USER MANUAL
It is strictly forbidden to reproduce this manual, even partially
EN
2
FWECSA
Controller for units
GENERAL FEATURES
The FWECSA controller is designed to control all of
the system units in the Daikin range with multi-speed,
single-phase motor or coupled to an inverter for speed
modulation
.
The FWECSA controller system is
composed of
:
•
I/O board
containing the power supply circuit,
the
microprocessor system
and the connectors
(unscrewable) to connect the input and output devices;
•
User unit
composed of
graphic display
and keyboard
(six keys) equipped with clock and probe to read the
room temperature.
The connection between the I/O board and the
user unit is set up using the relative connectors
and a data transmission cable fitted with a pair
of twisted conductors and shielding.
The controller makes
serial communication
possible on two
types of networks:
•
External Supervisor System solution
: connection
to an external supervision system with MODBUS RTU
protocol on serial RS485;
•
SMALL solution
: connection of multiple FWECSA
controllers in two possible configurations:
- MASTER/SLAVE on serial RS485
- MASTER/SLAVE on CW (Conveyed Waves),
which can also be set up with External Supervisor
System solutions.
•
Mixed net solution
: connection of multiple FWECSA
controllers on different levels :
- MASTER/SLAVE on serial RS485 (external
supervisor system or FWECSA),directions to the
slaves RS485 (called zone MASTER)
- zone MASTER FWECSA , receiving directions from
NET MASTER RS485,transmitting directions to
SLAVES OC
- NET SLAVES OC, working exactly to the ZONE
MASTER
MAIN FUNCTIONS
•
Automatic
or manual
fan speed variation (selected
from the keyboard);
•
Management of ON/OFF or modulating valves
for two
or four-piped systems.
•
SUPPORTING electric heater control,
used during
heating;
•
SUMMER/WINTER mode switch
(= cooling/heating)
in four possible ways:
- manually, from the keyboard;
- manually, remotely (from digital input);
- automatically, depending on water temperature;
- automatically, depending on air temperature.
•
dehumidification function control;
•
operation with TIME SLOTS.
It is also supplied with:
•
External pre-consensus digital input
(for example:
window contact, remote ON/OFF, presence sensor, etc.)
that can enable or disable unit operation (contact logic:
see board configuration parameters);
•
Digital switching input
Remote centralised Cooling/
Heating
(contact logic: see board configuration
parameters);
•
Digital input
to enable
ECONOMY
function from
remote control (contact logic: see board configuration
parameters);
•
Water temperature probe
(accessory), one or two
(optional with 4-pipe systems);
•
STANDARD room air temperature probe
(installed
inside the user unit)
;
•
Remote room air probe
(accessory) that can be used,
if connected, in place of the standard one installed in
the user interface;
•
Remote relative room air humidity probe
(accessory);
•
A completely configurable digital output
(dry contact).
Summary of Contents for FWECSA
Page 270: ...FC66003946 Rev 00 FWECSA 01 03 02 04 ...
Page 271: ...FC66003946 Rev 00 FWECSA 05 07 09 06 08 10 ...
Page 272: ...FC66003946 Rev 00 FWECSA 11 13 15 12 14 16 ...
Page 273: ...FC66003946 Rev 00 FWECSA 17 18 ...
Page 274: ...FC66003946 Rev 00 FWECSA 19 ...
Page 275: ...FC66003946 Rev 00 FWECSA 19 ...
Page 276: ...FC66003946 Rev 00 FWECSA NOTE ...
Page 277: ...FC66003946 Rev 00 FWECSA NOTE ...
Page 278: ...FC66003946 Rev 00 FWECSA NOTE ...
Page 279: ...FC66003946 Rev 00 FWECSA NOTE ...