Application Information
Outdoor Clearance
If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such as
substances may lead to failure of the unit.
• Where a wall or order obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the
installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Model: RXN25/35F
Wall facing one side
Wall facing two side
More than 50
Side View
Top View
Top View
Unit : mm
More than 50
More than 150
More than 50
More than 300
More than 50
More than 100
More
than 100
1200 or
less
More than 150
Wall facing three side
Model: RXN50/60C
ALL MODELS
Minimum Distance
A
300 mm
B
1000 mm
C
300 mm
D
500 mm
Return air
Discha
rge air
A
Obstacle
Obstacle
B
H/2
H
Return air
Service access
C
D
Obstacle
Obstacle