Daikin FTXN-LV Troubleshooting Manual Download Page 1

 

 

TS13-01 

 
        

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter Split 

Wall mounted Type L-Series 

 

 

 

 

 

 

 

Heat pump

Indoor unit: FTXN-LV  

Outdoor unit: RXN-LV

  

 

 

 

Troubleshooting 

Manual 

Summary of Contents for FTXN-LV

Page 1: ...TS13 01 Inverter Split Wall mounted Type L Series Heat pump Indoor unit FTXN LV Outdoor unit RXN LV Troubleshooting Manual...

Page 2: ...ality Efficiency Daikin DC Inverter compressor High Performance Daikin Inverter Controller 5 speed Step less Fan operation BioPro IAQ New Inverter only Remote Control Piping Length Elevation Model Max...

Page 3: ...unction kindly cut off the jumper J_AUTO as highlighted in attachment Please be informed that after disable auto random restart unit is not able to restart with last state memory after power resume fr...

Page 4: ...ndset The operating modes are Cool Heat Fan Auto Dry Cool Mode When Tr Ts 1 5 C Comp Indoor Fan and Outdoor Fan ON When Tr Ts 2 C Compressor and Outdoor Fan OFF Indoor Fan remains ON Tr Room Temperatu...

Page 5: ...oint compressor will stop FAN MODE Only High Medium and Low fan speeds are allowed When changing cool mode to fan mode the compressor will stop and OD fan stops based on fan OFF control Compressor onl...

Page 6: ...or once the valid data is received If the data communication line between indoor and outdoor disrupted for 15s continuously compressor will stop OD fan stop with fan OFF timer ID LED blinks error If t...

Page 7: ...peed control Also used for PMV overall current protection preheating operation control Heat sink Used for capturing heat sink temperature Suction pipe Used for EXV SH suction pipe SH protection contro...

Page 8: ...RESTART Factory pre set Allow unit to automatically resume the same operating mode it was in before a power failure 4 WAY VALVE CONTROL Change over switching is only carried out during operation OFF...

Page 9: ...igher fan speed with higher outdoor air temperature Heat mode Higher fan speed with lower outdoor air temperature When compressor stops fan OFF delay 30 seconds is carried out INDOOR COIL FREEZE PREVE...

Page 10: ...cation during startup To prevent liquid flood back to the compressor To limit starting current When compressor starts to rotate from OFF to ON compressor rotation is set to run gradually to each upper...

Page 11: ...rature T Limit Rotation Defrost control Fuzzy Control Based on temperature difference T current fan speed setting current indoor operating mode at every 30 seconds interval LIMIT ROTATION Determine fr...

Page 12: ...ar operating temperature current pressure Zone Control Stop Compressor is stopped when a certain limit reaches the stop zone for abnormality correction Drop Frequency will be dropped with a timer sett...

Page 13: ...uency is control to keep this temperature from going up further when it rises above a certain level If compressor discharge temperature 102 C 111 C for the first time this control starts and set the c...

Page 14: ...ll be reduced by another 1 step until total current falls between L2 and L3 This protection cut in when the input current exceeds L1 for 2 seconds RXN LV Compressor will stop and it is considered tota...

Page 15: ...Hz for every 120 minutes current rotation is remained EXV is fixed at current opening 50 pulse This control is reset after 5 minutes From indoor units When any error occurs indoor LED display will kee...

Page 16: ...zer will produce a long beep if the handset error code matched with unit error 4 A short and two consecutive beeps is Not the unit error 5 The code display will cancel itself if the button is not pres...

Page 17: ...etrieve error by using remote controller step Holding TIMER CANCEL Using wired handset BRC51A61 The error will show at the LCD display BRC51A61 can retrieved last state memory by Press SLEEP TIMER ACT...

Page 18: ...R CODE ERROR DESCRIPTION RXN50 60 LV1B RXN25 35LV1B 1 00 Normal 2 A1 INDOOR PCB ERROR 3 A3 DRAIN PUMP ABNORMAL x 4 A5 ANTIFREEZE PROTECTION 5 A6 INDOOR FAN MOTOR ABNORMAL 6 A7 AIR SWING MOTOR LOCK x 7...

Page 19: ...7 H0 COMPRESSOR SENSOR SYSTEM ABNORMAL x 18 H6 POSITION SENSOR ABNORMAL compressor 19 H8 AC CURRENT SENSOR ERROR 20 H9 OUTDOOR AIR THERMISTOR SHORT OPEN 21 J3 COMPRESSOR DISCHARGE PIPE THERMISTOR SHOR...

Page 20: ...TAGE OUT OF RANGE 29 U4 COMMUNICATION ERROR 30 UA INSTALLATION ERROR Error Code A1 Description Indoor unit PCB abnormality Supposed Cause 1 Faulty indoor PCB 2 Faulty connector connection at indoor Tr...

Page 21: ...TS13 01 Troubleshooting manual 21 Supposed Cause 1 Faulty drain pump or float switch 2 Improper drain piping work or drain pipe blockage Troubleshooting...

Page 22: ...on Anti freeze protection or High Pressure Control Supposed Cause 1 Indoor air filter heat exchanger block due to dust accumulation 2 Indoor air short circuit 3 Indoor coil thermistor faulty 4 Indoor...

Page 23: ...TS13 01 Troubleshooting manual 23...

Page 24: ...TS13 01 Troubleshooting manual 24...

Page 25: ...TS13 01 Troubleshooting manual 25 A6 Description Fan Motor or Related Abnormality Supposed Cause 1 Indoor fan motor winding short or the motor lead wire broken 2 Indoor PCB faulty Troubleshooting...

Page 26: ...n Indoor Coil Thermistor short open Supposed Cause 1 Thermistor connector faulty 2 Indoor PCB faulty Troubleshooting C9 Description Indoor Room Thermistor Short Open Supposed Cause 1 Thermistor connec...

Page 27: ...TS13 01 Troubleshooting manual 27...

Page 28: ...tor such as Noise Momentary voltage drop Momentary power failure 2 Damage of EEPROM 3 Faulty outdoor unit PCB Troubleshooting Check the outdoor condition Power on and off again Error Again Replace out...

Page 29: ...l 29 E3 Description High Pressure protection Supposed Cause 1 faulty high pressure switch connector or wire harness 2 Indoor filter outdoor coil dirty 3 Outdoor fan not running unit overcharge stop va...

Page 30: ...l 30 E4 Description Low Pressure protection Supposed Cause 1 faulty high pressure switch connector or wire harness 2 Indoor filter outdoor coil dirty 3 Outdoor fan not running unit overcharge stop val...

Page 31: ...Description Compressor Overload detected through compressor OL Supposed Cause Refrigerant Shortage 4 way valve malfunction Outdoor unit PCB defective Water mixed in the local piping Electronic expans...

Page 32: ...ff the power Disconnect the harness U V and W Normal Check with the inverter checker Correct the power supply Turn off the power and reconnect the harness Turn on the power again and get the system re...

Page 33: ...TS13 01 Troubleshooting manual 33 E7 Description DC Fan Lock Supposed Cause Fan motor breakdown Harness or connector disconnected between fan motor and PCB or in poor contact Troubleshooting...

Page 34: ...o short circuit Troubleshooting Input current flowing above its stop level Replace the outdoor unit Yes No Yes Turn off the power and disconnect the harness U V and W Check with the inverter checker M...

Page 35: ...Supposed Cause EXV faulty EXV connected wrongly Troubleshooting EA Description 4 way valve error Supposed Cause Thermistor defective Connector in poor contact 4 way valve defective Outdoor PCB defecti...

Page 36: ...e connector Resistance between harness about 3k Reconnect Replace outdoor unit PCB Check the 4 way valve switching output Functioning No Yes No Yes Any thermsistor disconnected Thermistor functioning...

Page 37: ...or defective Outdoor PCB defective Water mixed in the local piping EXV defective Stop Valve defective Troubleshooting F6 Description Heat exchanger overheat Supposed Cause The installation space is no...

Page 38: ...TS13 01 Troubleshooting manual 38 Troubleshooting...

Page 39: ...3 01 Troubleshooting manual 39 HO Description Compressor sensor system error Supposed Cause Reactor disconnection Compressor disconnection Outdoor unit PCB defective Compressor defective Troubleshooti...

Page 40: ...tdoor PCB defective Stop valve closed Input voltage out of specification Troubleshooting No No Yes Yes Check with inverter checker Check for short circuit Normal Check the electrolytic capacitor volta...

Page 41: ...TS13 01 Troubleshooting manual 41 H8 Description AC current sensor error Supposed Cause Internal wiring broken Outdoor unit PCB defective Troubleshooting...

Page 42: ...tr short open J5 Suction pipe thermistor short open J6 Outdoor heat exchanger thermistor short open J7 Subcooling heat exchanger thermistor short open J8 Liquid pipe thermistor short open J9 Gas pipe...

Page 43: ...iption Outdoor control box overheat Supposed Cause Fin temperature rise due to defective outdoor unit fan Fin temperature rise due to short circuit Fin thermistor defective Connector in poor contact O...

Page 44: ...n temperature rise due to short circuit Fin temperature rise due to defective outdoor unit fan Fin thermistor defective Connector in poor contact Outdoor unit PCB defective Silicon grease is not appli...

Page 45: ...ction due to defective PCB Over current due to closed stop valve Over current due to compressor failure Over current due to poor installation condition Connection between main board and IPM board is n...

Page 46: ...TS13 01 Troubleshooting manual 46 Troubleshooting...

Page 47: ...ulty outdoor unit PCB Faulty indoor unit PCB Indoor unit outdoor unit signal transmission error due to wiring error Indoor unit outdoor unit signal transmission error due to disturbed power supply wav...

Page 48: ...TS13 01 Troubleshooting manual 48...

Page 49: ...nication error outdoor PCB IPM PCB Supposed Cause Wrong models interconnected Wrong indoor unit PCB mounted Indoor unit PCB defective Wrong outdoor unit PCB mounted or defective Troubleshooting Check...

Page 50: ...TS13 01 Troubleshooting manual 50 4 0 Wiring Connection FTXN 25 35 LV1B RXN 25 35 LV1B...

Page 51: ...TS13 01 Troubleshooting manual 51 FTXN 50 60 LV1B RXN50 60 LV1B...

Page 52: ...TS13 01 Troubleshooting manual 52 Refrigerant Diagram FTXN 25 35 LV1B RXN 25 35 LV1B FTXN 50 60 LV1B RXN50 60 LV1B...

Page 53: ...TS13 01 Troubleshooting manual 53 Appendix Resistance value when 25 C RXN50 60 LV1B RXN 25 35 LV1B Indoor WM 10K 10K CC CK CM 10K Outdoor 10K 20K Table 1 Resistance R25 10K ohm...

Page 54: ...Troubleshooting manual 54 Table 2 Resistance R25 20K ohm Temperature C Resistance value k 20 211 0 15 150 0 10 116 5 5 88 0 0 67 2 5 51 9 10 40 0 15 31 8 20 25 0 25 20 0 30 16 0 35 13 0 40 10 6 45 8 7...