Daikin FTXTA30A2V1BW Installer'S Reference Manual Download Page 5

1 General safety precautions

Installer reference guide

5

FTXTA30A2V1BW
Split system air conditioner
4P518023-6E – 2019.04

(c)

Floor-standing unit (= Floor-standing unit)

1.2.3

Refrigerant

If applicable. See the installation manual or installer reference guide
of your application for more information.

NOTICE

Make  sure  refrigerant  piping  installation  complies  with
applicable  legislation.  In  Europe,  EN378  is  the  applicable
standard.

NOTICE

Make  sure  the  field  piping  and  connections  are  NOT
subjected to stress.

WARNING

During  tests,  NEVER  pressurize  the  product  with  a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).

WARNING

Take sufficient precautions in case of refrigerant leakage. If
refrigerant  gas  leaks,  ventilate  the  area  immediately.
Possible risks:

▪ Excessive  refrigerant  concentrations  in  a  closed  room

can lead to oxygen deficiency.

▪ Toxic  gas  may  be  produced  if  refrigerant  gas  comes

into contact with fire.

DANGER: RISK OF EXPLOSION

Pump  down  –  Refrigerant  leakage.

  If  you  want  to  pump

down  the  system,  and  there  is  a  leak  in  the  refrigerant
circuit:

▪ Do NOT use the unit's automatic pump down function,

with  which  you  can  collect  all  refrigerant  from  the
system  into  the  outdoor  unit. 

Possible  consequence:

Self-combustion  and  explosion  of  the  compressor
because of air going into the operating compressor.

▪ Use  a  separate  recovery  system  so  that  the  unit's

compressor does NOT have to operate.

WARNING

ALWAYS  recover  the  refrigerant.  Do  NOT  release  them
directly  into  the  environment.  Use  a  vacuum  pump  to
evacuate the installation.

NOTICE

After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.

NOTICE

▪ To avoid compressor breakdown, do NOT charge more

than the specified amount of refrigerant.

▪ When  the  refrigerant  system  is  to  be  opened,

refrigerant MUST be treated according to the applicable
legislation.

WARNING

Make  sure  there  is  no  oxygen  in  the  system.  Refrigerant
may only be charged after performing the leak test and the
vacuum drying.

▪ In  case  recharge  is  required,  see  the  nameplate  of  the  unit.  It

states the type of refrigerant and necessary amount.

▪ The unit is factory charged with refrigerant and depending on pipe

sizes  and  pipe  lengths  some  systems  require  additional  charging
of refrigerant.

▪ Only  use  tools  exclusively  for  the  refrigerant  type  used  in  the

system,  this  to  ensure  pressure  resistance  and  prevent  foreign
materials from entering into the system.

▪ Charge the liquid refrigerant as follows:

If

Then

A siphon tube is present

(i.e., the cylinder is marked with
"Liquid filling siphon attached")

Charge with the cylinder upright.

A siphon tube is NOT present

Charge with the cylinder upside
down.

▪ Open refrigerant cylinders slowly.

▪ Charge  the  refrigerant  in  liquid  form.  Adding  it  in  gas  form  may

prevent normal operation.

CAUTION

When  the  refrigerant  charging  procedure  is  done  or  when
pausing,  close  the  valve  of  the  refrigerant  tank
immediately.  If  the  valve  is  NOT  closed  immediately,
remaining  pressure  might  charge  additional  refrigerant.

Possible consequence: 

Incorrect refrigerant amount.

1.2.4

Brine

If applicable. See the installation manual or installer reference guide
of your application for more information.

WARNING

The selection of the brine MUST be in accordance with the
applicable legislation.

WARNING

Take  sufficient  precautions  in  case  of  brine  leakage.  If
brine  leaks,  ventilate  the  area  immediately  and  contact
your local dealer.

WARNING

The  ambient  temperature  inside  the  unit  can  get  much
higher than that of the room, e.g. 70°C. In case of a brine
leak,  hot  parts  inside  the  unit  can  create  a  hazardous
situation.

WARNING

The  use  and  installation  of  the  application  MUST  comply
with the safety and environmental precautions specified in
the applicable legislation.

1.2.5

Water

If applicable. See the installation manual or installer reference guide
of your application for more information.

NOTICE

Make  sure  water  quality  complies  with  EU  directive
98/83 EC.

Summary of Contents for FTXTA30A2V1BW

Page 1: ...Installer reference guide Split system air conditioner English Installer reference guide Split system air conditioner FTXTA30A2V1BW...

Page 2: ...4 4 Pipe bending guidelines 16 6 4 5 To flare the pipe end 16 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the electric...

Page 3: ...ted on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product cont...

Page 4: ...m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Page 5: ...e legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nameplate of...

Page 6: ...nt carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the curr...

Page 7: ...do and know to install the system Configuration What to do and know to configure the system after it is installed Commissioning What to do and know to commission the system after it is configured Han...

Page 8: ...53 EU This unit is considered as combined equipment according to the definition of Directive 2014 53 EU 4 3 1 Precautions when using the wireless adapter Do NOT use near Medical equipment E g persons...

Page 9: ...vapour may be present in the atmosphere Plastic parts may deteriorate and fall off or cause water leakage In places where the unit would be in the path of direct sunlight In bathrooms Sound sensitive...

Page 10: ...o the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 6 Installation...

Page 11: ...Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover NOTICE When closing the service cover make sure that the tightening torque does NOT exceed 1 4 0 2...

Page 12: ...ooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re install the cover first attach the electrical wiring box to the hooks close the electrical wiring box and re install the screw NOTI...

Page 13: ...rial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a...

Page 14: ...so it will NOT be pulled out of the drain pipe 50 mm To connect the piping on right side right back or right bottom INFORMATION The factory default is right side piping For left side piping remove th...

Page 15: ...l may dissolve and damage the system NOTICE Take the following precautions on refrigerant piping into account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g...

Page 16: ...the unit using flare connections Insulation Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c Interco...

Page 17: ...of practice 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide c a b d a Mounting plate accessory b Piece of packing material c Interconnection cable d Wire guide INFORMATION S...

Page 18: ...arking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT bend refrigeran...

Page 19: ...t of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Mak...

Page 20: ...m The wiring diagram is delivered with the unit located inside of the outdoor unit bottom side of the top plate 11 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring...

Page 21: ...lled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European national and local directives...

Page 22: ......

Page 23: ......

Page 24: ...4P518023 6E 2019 04 Copyright 2019 Daikin...

Reviews: