Is the continuity measurement correct? Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next step.
No
123].
3.10.2 Repair procedures
To remove the reactor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
2
Open the compressor insulation.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
3
Remove the cover of the compressor wire terminals.
a
a
Compressor wire terminals cover
4
Disconnect the connector.
5
Remove the clip and remove the reactor from the compressor.
6
To install the reactor, see
123].
To install the reactor
1
Install the reactor in the correct location and install the clip.
2
Connect the reactor connector.
3
Install the cover of the compressor wire terminals.