SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT

R410A is a new HFC refrigerant which does not damage the 

ozone layer. The working pressure of this new refrigerant is 

1.6 times higher than conventional refrigerant (R22), thus 

proper installation/servicing is essential.

Never use refrigerant other than R410A in an air conditioner 

which is designed to operate with R410A.

POE or PVE oil is used as lubricant for R410A compressor, 

which  is  different  from  the  mineral  oil  used  for  R22 

compressor. During installation or servicing, extra precaution 

must be taken not to expose the R410A system too long 

to moist air. Residual POE or PVE oil in the piping and 

components can absorb moisture from the air.

To prevent mischarging, the diameter of the service port 

on the flare valve is different from that of R22.

Use tools and materials exclusively for refrigerant R410A. 

Tools exclusively for R410A are manifold valve, charging 

hose, pressure gauge, gas leak detector, flare tools, torque 

wrench, vacuum pump and refrigerant cylinder.

As  an  R410A  air  conditioner  incurs  higher  pressure 

than R22 units, it is essential to choose the copper pipes 

correctly. 

If the refrigerant gas leakage occurs during installation/

servicing, be sure to ventilate fully. If the refrigerant gas 

comes into contact with fire, a poisonous gas may occur.

When installing or removing an air conditioner, do not 

allow air or moisture to remain in the refrigerant cycle.

VACUUMING AND CHARGING

Vacuuming is necessary to eliminate all moisture and air from the system. 

Vacuuming The Piping And The Indoor Unit

Except  for  the  outdoor  unit  which  is  pre-charged  with 

refrigerant, the indoor unit and the refrigerant connection 

pipes must be air-purged because the air containing moisture 

that remains in the refrigerant cycle may cause malfunction 

of the compressor.

Remove the caps from the valve and the service port.

Connect the center of the charging gauge to the vacuum 

pump.

Connect the charging gauge to the service port of the 3-way 

valve.

Start the vacuum pump. Evacuate for approximately 30 

minutes. The evacuation time varies with different vacuum 

pump capacity. Confirm that the charging gauge needle has 

moved towards -760mmHg.

Caution

If the gauge needle does not move to -760mmHg, be sure 

to check for leakage at flare type connection of the indoor 

and outdoor unit and repair the leak before proceeding to 

the next step.

Close the valve of the changing gauge and stop the vacuum 

pump.

On the outdoor unit, open the suction valve (3 way) and 

liquid valve (2 way) (in anti-clockwise direction) with 4mm 

key for hexagon sacked screw.

Charge Operation

This operation must be done by using a gas cylinder and a 

precise weighing machine. The additional charge is topped-up 

into the outdoor unit using the suction valve via the service 

port.

Remove the service port cap.

Connect the low pressure side of the charging gauge to the 

suction service port center of the cylinder tank and close 

the high pressure side of the gauge. Purge the air from the 

service hose.

Start the air conditioner unit.

Open the gas cylinder and low pressure charging valve.

When  the  required  refrigerant  quantity  is  pumped  into 

the unit, close the low pressure side and the gas cylinder 

valve.

Disconnect the service hose from service port. Put back 

the service port cap.

Refrigerant Piping

Outdoor Unit 3 ways valve

Allen key

Service Port

Flare nut

HIGH PRESSURE GAUGE

GAUGE MANIFOLD

LOW PRESSURE GAUGE

HANDLE 

HI 

(ALWAYS CLOSED)

CHARGE HOSE

-760mmHg

HANDLE 

LO

CHARGE HOSE

VACUUM PUMP 

ADAPTER FOR 
COUNTER FLOW 

PREVENTION

CHECK VALVE

LIQUID VALVE

HIGH PRESSURE GAUGE

LOW PRESSURE GAUGE

GAUGE MANIFOLD

-760mmHg

HANDLE 

LO

HANDLE 

HI 

(ALWAYS CLOSED)

CHARGE HOSE

CHARGE HOSE

CHECK VALVE

LIQUID VALVE

GAS VALVE 

(3-WAY)

CONFIGURATION OF AIR 

PURGE BY CHARGING

GAS VALVE 

(3-WAY)

CONFIGURATION OF AIR 

PURGE BY CHARGING

1 IM-5WMYJR-1114(3)DK VZ-EN-418213   13

1 IM-5WMYJR-1114(3)DK VZ-EN-418213   13

5/20/15   9:00:34 AM

5/20/15   9:00:34 AM

Summary of Contents for FTXS25A

Page 1: ...9048788 Installation Manual R410A Split Series Manual de instalaci n Serie Split R410A English Espa ol CVR IM 5WMYJR 1114 3 DAIKIN VZ E1 1 CVR IM 5WMYJR 1114 3 DAIKIN VZ E1 1 5 20 15 10 56 48 AM 5 20...

Page 2: ...CVR IM 5WMYJR 1114 3 DAIKIN VZ E2 2 CVR IM 5WMYJR 1114 3 DAIKIN VZ E2 2 5 20 15 8 59 08 AM 5 20 15 8 59 08 AM...

Page 3: ...OTTOM FRONT GRILLE FIXED SCREWS INSIDE LOUVER SIGNAL RECEIVER INDOOR UNIT ON OFF SWITCH ROOM TEMPERATURE THERMISTOR INSIDE NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL OUTLINE AND DIMENSIONS Original...

Page 4: ...5mm Drain hose position Liquid pipe end Gas pipe end INSTALLATION PLATE 50 60 Recommended mounting plate retention spots 7 spots in all All dimensions are in mm Recommended mounting plate retention sp...

Page 5: ...Model A B C D E F G H I J K L M N O 50 855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 60 855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 All dimensions are in mm Dimension Model P Q...

Page 6: ...oing into suction of the unit This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage fluctuates greatly Do not install the units at area like hot spring or o...

Page 7: ...e or exhaust airflow follow the installation guidelines below For any of the below installation patterns the wall height on the exhaust side should be 1200mm or less Wall facing two sides More than 50...

Page 8: ...ight H please allow more space than the figure indicated in the above table Dimension A B C D Minimum Distance mm 300 1000 300 500 Condensed Water Disposal Of Outdoor Unit Heat Pump Unit Only There ar...

Page 9: ...STALLATION OF THE INDOOR UNIT Remove pipe port cover here for right bottom piping Bind coolant pipe and drain hose together with insulating tape Remove pipe port cover here for left side piping Remove...

Page 10: ...to the mounting plate How To Remove The Indoor Unit Push up the marked area at the lower part of the front grille to release the claws Mounting plate Mounting plate fixing screw 50 60 25 35 When stri...

Page 11: ...50 60 Min Allowable Length L m 3 3 Max Allowable Length L m 20 30 Max Allowable Elevation E m 10 10 Gas Pipe Size mm in 9 52 3 8 12 70 1 2 15 88 5 8 Liquid Pipe Size mm in 6 35 1 4 6 35 1 4 Equivalent...

Page 12: ...The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool See Figure III Fix the pipe firmly on the swaging block Match the centers of both the s...

Page 13: ...crew head Over tightening can damage the terminal screws Do not connect wire of different gauge to same terminal Keep wiring in an orderly manner Prevent the wiring from obstructing other parts and th...

Page 14: ...port Connect the center of the charging gauge to the vacuum pump Connect the charging gauge to the service port of the 3 way valve Start the vacuum pump Evacuate for approximately 30 minutes The evac...

Page 15: ...ure by switching automatically to either cool or heat mode according to the temperature set by the user Cool Heat Timer IR Receiver ON OFF switch IR Receiver INDICATOR LIGHTS ON to OFF 1 Long Beep OFF...

Page 16: ...panel at the 3 points 1 on each side and 1 in the middle The air filter have a symmetrical form in the horizontal direction 4 20 15 0 3 7 2 5 2 0 1 20 18 10 0 10 15 20 25 23 14 15 19 20 10 50 46 43 40...

Page 17: ...ean the filter 1 2 3 At least once every 2 weeks More frequently if necessary Indoor unit Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water below 40...

Page 18: ...timer has been set incorrectly If the fault persist after all these verifications please contact the air conditioner unit installer The air flow is too low 3 The air filter is dirty The doors or wind...

Page 19: ...ECHA IZQUIERDA DEBAJO DEBAJO TORNILLOS FIJADOS EN LA REJILLA FRONTAL INTERIOR REJILLA RECEPTOR DE SE ALES UNIDAD INTERIOR INTERRUPTOR DE ENCENDIDO APAGADO TEMPERATURA AMBIENTE TERMISTOR INTERIOR PLACA...

Page 20: ...e l quido Extremo del tubo de gas PLACA DE INSTALACI N 50 60 Puntos de retenci n recomendados en la placa de montaje 7 puntos en total Todas las dimensiones est n en mm Puntos de retenci n recomendado...

Page 21: ...94 60 14 133 8 10 299 B A Q P R S D O K L L M N F E C G H I J N 3 0 U T V Dimensi n Modelo A B C D E F G H I J K L M N O 50 855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 60 855 730 328 520 1...

Page 22: ...rita o deforme como resultado del calor excesivo o de una reacci n qu mica Cuandolaunidadseutiliceenlacocina evitequeentreharinaenla zona de aspiraci n de la unidad Esta unidad no es adecuada para su...

Page 23: ...l aire de entrada o salida de la unidad exterior siga las instrucciones de instalaci n de abajo Para cualquiera de los modelo de instalaci n la altura de la pared del lado de salida ha de ser de 1200m...

Page 24: ...a altura de la unidad H por favor dejar un mayor margen a la cifra indicada en la tabla anterior Dimensi n A B C D Distancia minima mm 300 1000 300 500 Disposici n Condensada Del Agua De La Unidad Al...

Page 25: ...o del tubo para la tuber a derecha inferior Ate conjuntamente el tubo de refrigerante y la manguera de drenaje con cinta aislante Saque de aqu la tapa del orificio del tubo para la tuber a izquierda S...

Page 26: ...Fuga de agua Incorrecto Incorrecto Tuber a De Desag e De Agua La tuber a de desag e de interior debe tener una pendiente descendente para lograr un vaciado uniforme Evite situaciones que puedan causar...

Page 27: ...N 25 35 50 60 Largo m n admisible L m 3 3 Largo m x admisible L m 20 30 Elevaci n M xima Permitida E m 10 10 Tama o de la tuber a de gas mm pulg 9 52 3 8 12 70 1 2 15 88 5 8 Tama o de la tuber a de l...

Page 28: ...erior en las tuber as de cobre La longitud exacta de la tuber a que sobresale de la cara de la matriz de abocinamiento se determina mediante una herramienta de abocinamiento V ase la Figura III Fije l...

Page 29: ...odas las cubiertas se fijen correctamente para evitar cualquier espacio Utilice terminales preformados para conectar los cables a la regleta de bornes de la fuente de alimentaci n Conecte los cables s...

Page 30: ...alibrador de carga al orificio de servicio de la v lvula de 3 v as Arranque la bomba de vac o Evacue aproximadamente durante 30 minutos El tiempo de evacuaci n var a seg n la capacidad de la bomba de...

Page 31: ...Condiciones De Operaci n Normales Y Condiciones De Operaci n Defectuosas De La Unidad De Enfriamiento Unidad De Calentamiento REFRESQ ESE CALOR TEMPORIZADOR AZUL ROJO VIOLETA Operaci n AZUL Modo de e...

Page 32: ...por los 3 puntos uno en cada extremo y otro en el centro El filtro de aire tiene forma sim trica en direcci n horizontal 4 MARGEN DE OPERACI N 20 15 0 3 7 2 5 2 0 1 20 18 10 0 10 15 20 25 23 14 15 19...

Page 33: ...lo menos una vez cada 2 semanas M s frecuentemente si es necesario Unidad interior Limpie cualquier suciedad o polvo de la rejilla o el panel con un trapo suave empapado deagua tibia a menos de 40 C...

Page 34: ...puertas y las ventanas est n abiertas La entrada y salida del aire est n obstruidas La temperatura elegida en el ajuste no es lo suficientemente alta El flujo de aire de descarge huele mal 4 Estos olo...

Page 35: ...CVR IM 5WMYJR 1114 3 DAIKIN VZ E6 6 CVR IM 5WMYJR 1114 3 DAIKIN VZ E6 6 5 20 15 8 59 12 AM 5 20 15 8 59 12 AM...

Page 36: ...s en el presente manual en cualquier momento y sin notificaci n previa CVR IM 5WMYJR 1114 3 DAIKIN VZ E7 7 CVR IM 5WMYJR 1114 3 DAIKIN VZ E7 7 5 20 15 8 59 12 AM 5 20 15 8 59 12 AM Zandvoordestraat 30...

Reviews: