![background image](http://html1.mh-extra.com/html/daikin/fxfq-a/fxfq-a_technical-data-manual_2459697007.webp)
3
1
2
• VRV Systems • Indoor Unit
5
• Indoor Unit • Round flow cassette • FXFQ-A
2
Specifications
Standard Accessories : Clamps; Quantity : 1;
Standard Accessories : Drain sealing pad; Quantity : 1;
Standard Accessories : Sealing pads; Quantity : 4;
Standard Accessories : Insulation for fitting; Quantity : 2;
Standard Accessories : Installation guide; Quantity : 1;
Standard Accessories : Screws; Quantity : 1;
Standard Accessories : Washer for hanger bracket; Quantity : 1;
Standard Accessories : Clamp for drain hose; Quantity : 1;
Standard Accessories : Drain hose; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Standard Accessories : Operation manual; Quantity : 1;
Notes
(1) The sound power level is an absolute value indicating the power which a sound source generates.
(2) The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the
BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt.
(3) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(4) Maximum allowable voltage range variation between phases is 2%.
(5) MCA/MFA: MCA = 1.25 x FLA
(6) MFA
≤
4 x FLA
(7) Next lower standard fuse rating minimum 16A
(8) Select wire size based on the value of MCA
(9) Instead of a fuse, use a circuit breaker
Sound pressure level
Cooling
High
dBA
31
33
35
38
43
45
Nom.
dBA
29
31
33
34
37
41
Low
dBA
28
29
30
36
Heating
High
dBA
31
33
35
38
43
45
Nom.
dBA
29
31
33
34
37
41
Low
dBA
28
29
30
36
Refrigerant
Type
R-410A
Piping connections
Liquid
Type
Flare connection
OD
mm
6.35
9.52
Gas
Type
Flare connection
OD
mm
12.7
15.9
Drain
VP25 (O.D. 32 / I.D. 25)
Heat insulation
Foamed polystyrene / Foamed polyethylene
Sound absorbing insulation
Foamed Polyurethane
Air filter
Type
Resin net with mold resistance
2-2 Electrical Specifications
FXFQ20A
FXFQ25A
FXFQ32A
FXFQ40A
FXFQ50A
FXFQ63A
FXFQ80A
FXFQ100A FXFQ125A
Power supply
Frequency
Hz
50/60
Voltage
V
220-240/220
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz
Minimum circuit amps (MCA)
A
0.3
0.4
0.6
0.8
1.3
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Total
A
0.2
0.3
0.5
0.6
1.0
Current - 60Hz
Minimum circuit amps (MCA)
A
0.3
0.4
0.6
0.8
1.3
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Total
A
0.2
0.3
0.5
0.6
1.0
2-1 Technical Specifications
FXFQ20A
FXFQ25A
FXFQ32A
FXFQ40A
FXFQ50A
FXFQ63A
FXFQ80A
FXFQ100A FXFQ125A
Summary of Contents for FXFQ-A
Page 1: ...Air Conditioning Technical Data Round flow cassette EEDEN12 204 FXFQ A...
Page 2: ......
Page 5: ...3 1 1 VRV Systems Indoor Unit 3 Indoor Unit Round flow cassette FXFQ A 1 Features standard...
Page 10: ...Indoor Unit Round flow cassette FXFQ A 1 5 VRV Systems Indoor Unit 8 5 Options 5 1 Options...
Page 40: ......