Daikin FXFQ100M8V3B Installation And Operation Manual Download Page 4

 

Installation and operation manual

1

FXFQ20~125M8V3B

VRV System air conditioners

4PW25082-1A

C

ONTENTS

Page

Before installation.............................................................................. 1

Selecting installation site................................................................... 2

Preparations before installation......................................................... 2

Installation procedures for fresh air intake duct connection .............. 3

Indoor unit installation ....................................................................... 3

Refrigerant piping work ..................................................................... 3

Drain piping work .............................................................................. 4

Electric wiring work ........................................................................... 5

Wiring example and how to set the remote controller ....................... 5

Wiring example ................................................................................. 6

Field setting....................................................................................... 6

Installation of the decoration panel ................................................... 7

Test operation.................................................................................... 7

Maintenance...................................................................................... 8

Disposal requirements ...................................................................... 9

Wiring diagram ................................................................................ 10

B

EFORE

 

INSTALLATION

Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.

Refer to the installation manual of the outdoor unit for items not
described in this manual.

Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.

Do not place objects in direct proximity of the outdoor unit and
do not let leaves and other debris accumulate around the unit.
Leaves are a hotbed for small animals which can enter the unit.
Once in the unit, such animals can cause malfunctions, smoke
or fire when making contact with electrical parts.

Precautions

Do not install or operate the unit in rooms mentioned below.

Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)

Where corrosive gas like sulphurous gas exists. (Copper tubing
and brazed spots may corrode.)

Where volatile flammable gas like thinner or gasoline is used.

Where machines generating electromagnetic waves exist.
(Control system may malfunction.)

Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories). Also
in vehicles or vessels.

When selecting the installation site, use the supplied paper
pattern for installation.

Do not install accessories on the casing directly. Drilling holes in the
casing may damage electrical wires and consequently cause fire.

Accessories

Check if the following accessories are included with your unit.

Optional accessories

There are two types of remote controllers: wired and wireless.
Select a remote controller according to customers request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.

A decoration panel is also required for this indoor unit.

For the following items, take special care during 
construction and check after installation is finished

FXFQ20M8V3B

FXFQ40M8V3B

FXFQ80M8V3B

FXFQ25M8V3B

FXFQ50M8V3B

FXFQ100M8V3B

FXFQ32M8V3B

FXFQ63M8V3B

FXFQ125M8V3B

VRV System air conditioners

Installation

and operation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

Clamp

1 piece

Also used as packing 

material

Paper pattern for 

installation 1 piece

Drain hose 1 piece

Sealing 2 pieces

Screws M5

For paper pattern 

for installation 

4 pieces.

Washer for hanging 

bracket 8 pieces

Insulation for fitting 1 each

Other: installation and 
operation manual

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

for gas pipe

for liquid pipe

Summary of Contents for FXFQ100M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20M8V3B FXFQ25M8V3B FXFQ32M8V3B FXFQ40M8V3B FXFQ50M8V3B FXFQ63M8V3B FXFQ80M8V3B FXFQ100M8V3B FXFQ125M8V3B System air conditioners ...

Page 2: ... 840 780 5 6 7 8 680 840 860 910 950 12 12 3 5 10 1 8 6 7 11 12 15 4 2 14 7 9 13 4 4 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 6 6 1 2 3 4 7 7 7 1 4 6 3 5 2 3 18 mm 8 8 5 75 550 750 220 300 mm 1 1 5 mm 1 2 3 4 5 6 9 9 100 mm 1 10 10 2 5 1 4 3 4 3 11 11 1 3 2 1 10mm 13 13 3 2 5 4 1 7 6 100 ...

Page 3: ...ane są zgodnie z naszymi instrukcjami 18 sunt în conformitate cu următorul următoarele standard e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 20 on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokum...

Page 4: ...ssories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller A decoration panel is also required for this indoor unit For the following items take special care d...

Page 5: ...pad kit and to the chapter Field setting See figure 1 air flow direction 4 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling before installing the unit The installation pitch is marked on the paper pattern for installation Refer to it to check for points requiring reinforcing Space requ...

Page 6: ...equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four corners with a water level or a water filled vinyl tube as shown in figure 15 5 Remove the paper pattern for installation For new ceilings only REFRIGERANT PIPING WORK For refrigerant piping of outdoor ...

Page 7: ...ing water See figure 13 When electric wiring work is finished Check drainage flow during COOL running explained in chapter Test operation When electric wiring work is not finished Remove the switch box lid and connect the power supply and remote controller to the terminals See figure 12 Next press the inspection test operation button on the remote controller The unit will engage the test operation...

Page 8: ...es Precautions 1 Observe the notes mentioned below when wiring to the power supply terminal board Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the figure Use the specified electric wire Connect the wire securely to the terminal Lock the wire down without ...

Page 9: ...s 100 hrs 1 Long life filter type Change the setting when ultra long life filter is installed This setting is important for time between 2 filter cleaning display indications refer to 10 0 0X Long life filter Ultra long life filter 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor i...

Page 10: ...e No 12 then set the first code switch No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 22 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Refer to the installa...

Page 11: ...r or wash the air filter with water When the air filter is very dirty use a soft brush and neutral detergent Remove water and dry in the shade 4 Fix the air filter Attach the air filter to the suction grill by hanging it to the projected portion above the suction grill Press the bottom of the air filter against the projections on the bottom of the grille to snap the air filter into its place 5 Shu...

Page 12: ...eattach the suction grill See item No 2 5 Close the suction grill See item No 1 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation NOTES NOTE When the suction grill is very dirty use a typical kitchen cleaner and let it sit for about 10 minutes Than wash it with water ...

Page 13: ... DIODE SERVICE MONITOR RED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET CONNECTOR FOR OPTIONAL PARTS X18A CONNECTOR ADAPTOR FOR ELECTRICAL APPENDICES X23A CONNECTOR WIRELESS REMOTE CONTROLLER FIELD WIRING BLK BLACK TERMINAL BLU BLUE CO...

Page 14: ...NOTES NOTES ...

Page 15: ...F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 20 20 S M S S M 2 3 1 17 17 18 18 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 16 16 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 19 19 F2 T1 T2 FORCED OFF 1 ...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25082 1A ...

Reviews: