TS13-01 Troubleshooting manual
37
F3
Description
Discharge pipe overheat
Supposed Cause
-
Refrigerant shortage
-
Four way valve malfunctioning
-
Discharge pipe thermistor defective
-
Outdoor PCB defective
-
Water mixed in the local piping
-
EXV defective
-
Stop Valve defective
Troubleshooting
F6
Description
Heat exchanger overheat
Supposed Cause
-
The installation space is not large enough
-
Faulty outdoor unit fan
-
Faulty EXV
-
Faulty defrost thermistor
-
Faulty stop valve
-
Dirty heat exchanger
-
Unit overcharge
-
Working out of operating limit