Installer reference guide

Split system air conditioner

English

Installer reference guide

Split system air conditioner

FTXTA30A2V1BW

Summary of Contents for FTXTA30A2V1BW

Page 1: ...Installer reference guide Split system air conditioner English Installer reference guide Split system air conditioner FTXTA30A2V1BW...

Page 2: ...4 4 Pipe bending guidelines 16 6 4 5 To flare the pipe end 16 6 4 6 To connect the refrigerant piping to the indoor unit 16 6 5 Connecting the electrical wiring 16 6 5 1 About connecting the electric...

Page 3: ...ted on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it might be necessary to provide a logbook with the product cont...

Page 4: ...m Floor standing units 1 8 x 2 2 m Wall mounted units 2 2 m Ceiling mounted units 3 Use the graph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160...

Page 5: ...e legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case recharge is required see the nameplate of...

Page 6: ...nt carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the curr...

Page 7: ...do and know to install the system Configuration What to do and know to configure the system after it is installed Commissioning What to do and know to commission the system after it is configured Han...

Page 8: ...53 EU This unit is considered as combined equipment according to the definition of Directive 2014 53 EU 4 3 1 Precautions when using the wireless adapter Do NOT use near Medical equipment E g persons...

Page 9: ...vapour may be present in the atmosphere Plastic parts may deteriorate and fall off or cause water leakage In places where the unit would be in the path of direct sunlight In bathrooms Sound sensitive...

Page 10: ...o the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 6 Installation...

Page 11: ...Pull out the service cover horizontally away from the unit a b a Service cover screw b Service cover NOTICE When closing the service cover make sure that the tightening torque does NOT exceed 1 4 0 2...

Page 12: ...ooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re install the cover first attach the electrical wiring box to the hooks close the electrical wiring box and re install the screw NOTI...

Page 13: ...rial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a...

Page 14: ...so it will NOT be pulled out of the drain pipe 50 mm To connect the piping on right side right back or right bottom INFORMATION The factory default is right side piping For left side piping remove th...

Page 15: ...l may dissolve and damage the system NOTICE Take the following precautions on refrigerant piping into account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g...

Page 16: ...the unit using flare connections Insulation Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insulation c Interco...

Page 17: ...of practice 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide c a b d a Mounting plate accessory b Piece of packing material c Interconnection cable d Wire guide INFORMATION S...

Page 18: ...arking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT bend refrigeran...

Page 19: ...t of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Mak...

Page 20: ...m The wiring diagram is delivered with the unit located inside of the outdoor unit bottom side of the top plate 11 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring...

Page 21: ...lled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European national and local directives...