background image

3

1

8

• VRV Systems • Indoor Unit

11

• Indoor Unit • Small concealed ceiling unit • FXDQ-M9

8

Wiring diagrams

8 - 1 Wiring Diagrams - Single Phase

FXDQ-M9

2TW23666-1E

indoor

Terminals

for operation 

indicator

Compressor

operation

Fan

operation

Wiring adapters

Switch box

Switch box cover

Note 4 input
from outside

Centralised remote
control note 2

Wired
remote
control

NOTES

1

Use copper conductors only.

2

When using a centralised remote control, see manual for connection to the unit.

3

When installing the electric heater change the wiring for the heater circuit. The main power supply has to be supplied independently.

4

When connecting the input wires from the outdoor unit 'forced off' or 'on/off' operation can be selected by the remote control. For more details see installation manual.

A1P

Printed circuit board

RyF1-3

Magnetic relay (Fan)

RyC, RyF

Magnetic relay

C1R

Capacitor (Fan)

T1R

Transformer (220-240V/22V)

RyH

Magnetic relay (J1EH)

F1U

Fuse (250V, 10A)

X1M

Terminal strip (Power)

F1U, F2U

Fuse (250V, 5A)

F2U

Field fuse

X2M

Terminal strip (Control)

X1A, X2A Connector (Wiring adapter)

HAP

Light emitting diode (Service monitor-green)

Y1E

Electronic expansion valve

X1M

Terminal strip

M1F

Motor (Fan)

Optional parts

Connector for optional parts

Q1E

Earth leak detector

J1EH

Electric heater

X16A

Connector (Wiring adapter)

R1T

Thermistor (Air)

K1R

Magnetic relay (J1EH)

X18A

Connector (Wiring adapter for electronical appendices)

R2T, R3T

Thermistor (Refrigerant)

Wiring adapter

: Field wiring

COLORS  :  BLK : Black 

PNK : Pink

 

  BLU : Blue 

RED : Red

 

  BRN: Brown 

WHT : White

 

  ORG : Orange 

YLW : Yellow

: Live
: Neutral
: Connector
: Wire clamp
: Protective earth (screw)

L
N

Summary of Contents for FXDQ20M9

Page 1: ...Air Conditioning Technical Data Small concealed ceiling unit EEDEN12 204 FXDQ M9 ...

Page 2: ......

Page 3: ...cal Specifications 3 3 Safety device settings 5 Safety Device Settings 5 4 Options 6 Options 6 5 Capacity tables 7 Cooling Capacity Tables 7 Heating Capacity Tables 8 6 Dimensional drawings 9 Dimensional Drawings 9 7 Piping diagrams 10 Piping Diagrams 10 8 Wiring diagrams 11 Wiring Diagrams Single Phase 11 9 Sound data 12 Sound Level Data 12 Sound Pressure Spectrum 13 ...

Page 4: ...sily be mounted in a ceiling void Blends unobtrusively with any interior décor only the suction and discharge grilles are visible Standard air filter removes airborne dust particles to ensure a steady supply of clean air The air suction direction can be altered from rear to bottom suction For easy mounting the drain pan can be located to the left or right of the unit Allows multi tenant applicatio...

Page 5: ...XSS Fin Type Symmetric waffle louvre Treatment Hydrophilic Fan Type Sirocco fan Quantity 1 Air flow rate 50Hz Cooling High m min 6 7 7 4 Low m min 5 2 5 8 Heating High m min 6 7 7 4 Low m min 5 2 5 8 Fan motor Quantity 1 Model Step motor Speed Steps 3 Output High W 10 Drive Direct drive Sound power level Cooling Nom dBA 50 Sound pressure level Cooling High dBA 37 Low dBA 32 Heating High dBA 37 Low...

Page 6: ...r fan motor heat 4 Voltage range units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits 5 Maximum allowable voltage range variation between phases is 2 6 MCA MFA MCA 1 25 x FLA 7 MFA 4 x FLA 8 Next lower standard fuse rating minimum 16A 9 Select wire size based on the value of MCA 10 Instead of a fuse use a circuit breaker...

Page 7: ...s Indoor Unit 5 Indoor Unit Small concealed ceiling unit FXDQ M9 3 Safety device settings 3 1 Safety Device Settings 3TW25511 3 FXDQ20M9 FXDQ25M9 FAN MOTOR THERMAL PROTECTOR C OFF 135 8 ON 87 15 PC BOARD FUSE 250V 10A ...

Page 8: ...C4C64 2 Simplified remote control BRC2A51 3 Remote control for hotel use BRC3A61 4 Adapter for wiring KRP1B61 5 1 Wiring adapter for electrical appendices 1 KRP2A51 5 2 Wiring adapter for electrical appendices 2 KRP4A51 6 Remote sensor KRCS01 1 7 Installation box for adapter PCB 8 Central remote control DCS302C51 8 1 Electrical box with earth terminal 3 blocks KJB311A 9 Unified ON OFF controller D...

Page 9: ...Indoor Unit 7 Indoor Unit Small concealed ceiling unit FXDQ M9 5 Capacity tables 5 1 Cooling Capacity Tables 4 0 7 7 7RWDO DSDFLW N 6 6HQVLEOH KHDW FDSDFLW N QGRRU DLU WHPS 8QLW VL H 2XW GRRU 7 6 7 6 7 6 7 6 7 6 7 6 7 6 ...

Page 10: ... 3 2 3 2 2 3 0 2 2 2 5 2 5 2 4 2 4 2 3 2 2 5 0 4 1 2 5 2 5 2 5 2 4 2 3 2 2 7 0 6 0 2 6 2 6 2 5 2 4 2 3 2 2 9 0 7 9 2 7 2 7 2 5 2 4 2 3 2 2 11 0 9 8 2 8 2 7 2 5 2 4 2 3 2 2 13 0 11 8 2 8 2 7 2 5 2 4 2 3 2 2 15 0 13 7 2 8 2 7 2 5 2 4 2 3 2 2 25 3 2 19 8 20 0 1 9 1 9 1 9 1 9 1 9 1 9 18 8 19 0 1 9 1 9 1 9 1 9 1 9 1 9 16 7 17 0 2 1 2 1 2 0 2 0 2 0 2 0 14 7 15 0 2 2 2 2 2 2 2 2 2 2 2 1 12 6 13 0 2 3 2 3...

Page 11: ...mensional Drawings FXDQ M9 3TW25774 1 Suspension position 250 or more Suspensi o n posi t i o n 300 or more Nr Part name 1 Liquid pipe connection ø 6 35 2 Gas pipe connection ø 12 7 3 Drain hole o d ø 27 2 i d ø 21 6 4 Transmission wiring port 5 Power supply wiring port 6 Service space 7 Switch box 8 Nameplate ...

Page 12: ...it 10 7 Piping diagrams 7 1 Piping Diagrams FXDQ M9 3TW21175 1C Heat exchanger Fan Filter Filter Electronic expansion valve Liquid pipe connection port Gas pipe connection port Refrigerant flow Cooling Heating Piping connection diameters Model Gas Liquid FXDQ20 25M9 ø12 7 ø6 4 ...

Page 13: ...be selected by the remote control For more details see installation manual A1P Printed circuit board RyF1 3 Magnetic relay Fan RyC RyF Magnetic relay C1R Capacitor Fan T1R Transformer 220 240V 22V RyH Magnetic relay J1EH F1U Fuse 250V 10A X1M Terminal strip Power F1U F2U Fuse 250V 5A F2U Field fuse X2M Terminal strip Control X1A X2A Connector Wiring adapter HAP Light emitting diode Service monitor...

Page 14: ...ng a power source of 230V 50Hz 4 These operating values were obtained in a dead room conversion values Noise values will vary depending on a range of factors such as the construction of the particular room in which the equipment is installed 5 Operating noise differs with operation and ambient conditions Model Sound pressure level 230V Sound power level H L Measuring location FXDQ20M9 37 32 50 FXD...

Page 15: ... 13 Indoor Unit Small concealed ceiling unit FXDQ M9 9 Sound data 9 2 Sound Pressure Spectrum FXDQ20M9 3TW21467 1 Octave band frequency Hz Sound pressure level dB FXDQ25M9 3TW21477 1 Octave band frequency Hz Sound pressure level dB ...

Page 16: ...lash com EEDEN12 204 07 12 Copyright Daikin The present publication supersedes EEDEN11 204 The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this leaflet to the best of its knowledge No express or implied warranty is given for the completeness accuracy re liability or fitness for ...

Reviews: