12
English
Indoor Unit Installation
4.
Wiring
1) Strip wire ends (15mm).
2) Match wire colours with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the
corresponding terminals.
3) Connect the earth wires to the corresponding terminals.
4) Pull wires to make sure that they are securely latched up, then retain wires with wire retainer.
5) Shape the wires so that the service lid fits securely, then close service lid.
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electri-
cal shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
5.
Drain piping
1)Connect
the drain
hose, as
described
right.
2)Remove
the air filters
and pour
some water
into the
drain pan to
check the
water flows
smoothly
3)If drain hose
extension or
embedded
drain piping is
required, use
appropriate
parts that
match the
hose front end.
[Figure of hose
front end
4)When extending the drain hose, use a commercially
available extension hose with an inner diameter of
16mm. Be sure to thermally insulate the indoor section
of the extension hose.
5)When connecting a rigid polyvinyl chloride pipe
(nominal diameter 13mm) directly to the drain hose
attached to the indoor unit as with embedded piping
work, use any commercially available drain socket
(nominal diameter 13mm) as a joint.
Terminal block
Electrical component box
Wire retainer
Use the specified
wire type.
Shape wires so that the
service lid will fit securely.
Inter-unit wire
4-core 1.5mm² or more
H05RN
Firmly fix the wires with
the terminal screws.
Outdoor unit
Indoor
unit
Firmly secure wire retainer so that
wires sustain no external stress.
Firmly fix the wires with
the terminal screws.
The drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
Indoor unit
drain hose
Extension drain hose
Heat insulation tube
(field supply)
Drain hose supplied
with the indoor unit
Commercially available drain
socket
(nominal diameter 13mm)
Commercially available rigid
polyvinyl chloride pipe
(nominal diameter 13mm)
Drain hose supplied
with the indoor unit
3PEN482320-6B.book Page 12 Wednesday, July 12, 2017 2:30 PM