Installation and operation manual

3

FXFQ20~125P8VEB

VRV System air conditioners

4PW44997-1

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1.

Relation of ceiling opening to unit and suspension bolt
position. 

(See figure 3)

Use the installation guide (delivered with the unit) for exact
vertical positioning of the unit. 

Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. 

(See figure 4)

2.

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

Refer to the paper pattern for installation for the ceiling opening
dimensions.

Create the ceiling opening required for installation. From the side
of the opening to the casing outlet, implement the refrigerant and
drain piping and wiring for remote controller (unnecessary for
wireless type) and indoor-outdoor unit casing outlet. Refer to
each piping or wiring section.

After making an opening in the ceiling, it may be necessary to
reinforce ceiling beams to keep the ceiling level and to prevent it
from vibrating. Consult the builder for details.

3.

Install the suspension bolts. (use either a W3/8 or M10 size bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce the
ceiling in order to bear the weight of the unit. Adjust clearance from
the ceiling before proceeding further.

Installation example see 

figure 5

.

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories (except for the decoration
panel), read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed. However, for existing
ceilings, install fresh air intake kit before installing the unit.

1.

Install the indoor unit temporarily. 

Attach the hanger bracket to the suspension bolt. Be sure to fix it
securely by using a nut and washer from the upper and lower
sides of the hanger bracket.

Securing the hanger bracket see 

figure 6

.

2.

Fix the paper pattern for installation. (For new ceilings
only.)

The paper pattern for installation corresponds with the measure-
ments of the ceiling opening. Consult the builder for details.

The centre of the ceiling opening is indicated on the paper
pattern for installation. The centre of the unit is indicated on the
unit casing and on the paper pattern for installation.

After removing the packaging material from the paper pattern for
installation, attach the paper pattern for installation to the unit
with the attached screws as shown in 

figure 8

.

Adjust the height of the unit until it matches the indication in

figure 8

.

3.

Adjust the unit to the right position for installation.

(Refer to 

"Preparations before installation" on page 3

.)

4.

Check if the unit is horizontally levelled.

Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch. (If the unit is tilted against the
direction of the condensate flow (the drain piping side is raised),
the float switch may malfunction and cause water to drip.)

Check if the unit is levelled at all four corners with a water level or
a water-filled vinyl tube as shown in 

figure 12

.

5.

Remove the paper pattern for installation. (For new ceilings
only.)

1

Refrigerant piping

2

Suspension bolt (x4)

3

Hanger bracket

4

False ceiling

5

Suspension bolt pitch

6

Indoor unit

7

Ceiling opening

8

Decoration panel

Apply the short side 

of the installation guide in case of 

normal installation

Apply the long side 

of the installation guide in case of 

installation with fresh air intake kit

1

Lower ceiling surface

2

Underside of the unit

1

Dimensions inside frame

2

Opening dimension inside the frame for ceiling

3

Frame

4

Ceiling material

5

Ceiling opening dimension

6

Ceiling-panel overlapping dimension

NOTE

Installation is possible with a ceiling dimension of
910 mm (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.

1

2

1

2

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation, contact
your dealer for details.

1

Nut (field supplied)

2

Washer (supplied with the unit)

3

Hanger bracket

4

Double nut (field supply, tighten)

1

Paper pattern for installation

2

Centre of the ceiling opening

3

Centre of the unit

4

Screws (supplied with the unit)

1

Water level

2

Vinyl tube

Summary of Contents for FXFQ20P8VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20P8VEB FXFQ25P8VEB FXFQ32P8VEB FXFQ40P8VEB FXFQ50P8VEB FXFQ63P8VEB FXFQ80P8VEB FXFQ100P8VEB FXFQ125P8VEB System air conditioners...

Page 2: ...1 1 2 1500 1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 80 100 mm 2 7 2 2 4 5 6 5 10 7 9 4 3 5 1 2 2 2 1 5 10 4 4 1 2...

Page 3: ...til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 va...

Page 4: ...tion Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the...

Page 5: ...te controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent light...

Page 6: ...lder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing and on the paper pattern for installation A...

Page 7: ...ooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazi...

Page 8: ...if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water See figure 11 Check the drainage flow In case electric wiring work is finis...

Page 9: ...rminal While doing this pull the wires inside through the hole in the casing and clamp the wires along with other wires using a clamp as indicated in the figure Unit transmission wiring and remote con...

Page 10: ...Incomplete connections could result in overheating and in the worse case electric shock or fire WIRING EXAMPLE Fit the power supply wiring of each unit with a switch and fuse as shown in figure 17 Com...

Page 11: ...ay Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by 10 2 0X or 10 6 0X 6 Thermostat sensor in group contro...

Page 12: ...r filter back in place perform actions 2 to 4 in the illustration in reverse order Attach the air filter to the suction grille by hanging it over the projected portion above the suction grille Press t...

Page 13: ...nce with relevant local and national legislation NOTES NOTE Do not use gasoline benzene thinner polishing powder liquid insecticide It may cause discoloring or warping Do not let the indoor unit get w...

Page 14: ...ed H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector a...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...4PW44997 1 Copyright Daikin...

Reviews: