 00_CV_3P249378 8N fm Page 2 Sunday September 30 2012 4 47 PM...

Reviews: