Field Settings
SiUS041829E
130
Part 7 Trial Operation and Field Settings
Caution
Reference
Wireless Remote
Controller
1. Slide down the cover and take it off.
2. Cut the address setting jumper J4.
Be careful not to cut the jumper J8.
Replace the remote controller if you cut a jumper unintentionally
.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
4.3 Jumper and Switch Settings
For the location of the jumper, refer to 18 page.
(R25252)
Jumper
on indoor
unit PCB
Function
When connected
(factory setting)
When cut
JB
Fan speed setting when
compressor stops for
thermostat OFF.
(effective only at cooling
operation)
The fan stops.
Fan speed setting;
Remote controller setting
JC
Power failure recovery
function
Auto-restart
The unit does not
resume operation after
recovering from a power
failure. Timer settings
are cleared.
Summary of Contents for FTXR-T Series
Page 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Page 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Page 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Page 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...