background image

3

Read Before Operation

Read Before Operation

Safety Precautions

Read the precautions in this manual carefully 

before operating the unit.

This appliance is filled with R32.

• 

Keep this manual where the user can easily find it.

• 

The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding 
safety. Be sure to observe all precautions without fail.

 WARNING

Failure to follow these instructions properly may result in personal injury or loss of life.

 CAUTION

Failure to observe these instructions properly may result in property damage or personal injury, 

 

which may be serious depending on the circumstances.

Never attempt.

Be sure to follow the 
instructions.

Be sure to establish an earth 
connection.

• 

After reading, keep this manual in a convenient place so that you can refer to it whenever necessary. If the equipment is 
transferred to a new user, be sure also to hand over the manual.

 WARNING

• 

Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.

• 

The appliance must be stored in a room without continuously operating ignition sources (for example: open flames, an 

operating gas appliance or an operating electric heater).

• 

Do not pierce or burn.

• 

Be aware that refrigerants may not contain an odour. 

• 

The appliance must be installed, operated and stored in a room with a floor area larger than –* m

2

 for FTXV22/28/36,1.9 m

2

 

for FTXV41/50, 2.5 m

2

 FTXV60, 3.5 m

2

 FTXV71, 6.2 m

2

 FTXV80/90.

 

* Since the maximum refrigerant charge of the models is below 1.22kg, it does not have any limitation for the minimum floor area.

 

Maintain an installation height of 1.8m or more from the floor surface to the bottom of the appliance. If the size of the room 

where the appliance is to be installed has less than the indicated minimum floor area, install it in a well ventilated room.

• 

To avoid fire, explosion or injury, do not operate the unit when harmful gases (e.g. flammable or corrosive) are detected near the unit.

• 

Be aware that prolonged, direct exposure to cool or warm air from the air conditioner, or to air that is too cool or too warm, 

can be harmful to your physical condition and health.

• 

Do not place objects, including rods, your fingers, etc., in the air inlet or outlet. Product damage or personal injury may 

result due to contact with the air conditioner’s high-speed fan blades.

• 

Do not attempt to repair, dismantle, reinstall or modify the air conditioner yourself as this may result in water leakage, 

electric shock or fire hazards.

• 

Do not use flammable spray near the air conditioner, or otherwise fire may result.

• 

Do not use a refrigerant other than the one indicated on the outdoor unit (R32) when installing, moving or repairing. Using 

other refrigerants may cause trouble or damage to the unit, and personal injury.

• 

To avoid electric shock, do not operate with wet hands.

• 

Beware of fire in case of refrigerant leakage. If the air conditioner is not operating correctly, i.e. not generating cool or warm 

air, refrigerant leakage could be the cause. Consult your dealer for assistance. The refrigerant within the air conditioner is 

safe and normally does not leak.

 

However, in the event of a leakage, contact with a naked burner, heater or cooker may result in generation of noxious gas. 

Do not use the air conditioner until a qualified service person confirms that the leakage has been repaired.

• 

Do not attempt to install or repair the air conditioner yourself. Improper workmanship may result in water leakage, electric 

shock or fire hazards. Please contact your local dealer or qualified personnel for installation and maintenance work.

• 

If the air conditioner is malfunctioning (giving off a burning odour, etc.), turn off power to the unit and contact your local 

dealer. Continued operation under such circumstances may result in a failure, electric shock or fire hazards.

• 

Be sure to install an earth leakage circuit breaker. Failure to install an earth leakage circuit breaker may result in electric shock or fire.

• 

Be sure to earth the unit. Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. 

 

Imperfect earthing may result in electric shock.

 CAUTION

• 

Do not use the air conditioner for purposes other than those for which it is intended. Do not use the air conditioner for 

cooling precision instruments, food, plants, animals or works of art as this may adversely affect the performance, quality 

and/or longevity of the object concerned.

• 

Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects.

• 

Do not place appliances that produce naked flames in places exposed to the airflow from the unit as this may impair 

combustion of the burner.

• 

Do not block the air inlets nor outlets. Impaired airflow may result in insufficient performance or trouble.

01_EN_3P697657-1.indd   3

30-Nov-22   3:47:42 PM

Summary of Contents for FTXV22XVLT

Page 1: ...TION MANUAL MODELS FTXV22XVLT FTXV28XVLT FTXV36XVLT FTXV41XVLT FTXV50XVLT FTXV60XVLT FTXV71XVLT FTXV80XVLT FTXV90XVLT DAIKIN ROOM AIR CONDITIONER DAIKIN English 00_CV_3P697657 1 indd 1 31 Oct 22 2 57...

Page 2: ...rhood Page 21 INTELLIGENT EYE The INTELLIGENT EYE sensor detects human movement in a room If no one is in the room for more than 20 minutes the operation automatically changes to energy saving operati...

Page 3: ...ore Operation 9 Basic Operation AUTO DRY COOL HEAT FAN ONLY Operation 10 Adjusting the Airflow Rate 12 Adjusting the Airflow Direction 13 Useful Functions MOLD PROOF Operation 14 FLASH STREAMER AIR CL...

Page 4: ...conditioner s high speed fan blades Do not attempt to repair dismantle reinstall or modify the air conditioner yourself as this may result in water leakage electric shock or fire hazards Do not use f...

Page 5: ...ou may topple over or injury yourself Locate the remote controller in places out of reach of children The wrong operation of the remote controller may result in injury To avoid oxygen depletion ensure...

Page 6: ...oor unit ON OFF switch and OPERATION lamp Green Press this switch once to start operation Press once again to stop it For the operation mode setting refer to the following table Mode Temperature setti...

Page 7: ...ackside of the front panel Fixing tab Panel support plate Outdoor temperature sensor back Earth terminal inside Refrigerant pipes and inter unit wire Drain hose Deodorizing filter enzyme blue Streamer...

Page 8: ...el Fixing tab Panel support plate Outdoor temperature sensor back Refrigerant pipes and inter unit wire Drain hose Deodorizing filter enzyme blue Streamer unit inside Prevents mold and allergens with...

Page 9: ...EL button Cancels the timer setting Page 22 23 Model name ARC480A80 Display LCD Displays the current settings In this illustration each section is shown with its displays on for the purpose of explana...

Page 10: ...s accelerated owing usage conditions signal reception may decline before the LCD begins blinking The batteries supplied with the remote controller are for initial operation The batteries may run out i...

Page 11: ...ct is insufficient it is recommended to use another heating appliance in combination with the air conditioner The heat pump system heats the room by circulating hot air around all parts of the room Af...

Page 12: ...ise the temperature and press to lower the temperature Each pressing of the button changes the temperature by 0 5 C COOL operation HEAT operation AUTO operation DRY FAN ONLY operation 18 0 32 0 C 10 0...

Page 13: ...s a small amount of electricity even while it is not operating Adjusting the Airflow Rate You can adjust the airflow rate to increase your comfort To adjust the airflow rate setting Press Each pressin...

Page 14: ...d appear on the LCD The flaps and louvres move in turn To cancel 3 D airflow press either or again The flaps or louvres will stop moving To set the flaps or louvres at the desired position This functi...

Page 15: ...unit is turned off using the OFF TIMER MOLD PROOF operation is a function which reduces the spread of mold by using FAN operation to lower the humidity inside the indoor unit To automatically operati...

Page 16: ...r discharge This is a type of plasma discharge comprising high speed electrons with a high oxidative capacity that is released within the unit It decomposes odours and harmful gases The high speed ele...

Page 17: ...up COMFORT AIRFLOW Operation The flow of air will be in the upward direction while in COOL DRY operation and in the downward direction while in HEAT operation which will provide a comfortable wind th...

Page 18: ...place large objects near the INTELLIGENT EYE sensor Also keep heating units and humidifiers outside the sensor s detection area This sensor can detect undesirable objects Do not hit or violently push...

Page 19: ...peration decreases the airflow rate slightly in FAN operation only NOTE Notes on INTELLIGENT EYE operation Application range is as follows 90 55 7m 55 Vertical angle 90 Side view Horizontal angle 110...

Page 20: ...the capacity of the air conditioner if the air conditioner is already in operation with its maximum capacity demonstrated In COOL HEAT and AUTO operation To maximise the cooling heating effect the ca...

Page 21: ...TE Notes on ECONO operation This operation is performed with lower power and therefore may not provide a sufficient cooling heating effect Pressing causes the settings to be cancelled and disappears f...

Page 22: ...ation cannot be used at the same time Priority is given to the function of whichever button is pressed last Even the operation is stopped by using the remote controller or the indoor unit ON OFF switc...

Page 23: ...set Press appears on the LCD Each pressing of changes the time setting by 1 hour The time can be set between 1 and 12 hours The TIMER lamp lights orange Display To cancel Press disappears from the LCD...

Page 24: ...ting by 1 hour The time can be set between 1 and 12 hours The TIMER lamp lights orange Display To cancel Press disappears from the LCD The TIMER lamp goes off ON OFF TIMER combination To combine A sam...

Page 25: ...lity filter enzyme blue with PM2 5 without frame BAFP094A43 set of 2 BAFP094A47 set of 3 Deodorizing filter enzyme blue without frame BAFP094A41 set of 2 BAFP094A45 set of 3 Dust collection filter PM...

Page 26: ...t is recommended to clean the air filters every 2 weeks If the dust does not come off easily Wash the air filters with neutral detergent thinned with lukewarm water then dry them up in the shade Be su...

Page 27: ...ilter can be renewed by washing it with water once every 6 months and we recommend replacing it once every 3 years Do not wiring out the filter when removing water from it Air quality filter enzyme bl...

Page 28: ...ler We recommend periodical maintenance In certain operating conditions the inside of the air conditioner may get foul after several seasons of use resulting in poor performance It is recommended to h...

Page 29: ...nt control valves or the electrical parts operate Clopping sound This sound is heard from the inside of the air conditioner when the exhaust fan is activated while the room doors are closed Open the w...

Page 30: ...m up Case Description what to check Air does not come out In HEAT operation The air conditioner is warming up Wait for about 1 to 4 minutes During defrosting operation hot air does not flow out of the...

Page 31: ...OFF button remains functional Other electric devices start operating If the remote controller activates other electric devices move them away or consult your dealer Air has an odour Case Description w...

Page 32: ...breaker a fuse or the earth leakage circuit breaker cuts off the operation frequently A switch or a button often fails to work properly There is a burning smell Water leaks from the indoor unit Turn...

Page 33: ...TURE SENSOR C9 FAULTY SUCTION AIR TEMPERATURE SENSOR CC FAULTY HUMIDITY SENSOR OUTDOOR UNIT EA COOLING HEATING SWITCHING ERROR E1 CIRCUIT BOARD FAULT E5 OL STARTED E6 FAULTY COMPRESSOR START UP E7 DC...

Page 34: ...1 16 21 20 17 15 14 02_TW_3P697657 1 indd 1 30 Nov 22 3 44 48 PM...

Page 35: ...2 20 3 5 9 10 12 13 14 15 16 17 19 20 21 22 24 FAQ 28 29 33 02_TW_3P697657 1 indd 2 30 Nov 22 3 44 50 PM...

Page 36: ...3 R32 m2 FTXV22 28 36 1 9m2 FTXV41 50 2 5m2 FTXV60 3 5m2 FTXV71 6 2m2 FTXV80 90 1 22 1 8m R32 02_TW_3P697657 1 indd 3 30 Nov 22 3 44 51 PM...

Page 37: ...4 1m 1m 02_TW_3P697657 1 indd 4 30 Nov 22 3 44 52 PM...

Page 38: ...5 13 13 17 18 25 0 22 23 14 15 LAN LAN LAN BRP084C45 15 14 22 23 02_TW_3P697657 1 indd 5 30 Nov 22 3 44 52 PM...

Page 39: ...6 15 FTXV22 28 36 41 50 60 71 02_TW_3P697657 1 indd 6 30 Nov 22 3 44 53 PM...

Page 40: ...7 15 FTXV80 90 02_TW_3P697657 1 indd 7 30 Nov 22 3 44 54 PM...

Page 41: ...8 ARC480A80 LCD 10 10 11 17 21 19 15 23 22 7m 7m 10 12 20 13 14 16 20 23 02_TW_3P697657 1 indd 8 30 Nov 22 3 44 55 PM...

Page 42: ...9 1 AAA LR03 LCD LCD 1 1 2 AAA LR03 2 3 1 2 3 26 02_TW_3P697657 1 indd 9 30 Nov 22 3 44 59 PM...

Page 43: ...10 LCD LCD LCD LCD LCD 02_TW_3P697657 1 indd 10 30 Nov 22 3 45 02 PM...

Page 44: ...11 0 5 18 0 32 0 10 0 30 0 18 0 30 0 02_TW_3P697657 1 indd 11 30 Nov 22 3 45 02 PM...

Page 45: ...12 26 0 28 0 20 0 24 0 2 25 1 5 1 02_TW_3P697657 1 indd 12 30 Nov 22 3 45 03 PM...

Page 46: ...13 LCD LCD 3D LCD 3D 3D LCD 3D 3D 02_TW_3P697657 1 indd 13 30 Nov 22 3 45 06 PM...

Page 47: ...14 2 LCD 2 LCD 2 LCD 60 02_TW_3P697657 1 indd 14 30 Nov 22 3 45 07 PM...

Page 48: ...15 LCD LCD 1 1 02_TW_3P697657 1 indd 15 30 Nov 22 3 45 09 PM...

Page 49: ...16 LCD LCD 02_TW_3P697657 1 indd 16 30 Nov 22 3 45 10 PM...

Page 50: ...17 20 LCD LCD 02_TW_3P697657 1 indd 17 30 Nov 22 3 45 12 PM...

Page 51: ...18 20 20 2 2 2 30 1 1 90 55 7m 55 90 110 7m 7m 23 02_TW_3P697657 1 indd 18 30 Nov 22 3 45 13 PM...

Page 52: ...19 LCD 20 LCD LCD 2 5 02_TW_3P697657 1 indd 19 30 Nov 22 3 45 14 PM...

Page 53: ...20 LCD LCD LCD 02_TW_3P697657 1 indd 20 30 Nov 22 3 45 15 PM...

Page 54: ...21 LCD LCD 02_TW_3P697657 1 indd 21 30 Nov 22 3 45 16 PM...

Page 55: ...22 LCD 1 1 12 LCD 02_TW_3P697657 1 indd 22 30 Nov 22 3 45 17 PM...

Page 56: ...23 0 5 2 LCD 1 1 12 LCD LCD 1 7 2 3 02_TW_3P697657 1 indd 23 30 Nov 22 3 45 19 PM...

Page 57: ...22 28 36 41 50 60 71 FTXV80 90 PM2 5 BAFP094A43 2 BAFP094A47 3 BAFP094A41 2 BAFP094A45 3 PM 2 5 BAFP046A41 2 BAFP046A43 3 KAF970A46 2 KAF970A48 3 6 3 26 26 PM2 5 PM 2 5 6 26 02_TW_3P697657 1 indd 24 3...

Page 58: ...25 1 2 1 2 3 2 4 5 02_TW_3P697657 1 indd 25 30 Nov 22 3 45 21 PM...

Page 59: ...26 24 1 25 2 1 25 2 4 3 3 1 10 15 3 2 6 3 PM2 5 PM 2 5 6 4 02_TW_3P697657 1 indd 26 30 Nov 22 3 45 22 PM...

Page 60: ...27 1 14 2 3 25 4 02_TW_3P697657 1 indd 27 30 Nov 22 3 45 22 PM...

Page 61: ...28 FAQ 4 12 3 02_TW_3P697657 1 indd 28 30 Nov 22 3 45 23 PM...

Page 62: ...29 32 3 32 1 1 4 1 3 15 1 20 21 02_TW_3P697657 1 indd 29 30 Nov 22 3 45 25 PM...

Page 63: ...30 AAA LR03 9 LCD AAA LR03 9 LCD AAA LR03 LCD 10 0 46 0 18 0 32 0 80 15 0 24 0 10 0 30 0 02_TW_3P697657 1 indd 30 30 Nov 22 3 45 25 PM...

Page 64: ...31 3 02_TW_3P697657 1 indd 31 30 Nov 22 3 45 26 PM...

Page 65: ...32 1 5 2 2 5 1 00 UA U0 U2 U4 A1 PCB A5 A6 C4 C9 CC EA E1 E5 E6 E7 E8 F3 F6 F8 H0 H6 H8 H9 J3 J6 L3 L4 L5 P4 02_TW_3P697657 1 indd 32 30 Nov 22 3 45 26 PM...

Page 66: ...8 4 7 6 3 W 440 600 780 995 1370 COP W W 5 00 4 67 4 49 4 12 3 65 CSPF kWh kWh 6 82 6 47 6 68 6 37 5 96 CNS W 2700 3400 3800 4700 6000 kcal h 2320 2920 3270 4040 5160 A 2 7 3 7 4 0 5 0 7 1 W 540 750 8...

Page 67: ...9 8 10 0 11 3 W 1580 2090 2120 2400 COP W W 3 80 3 44 3 77 3 63 CSPF kWh kWh 6 15 5 75 5 88 5 62 CNS W 7000 8000 9000 9500 kcal h 6020 6880 7740 8170 A 8 2 9 1 12 4 13 7 W 1740 1940 2640 2900 1 220V 6...

Page 68: ...https www daikin com The two dimensional bar code is a manufacturing code 3P697657 1 M22N056 2211 HT 00_CV_3P697657 1 indd 2 31 Oct 22 2 57 18 PM...

Reviews: