• Indoor Unit • 2-way blow ceiling mounted cassette • FXCQ-A

1

6

• VRV Systems • Indoor Unit

8

6

Capacity tables

6 - 1 Cooling Capacity Tables

Unit size

Indoor air temp.

14.0 °CWB

16.0 °CWB

18.0 °CWB

19.0 °CWB

20.0 °CWB

22.0 °CWB

24.0 °CWB

20 °CDB

23 °CDB

26 °CDB

27 °CDB

28 °CDB

30 °CDB

32 °CDB

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

20

1.5

1.4

1.8

1.7

2.1

1.9

2.2

1.9

2.2

1.8

2.3

1.7

2.3

1.7

25

1.9

1.7

2.3

2.0

2.6

2.2

2.8

2.3

2.8

2.2

2.9

2.1

3.0

2.1

32

2.4

2.0

2.9

2.3

3.4

2.6

3.6

2.6

3.6

2.6

3.7

2.6

3.8

2.5

40

3.0

2.5

3.6

2.9

4.2

3.2

4.5

3.2

4.6

3.1

4.7

3.0

4.8

3.0

50

3.8

3.0

4.5

3.5

5.2

3.9

5.6

3.9

5.7

3.8

5.8

3.6

5.9

3.1

63

4.8

3.9

5.7

4.9

6.6

5.0

7.1

5.0

7.2

5.4

7.4

5.3

7.5

5.9

80

6.1

4.9

7.2

5.7

8.4

6.3

9.0

6.5

9.1

6.3

9.3

6.1

9.5

6.1

125

9.4

7.5

11.3 8.7

13.1

9.7

14.0

9.9

14.2

9.8

14.5

9.5

14.9

9.1

NOTES - OPMERKINGEN - REMARQUES - ANMERKUNGEN - NOTAS - NOTE - 

ȈǾȂǼǿȍȈǼǿȈ

 - NOTLAR - 

ɉɊɂɆȿɑȺɇɂə

FXCQ-A

Cooling Capacity

TC: Total capacity; kW

SHC: Sensible heat capacity; kW

1

‡

This table is for the selection of indoor equipment. 

‡

Deze tabel is bedoeld voor het kiezen van de binnenunit.

‡

Ce tableau concerne la sélection de l’équipement intérieur. 

‡

Diese Tabelle ist für die Auswahl der Innenanlagen. 

‡

Esta tabla es para seleccionar el equipo interior. 

‡

Usare questa tabella per la selezione delle apparecchiature interne. 

‡ ǹȣIJȩȢȠʌȓȞĮțĮȢʌȡȠȠȡȓȗİIJĮȚȖȚĮIJȘȞİʌȚȜȠȖȒİıȦIJİȡȚțȠȪİȟȠʌȜȚıȝȠȪ
‡ %XWDEORLoQLWHHNLSPDQODUÕQÕQVHoLPLQH\|QHOLNWLU
‡ ɗɬɚɬɚɛɥɢɰɚɩɪɟɞɧɚɡɧɚɱɟɧɚɞɥɹɜɵɛɨɪɚɭɫɬɚɧɚɜɥɢɜɚɟɦɨɝɨɜɩɨɦɟɳɟɧɢɢɨɛɨɪɭɞɨɜɚɧɢɹ

2

‡

In the event that conditions differ due to the design requirements after system selection, actual operating ability of the indoor equipment will 
differ from that noted in the table because of changes in the outdoor air temperature and load factor. 

‡

Als nadat u het systeem hebt gekozen de voorwaarden afwijken van de ontwerpvereisten, dan zal het reële bedrijfsvermogen van de 
binnenunit afwijken van de in de tabel vermelde gegevens, wegens de afwijkende buitenluchttemperatuur en de belastingsfactor.

‡ 6LOHVH[LJHQFHVGHFRQFHSWLRQDSUqVODVpOHFWLRQGXV\VWqPHHQWUDvQHQWXQHPRGL¿FDWLRQGHVFRQGLWLRQVOHVFDSDFLWpVRSpUDWLRQQHOOHV

UpHOOHVGHO¶pTXLSHPHQWLQWpULHXUGLIIqUHQWGHFHOOHVLQGLTXpHVGDQVOHWDEOHDXHQUDLVRQGHODPRGL¿FDWLRQGHODWHPSpUDWXUHGHO¶DLU

extérieure et du facteur de charge. 

‡

Falls Bedingungen aufgrund der Konstruktionsanforderungen nach der Systemauswahl abweichen, dann weicht aufgrund der Änderungen 
der Außenlufttemperatur und des Lastfaktors die tatsächliche Betriebsfähigkeit der Innenanlage von der in der Tabelle aufgeführten ab. 

‡ (QFDVRGHTXHODVFRQGLFLRQHVGL¿HUDQGHELGRDORVUHTXLVLWRVGHGLVHxRWUDVVHOHFFLRQDUHOVLVWHPDODFDSDFLGDGGHIXQFLRQDPLHQWRUHDO

del equipo interior diferirá de la que se muestra en la tabla debido a los cambios de la temperatura de aire exterior y al factor de carga. 

‡

Nel caso in cui intervenissero dei cambiamenti nelle condizioni dovuti a requisiti di progettazione successivi alla selezione del sistema, 
la capacità operativa effettiva delle apparecchiature interne sarà diversa da quella indicata in tabella a causa della diversa temperatura 
dell’aria esterna e del fattore di carico.

‡ ȈIJȘȞʌİȡȓʌIJȦıȘʌȠȣȠȚıȣȞșȒțİȢįȚĮijȑȡȠȣȞȜȩȖȦIJȦȞĮʌĮȚIJȒıİȦȞıȤİįȚĮıȝȠȪȝİIJȐIJȘȞİʌȚȜȠȖȒıȣıIJȒȝĮIJȠȢȘʌȡĮȖȝĮIJȚțȒįȣȞĮIJȩIJȘIJĮ

IJȠȣİıȦIJİȡȚțȠȪİȟȠʌȜȚıȝȠȪșĮįȚĮijȑȡİȚĮʌȩIJȘȞĮȞĮijİȡȩȝİȞȘıIJȠȞʌȓȞĮțĮȜȩȖȦIJȦȞĮȜȜĮȖȫȞıIJȘȞİȟȦIJİȡȚțȒșİȡȝȠțȡĮıȓĮĮȑȡĮțĮȚıIJȠ
ıȣȞIJİȜİıIJȒijȠȡIJȓȠȣ

‡ 6LVWHPVHoLPLQGHQVRQUDWDVDUÕPJHUHNOHULQHGHQL\OHNRúXOODUÕQGH÷LúPHVLGXUXPXQGDGÕúKDYDVÕFDNOÕ÷ÕYH\NIDNW|UQGHNLGH÷LúLNOLNOHU

QHGHQL\OHLoHNLSPDQÕQJHUoHNoDOÕúPDNDSDVLWHVLWDEORGDEHOLUWLOHQGHQIDUNOÕRODFDNWÕU

‡ ȼɫɥɭɱɚɟɟɫɥɢɪɟɚɥɶɧɵɟɭɫɥɨɜɢɹɨɬɥɢɱɚɸɬɫɹɨɬɩɪɨɟɤɬɧɵɯɭɫɥɨɜɢɣɪɚɛɨɬɵɢɫɩɨɥɶɡɭɟɦɵɯɩɪɢɜɵɛɨɪɟɫɢɫɬɟɦɵɮɚɤɬɢɱɟɫɤɢɟ

ɯɚɪɚɤɬɟɪɢɫɬɢɤɢɭɫɬɚɧɚɜɥɢɜɚɟɦɨɝɨɜɩɨɦɟɳɟɧɢɢɨɛɨɪɭɞɨɜɚɧɢɹɛɭɞɭɬɨɬɥɢɱɚɬɶɫɹɨɬɭɤɚɡɚɧɧɵɯɜɬɚɛɥɢɰɟɜɫɥɟɞɫɬɜɢɟɢɡɦɟɧɟɧɢɹ
ɬɟɦɩɟɪɚɬɭɪɵɜɨɡɞɭɯɚɫɧɚɪɭɠɢɢɩɨɤɚɡɚɬɟɥɹɧɚɝɪɭɡɤɢ

3

‡

In this case, use the ability table for the indoor equipment selected and correct for the ratio of change in ability. 

‡

Gebruik in dat geval de vermogenstabel van de gekozen binneninstallatie en kies het juiste vermogen.

‡ /HFDVpFKpDQWXWLOLVHUOHWDEOHDXGHFDSDFLWpGHO¶pTXLSHPHQWLQWpULHXUVpOHFWLRQQHUHWFRUULJHUOHUDSSRUWGHPRGL¿FDWLRQGHFDSDFLWp
‡

Verwenden Sie in diesem Fall die Fähigkeit für die ausgewählte Innenanlage und korrigieren Sie das Verhältnis der Änderung in der 
Fähigkeit.

‡

En este caso, utilice la tabla de capacidades del equipo interior seleccionado y corrija la relación de cambio en capacidad. 

‡ ,QTXHVWRFDVRXVDUHODWDEHOODGHOOHFDSDFLWjSHUOHDSSDUHFFKLDWXUHLQWHUQHVHOH]LRQDWHHGDSSRUWDUHOHPRGL¿FKHGHOFDVRLQEDVHDOOD

percentuale di cambiamento di capacità.

‡ ȈİĮȣIJȒIJȘȞʌİȡȓʌIJȦıȘȤȡȘıȚȝȠʌȠȚȒıIJİIJȠȞʌȓȞĮțĮįȣȞĮIJȠIJȒIJȦȞȖȚĮIJȠȞİʌȚȜİȖȝȑȞȠİıȦIJİȡȚțȩİȟȠʌȜȚıȝȩțĮȚįȚȠȡșȫıIJİȖȚĮIJȘȞĮȞĮȜȠȖȓĮ

ĮȜȜĮȖȒȢıIJȘįȣȞĮIJȩIJȘIJĮ

‡ %XGXUXPGDVHoLOHQLoHNLSPDQLoLQNDSDVLWHWDEORVXQXNXOODQÕQYHNDSDVLWHGHNLGH÷LúLPRUDQÕQDJ|UHG]HOWPH\DSÕQ
‡ ȼɷɬɨɦɫɥɭɱɚɟɢɫɩɨɥɶɡɭɣɬɟɬɚɛɥɢɰɭɯɚɪɚɤɬɟɪɢɫɬɢɤɜɵɛɪɚɧɧɨɝɨɭɫɬɚɧɚɜɥɢɜɚɟɦɨɝɨɜɩɨɦɟɳɟɧɢɢɨɛɨɪɭɞɨɜɚɧɢɹɢɜɧɟɫɢɬɟ

ɧɟɨɛɯɨɞɢɦɭɸɩɨɩɪɚɜɤɭɧɚɢɯɢɡɦɟɧɟɧɢɟ

Summary of Contents for FXCQ-A

Page 1: ...Air Conditioning Technical Data 2 way blow ceiling mounted cassette EEDEN13 204 FXCQ A...

Page 2: ......

Page 3: ...ical Data 5 4 Safety device settings 6 Safety Device Settings 6 5 Options 7 Options 7 6 Capacity tables 8 Cooling Capacity Tables 8 Heating Capacity Tables 9 Capacity Correction Factor 10 7 Dimensiona...

Page 4: ...s close entirely when not in operation Improved comfort thanks to automatic air flow adjustment to required load Individual flap control one flap can be easily closed via the wired remote controller B...

Page 5: ...Q40HW1 BYBCQ63HW1 BYBCQ125HW1 Colour Fresh white 6 5Y 9 5 0 5 Dimensions Height mm 55 Width mm 1 070 1 285 1 740 Depth mm 700 Weight kg 10 11 13 Heat exchanger Rows Quantity 2 Fin pitch mm 1 2 Face ar...

Page 6: ...r fan motor heat 4 Voltage range units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits 5 Maximum allowable voltage range va...

Page 7: ...3 1 3 VRV Systems Indoor Unit 5 Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 3 Electrical data 3 1 Electrical Data...

Page 8: ...Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 1 4 VRV Systems Indoor Unit 6 4 Safety device settings 4 1 Safety Device Settings...

Page 9: ...3 1 5 VRV Systems Indoor Unit 7 Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 5 Options 5 1 Options...

Page 10: ...HOOHV UpHOOHV GH O pTXLSHPHQW LQWpULHXU GLIIqUHQW GH FHOOHV LQGLTXpHV GDQV OH WDEOHDX HQ UDLVRQ GH OD PRGL FDWLRQ GH OD WHPSpUDWXUH GH O DLU ext rieure et du facteur de charge Falls Bedingungen aufgru...

Page 11: ...HU RQVWUXNWLRQVDQIRUGHUXQJHQ QDFK GHU 6 VWHPDXVZDKO DEZHLFKHQ GDQQ ZHLFKW DXIJUXQG GHU bQGHUXQJHQ der Au enlufttemperatur und des Lastfaktors die tats chliche Betriebsf higkeit der Innenanlage von der...

Page 12: ...08 1 086 1 061 1 041 FXCQ32 TC 0 681 0 690 0 741 0 766 0 787 0 817 0 842 SHF 1 147 1 192 1 135 1 108 1 086 1 061 1 041 FXCQ40 TC 0 671 0 687 0 748 0 772 0 792 0 821 0 854 SHF 1 167 1 191 1 128 1 101 1...

Page 13: ...45 1 192 1 127 1 089 FXCQ32 TC 0 546 0 559 0 570 0 603 0 637 0 690 0 730 SHF 1 147 1 250 1 306 1 245 1 192 1 127 1 089 FXCQ40 TC 0 540 0 548 0 571 0 611 0 645 0 697 0 744 SHF 1 167 1 273 1 300 1 231 1...

Page 14: ...Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 1 7 VRV Systems Indoor Unit 12 7 Dimensional drawings 7 1 Dimensional Drawings...

Page 15: ...3 1 7 VRV Systems Indoor Unit 13 Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 7 Dimensional drawings 7 1 Dimensional Drawings...

Page 16: ...Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 1 8 VRV Systems Indoor Unit 14 8 Centre of gravity 8 1 Centre of Gravity...

Page 17: ...3 1 9 VRV Systems Indoor Unit 15 Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 9 Piping diagrams 9 1 Piping Diagrams...

Page 18: ...Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 1 10 VRV Systems Indoor Unit 16 10 Wiring diagrams 10 1 Wiring Diagrams Single Phase...

Page 19: ...3 1 11 VRV Systems Indoor Unit 17 Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 11 Sound data 11 1 Sound Pressure Spectrum...

Page 20: ...Indoor Unit 2 way blow ceiling mounted cassette FXCQ A 1 11 VRV Systems Indoor Unit 18 11 Sound data 11 1 Sound Pressure Spectrum...

Page 21: ...4 The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this leaflet to the best of i...

Reviews: