SiUS042113E
Troubleshooting
Part 6 Service Diagnosis
99
4.8 Low-voltage Detection or Over-voltage Detection
Error Code
U2
Method of Error
Detection
Indoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Indoor Unit
The voltage detected by the DC voltage detection circuit is below 140 V.
Outdoor Unit
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 162 V (09/12 class), 160 V
(18/24 class).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
The voltage detected by the DC voltage detection circuit is below 458 V (depending on the
model).
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage out of specification
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
Defective indoor unit PCB
Summary of Contents for FTXM-V Series
Page 16: ...SiUS042113E 12 Part 2 Specifications 1 Specifications 13 Part 2 Specifications...
Page 96: ...Troubleshooting SiUS042113E 92 Part 6 Service Diagnosis Reference Check No 01 Refer to P 134...
Page 150: ...Check SiUS042113E 146 Part 6 Service Diagnosis 18 24 class R24539 DC DC W V U...
Page 166: ...Piping Diagrams SiUS042113E 162 Part 8 Appendix RXM24VVJU 3D132217...
Page 171: ...SiUS042113E Operation Limit Part 8 Appendix 167 3 Operation Limit RXM09 12 18 24VVJU 3D133582A...