6 Piping installation

Installation manual

6

FTXTA30B2V1B(W)(B)

Daikin room air conditioner

3P482320-12U – 2021.03

5.2.3

To remove the pipe port cover

INFORMATION

To  connect  the  piping  on  right-side,  right-bottom,  left-side
or left-bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.3

Connecting the drain piping

5.3.1

To connect the piping on right side, right-
back, or right-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.

2

Wrap  the  drain  hose  and  the  refrigerant  pipes  together  using
insulation tape.

A

B

a b

A

Right-side piping

B

Right-bottom piping

C

Right-back piping

a

Remove the pipe port cover here for right side piping

b

Remove the pipe port cover here for right-bottom piping

5.3.2

To connect the piping on left side, left-
back, or left-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Remove  the  insulation  fixing  screw  on  the  right  side  and
remove the drain hose.

2

Remove the drain plug on the left side and attach it to the right
side.

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant piping bottom side using
adhesive vinyl tape.

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping

b

Remove the pipe port cover here for left-bottom piping

5.3.3

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

Summary of Contents for FTXTA30B2V1BB

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXTA30B2V1BW FTXTA30B2V1BB ...

Page 2: ...cal data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 10 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for...

Page 3: ... site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cabl...

Page 4: ...edical equipment E g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause faulty behaviour of the equipment Microwave oven It may affect wireless LAN communications 4 2 2 Basic parameters Parameter Value Frequency range 2400 MHz 2483 5 MHz Radio protocol IEEE ...

Page 5: ... a a a a h 610 605 555 k j i a Recommended mounting plate fixing spots g Value for tape measure b Pocket for the pipe port cover h Position for tape measure at symbol c Use tape measure as shown i Drain hose d Tabs for placing a spirit level j Liquid pipe e Unit center k Gas pipe f Hole for embedded piping Ø65 mm 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal boar...

Page 6: ...eft side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plu...

Page 7: ... the refrigerant piping DANGER RISK OF BURNING SCALDING 6 2 1 To connect the refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible 1 Connect refrigerant piping to the unit using flare connections 2 Insulate the refrigerant piping interconnection cable and drain hose on th...

Page 8: ...make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Cable clamp 5 Strip the wire ends approximately 15 mm 6 Match wire colours with terminal numbers on the indoor unit terminal blocks and firmly screw the wires to the corresponding terminals 7 Connect the earth wire to the corresponding terminal 8 Firmly fix the wires with t...

Page 9: ...tom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4 12L accessory 9 Configuration 9 1 To set a different address In case 2 indoor units are installed in 1 room different addresses for 2 user interfaces can be set 1 Remove the cover and the batteries from the user interf...

Page 10: ...nts or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 10 2 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite ...

Page 11: ...K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board Symbol Meaning PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circui...

Page 12: ...3P482320 12U 2021 03 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...

Reviews: