FWEC1
Standard electronic controller
FC66002763
GENERAL CHARACTERISTICS
LCD controller has been designed to govern the operation
of Daikin indoor units with single-phase multispeed
asynchronous motor.
MAIN FUNCTIONS AND FEATURES:
■
Air temperature adjustment through automatic variation
of fan speed;
■
Regulation of air temperature via fan on-off control (fan
runs at a
fi
xed speed),
■
Control of On-Off valves for two or four-pipe systems
■
Control of heating element for auxiliary heating.
■
Cooling/heating switching in the following modes:
-
local manual switching
-
remote, manual (centralised);
-
automatic, depending on water temperature
-
automatic, depending on air temperature
Additional features include:
■
Digital input 1 – Clean contact for remote centralised
switching of cooling/heating function (contact logic: see
con
fi
guration parameters of board).
■
Digital input 2 - Clean contacts for external activation (e.g.
window contact, remote ON/OFF, occupancy sensor, etc.)
which may enable or disable unit operation (contact logic:
see con
fi
guration parameters of board)
■
Remote water temperature sensor (FWTSK)
■
Remote air sensor (FWTSK) (this sensor, if present, is used
in place of the internal one for the measurement of room
temperature).
The control panel is composed of:
■
LCD display
■
Keyboard
LCD DISPLAY (SEE FIGURE 1)
(1) room
temperature
(2)
Thermostat / fan status
(3) Set
temperature
AUTO
Automatic ventilation logic
Fan
speed
Operation mode: Cooling. When
fl
ashing it indicates
that water circuit is not enabled to fan ventilation.
Operation mode: Heating. When
fl
ashing it indicates
that water circuit is not enabled to fan ventilation.
Economy option enabled
Alarm
triggered
Minimum Temperature Control
Valve
open
Heating element. If the symbol
fl
ashes it means that
the heating element is on; if steadily lit it means only
that the heating element has been selected
____________________________________________________________
The appliance is not to be used by children or person
with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction.
Children being supervised not to play with appliance
Keyboard (see fi gure 2)
____________________________________________________________
KEYBOARD (SEE FIGURE 2)
On/Off
key:
Thermostat
On/Off. During the
procedure of parameter modi
fi
cation, it permits to
return to normal operating conditions
Up
and
Down
keys: changing of thermostat
setting temperature (Heating :[5.0-30.0°C],
Cooling: [10.0-35.0°C]). During the procedure of
parameter modi
fi
cation, they are used to select the
parameters or to change their value
SEL
key: in the heating mode, the electric heating
element can be selected as auxiliary function
Mode
key: selection of Heating/Cooling operating
mode
Fan
key: selection of operating speed
EC
key: selection of Economy mode
ACTIVE KEY COMBINATIONS
With OFF thermostat: access to the parameter con
fi
guration
procedure
With ON thermostat: display of current water temperature
Selection of Minimum air temperature function
BOARD CONFIGURATION
The board can be con
fi
gured according to the type of unit/
system to be governed by changing some parameters.
PARAMETER LIST
■
P00
= controller con
fi
guration (see “Available con
fi
gurations”)
to select the type of unit to be governed.
■
P01
= type of controller installation
-
000
: on the unit
-
001
: wall mounted
■
P02
= (not used)
■
P03
= neutral zone [20-50°C/10]; parameter used in case of
con
fi
gurations with automatic cooling/heating changeover
according to air temperature.
Summary of Contents for FWEC1
Page 2: ...1 3 2 1 2 3 ...
Page 3: ...6 4 5 ...
Page 4: ...NOTES ...
Page 105: ...NOTES ...
Page 106: ...FC66002487 FC66002491 1 2 ...
Page 107: ...FWL M V FWL M V FWD FWB EPIMSB6 FC66002493 UT66000879 3 4 ...
Page 108: ...EPIB6 UT66000880 UT66000881 5 6 ...
Page 109: ...UT66000882 EPIB6 UT66000883 7 8 ...
Page 110: ...UT66000884 EPIB6 UT66000885 9 10 ...
Page 111: ...UT66000886 11 NOTES ...
Page 112: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002763 ...