background image

English

3

Also review the “SAFETY PRECAUTIONS”.

b. Items to be checked at time of delivery

c. Points for explanation about operations

3.

SELECTING INSTALLATION SITE 

CAUTION

When moving the unit during or after unpacking, make sure 
to lift it by holding its lifting lugs.  Do not exert any pressure on 
other parts, especially the refrigerant piping, drain piping and 
flange parts.

If you think the humidity inside the ceiling might exceed 
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that 
it is no thicker than 10mm and fits inside the ceiling open-
ing.

(1) Select an installation site where the following conditions 

are fulfilled and that meets with your customer’s approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate can be properly drained.

Where the ceiling is strong enough to bear the indoor unit 
weight.

Where the false ceiling is not noticeably on an incline.

Where there is no risk of flammable gas leakage.

Where sufficient clearance for maintenance and service 
can be ensured. 

(Refer to Fig. 1)

Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation 
manual for the outdoor unit.)

The equipment is not intended for use in a potentially 
explosive atmosphere.

*H1 dimension means the minimum height of the unit.

Select the *H1, *H2 dimension such that a downward 
slope of at least 1/100 is ensured as indicated in 

7. DRAIN PIPING WORK

”.

The maintenance space marked with “*” is required when 
the installation box for adaptor PC board (KRP1BA101) 
sold separately is used.

[ PRECAUTION ]

Install the indoor and outdoor units, power supply wiring 
and connecting wires at least 1 m away from televisions or 
radios in order to prevent image interference or noise. 
(Depending on the radio waves, a distance of 1 m may not 
be sufficient enough to eliminate the noise.)

If installing the wireless kit in a room with electronic fluo-
rescent lighting (inverter or rapid start type), the remote 
controller’s transmission distance may be shortened. 
Indoor units should be installed as far away from fluores-
cent lighting as possible.

(2) Use suspension bolts for installation. Check whether 

the ceiling is strong enough to support the weight of 
the unit or not. If there is a risk, reinforce the ceiling 
before installing the unit.

To avoid contact with the fan, one of the following precaution 
actions must be taken:

-

Install the unit as high as possible at a minimum bottom  
height of 2.7 m.

-

Install the unit as high as possible at a minimum bottom 
height of 2.5 m in case the fan is externally screened by 
parts which can be removed without the aid of tools (e.g. 
false sealing, grill ... ).

-

Install the unit with ducting and grill which can only be 
removed with the aid of tooling. It shall be installed so that 
it gives adequate protection against touching the fan. If a 
maintenance panel exists in the ducting, it shall only be 
possible to remove the panel by the aid of tooling to avoid 
contact with the fan. The protection shall be according to 
relevant European and local legislation. There are no 
restrictions concerning the installation height.

Is something blocking the air 
outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient 
cooling.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in the 
system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
operation manual to your customer?

Did you hand the operation manual and warranty over to 
your customer?

Did you explain about the way of maintaining and cleaning 
local procurements (air filter, grille (both air outlet and suc-
tion grille), etc.) to your customer?

Did you hand manuals of local procurements (in case 
equipped) over to your customer?

The items with 

WARNING and 

CAUTION marks in 

the operation manual are the items pertaining to 
possibilities for bodily injury and material damage in 
addition to the general usage of the product. Accordingly, it 
is necessary that you make a full explanation about the 
described contents and also ask your customers to read the 
operation manual.

Control 

b

ox

M

a

inten

a

nce

s

p

a

ce

M

a

inten

a

nce

s

p

a

ce

3

00

or more

*3

00

or 
more

*

H2=20 or more

2500 or more

*

H1=

240 or more

200

Ceiling

Floor 

su

rf

a

ce

(length : mm)

Fi

g

. 1

Summary of Contents for FXDQ15P7VEB

Page 1: ...INSTALLATION MANUAL FXDQ15P7VEB FXDQ20P7VEB FXDQ25P7VEB FXDQ32P7VEB FXDQ40P7VEB FXDQ50P7VEB FXDQ63P7VEB SYSTEM Inverter Air Conditioners ...

Page 2: ...como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Ser...

Page 3: ... strength may result in the equip ment falling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified pers...

Page 4: ...the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal opera tion of the unit For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit 2 1 PRECAUTIONS Be sure to instru...

Page 5: ...y be shortened Indoor units should be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit To avoid contact with the fan one of the following precaution actions must be taken Install the unit as high ...

Page 6: ...einforce the ceiling frame to prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 In case of bottom suction 1 Remov...

Page 7: ...tion environment If the tempera ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil to the flare section when using a flare connection Only use the flare nuts included with the unit Using different flare nu...

Page 8: ...igerant pipe joints Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine may cause the refrigerant lubricant to deteriorate and affect adversely the refrigerant piping system Not recommendable but in case of emergency You must use a torque wrench bu...

Page 9: ...n 300mm from the unit Refer to Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of treatment may cause leaking If you are u...

Page 10: ... area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use an air filter whose dust collecting efficiency is at least 50 in a gravimetric technique The included filter is not used when the intake duct is attached Air outlet side Connect the duct according to the...

Page 11: ...re to use insulated terminals Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of protected pipes Use H07RN F in case of no protection 2 Insulated thickness 1mm or more 3 If the wiring is in a place where people it can be easily touched by people insta...

Page 12: ...he terminal block 3P Be sure to put the part of the sheathed vinyl into the control box Remote controller and transmission wiring Pull the wires into the unit through the wiring through hole and connect to the terminal block 6P Be sure to put the part of the sheathed vinyl into the control box Clamp Clamp Remove the clasp with screwdriver Let a wire go through the clasp and be sure to attach the c...

Page 13: ...ply wiring terminal block 3P 1 18 1 44 Electric wire Round crimp style terminal Insulation sleeve Connect wires of the same gauge to both sides Do not connect wires of the same gauge to one side Do not connect wires of different gauges Indoor unit A Indoor unit B Most downstream Indoor unit Power supply single phase 50Hz 220 240V or single phase 60Hz 220V Power supply single phase 50Hz 220 240V or...

Page 14: ...ed control 11 FIELD SETTING AND TEST RUN Field settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the control box lids are closed on the indoor and outdoor units 2 Depending on the type of installation make the field settings from the remote controller after the power is turned on following the Field Settings manual which came with the r...

Page 15: ...uid crystal display to identify the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a possi bility that the wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote controller to stop operatio...

Page 16: ...ADAPTOR FOR ELECTRICAL APPENDICES WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWITCH MAIN SUB FIELD WIRING BLK BLACK ORG ORANGE CONNECTOR BLU BLUE PNK PINK WIRE CLAMP BRN BROWN RED RED PROTECTIVE EARTH SCREW GRN GREEN WHT WHITE L LIVE GRY GREY YLW YELLOW N NEUTRAL WIRED REMOTE CONTROLLER OPTIONAL ACCESSORY SWITCH BOX INDOOR TRANSMISSION WIRING CENTRAL REMOTE CONTROLLER INPUT FROM OUTSI...

Page 17: ...NOTES ...

Page 18: ...NOTES ...

Page 19: ...NOTES ...

Page 20: ...Copyright 2011 Daikin 4PW67403 1 01 2011 ...

Reviews: