9 Relocation
Installation and operation manual
13
FXAA15~63AUV1B
VRV system air conditioner
3P622285-1B – 2020.10
If the system does NOT operate properly except for the above
mentioned cases and none of the above mentioned malfunctions is
evident, investigate the system in accordance with the following
procedures.
INFORMATION
Refer to the reference guide located on
www.daikineurope.com/support-and-manuals/product-
information/
for more troubleshooting tips.
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
9
Relocation
Contact your dealer for removing and reinstalling the total unit.
Moving units requires technical expertise.
10
Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
For the installer
11
About the box
11.1
Indoor unit
11.1.1
To remove the accessories from the
indoor unit
8/9×, 2×
1×
1×
4×
1×
c
b
a
d
1×
e
f
a
Installation and operation manual
b
General safety precautions
c
Screw pack: M4×25L (8× for FXAA15~32, 9× for
FXAA40~63), 2× M4×12L
d
Tie wraps (1 large, 3 small)
e
Insulation tape
f
Paper pattern for installation
12
Unit installation
12.1
Preparing the installation site
Avoid installation in an environment with a lot of organic solvents
such as ink and siloxane.
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
12.1.1
Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation
in
a
commercial
and
light
industrial
environment.
▪
Wall strength.
Check whether the wall is strong enough to
support the weight of the unit. If there is a risk, reinforce the wall
before installing the unit.
▪
Spacing
. Mind the following requirements:
≤
120
≥90
≥30
a
b
≥2500
≥50
≥50
≥90
(mm)
a
Obstruction
b
Minimum distance to the floor
NOTICE
NEVER mount the indoor unit directly on the wall. Use the
attached mounting plate for installation.
Minimum floor area requirements
CAUTION
The total refrigerant charge in the system cannot exceed
the requirements for minimum floor area of the smallest
room that is served. For minimum floor area requirements
for indoor units, see the installation and operation manual
of the outdoor unit.