1-1 TECHNICAL SPECIFICATIONS
FXHQ32MAVE
FXHQ63MAVE
FXHQ100MAVE
Capacity
Cooling
kW
3.6
7.1
11.2
Heating
kW
4.0
8.0
12.5
Power Input (50Hz)
Cooling
kW
0.111
0.115
0.135
Heating
kW
0.111
0.115
0.135
Power Input (60Hz)
Cooling
kW
0.142
0.145
0.199
Heating
kW
0.142
0.145
0.199
Casing
Colour
White (10Y9/0,5)
Dimensions
Unit
Height
mm
195
195
195
Width
mm
960
1,160
1,400
Depth
mm
680
680
680
Weight
Unit
kg
24
28
33
Heat Exchanger
Dimensions
Nr of Rows
2
3
3
Fin Pitch
mm
1.75
1.75
1.75
Face Area
m²
0.182
0.233
0.293
Nr of Stages
12
12
12
Fan
Type
Sirocco fan
Cooling
High
m³/min
12
17.5
25
Low
m³/min
10
14
19.5
Fan
Motor
Model
3D12K1AA1
4D12K1AA1
3D12K2AA1
Output (high)
W
62
62
130
Drive
Direct drive
Refrigerant
Name
R-410A
Cooling
Sound Pressure
High
dBA
36
39
45
Low
dBA
31
34
37
Piping connections
Liquid (OD)
Type
Flare connection
Diameter
mm
6.35
9.52
9.52
Gas
Type
Flare connection
Diameter
mm
12.7
15.9
15.9
Drain
Diameter
mm
VP20 (I.D. 20/O.D. 26)
Heat Insulation
Glass wool
Air Filter
Resin net with mold resistance
Refrigerant control
Electronic expansion valve
Temperature control
Microprocessor thermostat for cooling and heating
Safety devices
Fuse
Fan motor thermal protector
Standard Accessories
Operation manual
Installation manual
Drain hose
Paper pattern for installation
Clamp metal
Insulation for fitting
Clamps
Washer
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.