6
|
Installation
Installer reference guide
34
FTXP50~7 FTXF20~7 ATXF50~71A2V1B
Daikin room air conditioner
4P513661-8H – 2019.12
6.5.2 Precautions when connecting the electrical wiring
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
General safety precautions
▪
Preparation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3 mm between the contact
point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical
shock or fire.
WARNING
▪
Do NOT use locally purchased electrical parts inside the product.
▪
Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation
as such pipes will be very hot.
6.5.3 Guidelines when connecting the electrical wiring
Keep the following in mind:
▪
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
b
a
a
Stranded conductor wire
b
Round crimp-style terminal
▪
Use the following methods for installing wires: