9 Configuration

Installation manual

9

FTXJ35MV1BS/W6
Split system air conditioners
3P482320-15Z – 2021.10

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant piping

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

8.2

To pass the pipes through the wall
hole

1

Shape the refrigerant pipes along the pipe path marking on the
mounting plate.

a

b

c

c

d

e

a

Drain hose

b

Caulk this hole with putty or caulking material

c

Adhesive vinyl tape

d

Insulation tape

e

Mounting plate (accessory)

NOTICE

▪ Do NOT bend refrigerant pipes.

▪ Do  NOT  push  the  refrigerant  pipes  onto  the  bottom

frame or the front grille.

2

Pass the drain hose and refrigerant piping through the wall hole
and seal the gap with a putty.

8.3

To fix the unit on the mounting
plate

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

2

Press the bottom frame of the unit with both hands to set it on
the  bottom  hooks  of  the  mounting  plate.  Make  sure  that  the
wires do NOT get squeezed anywhere.

Note: 

  Take  care  that  the  interconnection  cable  does  NOT  get

caught in the indoor unit.

3

Press the bottom edge of the indoor unit with both hands until it
is firmly caught by the mounting plate hooks.

4

Secure the indoor unit to the mounting plate using 2 indoor unit
fixing screws M4×12L (accessory).

9

Configuration

9.1

To set a different address

In case 2 indoor units are installed in 1 room, different addresses for
2 user interfaces can be set.

1

Remove the cover and the batteries from the user interface.

2

Cut the address jumper J4.

a

a

Address jumper J4

NOTICE

Be  careful  NOT  to  damage  any  of  the  surrounding  parts
when cutting the address jumper.

3

Turn the power supply on.

4

Press 

 and 

 simultaneously.

5

Press 

, select   and press 

.

Result: 

The operation lamp will start to blink.

a

a

Indoor unit ON/OFF switch

6

Press  the  indoor  unit  ON/OFF  switch  while  the  operation  lamp
is blinking.

Address jumper

Address

Factory setting

1

Summary of Contents for FTXJ35MV1BS6

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FTXJ35MV1BW6 FTXJ35MV1BS6 ...

Page 2: ...cal data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 11 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for...

Page 3: ...g N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped...

Page 4: ...the latest version of this manual visit app daikineurope com INFORMATION Daikin Industries Czech Republic s r o declares that the radio equipment type inside of this unit is in compliance with Directive 2014 53 EU This unit is considered as combined equipment according to the definition of Directive 2014 53 EU 4 2 1 Precautions when using the wireless LAN Do NOT use near Medical equipment E g pers...

Page 5: ...25L screws field supply INFORMATION The removed pipe port cover can be kept in the mounting plate pocket mm 998 357 135 142 348 160 151 φ65 φ 6 5 49 100 200 124 303 49 50 203 234 67 a f b c d e h g a Recommended mounting plate fixing spots b Pocket for the pipe port cover c Tabs for placing a spirit level d Through the wall hole Ø65 mm e Drain hose position f Position for the tape measure at symbo...

Page 6: ... the piping on left side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE Do NOT apply lubricating oil refrigerant oil ...

Page 7: ...If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation 6 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 6 2 1 To connect the refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is ...

Page 8: ...at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b e f 1 2 3 c d a Terminal block b Electrical component block c Shape wires d Firmly secure wire retainer e Wire retainer f Specified wire type 5 Strip the wire ends approximately 15 mm 6 Mat...

Page 9: ...e bottom frame of the unit with both hands to set it on the bottom hooks of the mounting plate Make sure that the wires do NOT get squeezed anywhere Note Take care that the interconnection cable does NOT get caught in the indoor unit 3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4 Secure the indoor unit to the mounting plate using ...

Page 10: ...pecified wires are used for the interconnection cable The indoor unit receives the signals of the user interface There are NO loose connections or damaged electrical components in the switch box The insulation resistance of the compressor is OK There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is ins...

Page 11: ... diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor Symbol Meaning M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplit...

Page 12: ...ülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe İstanbul TÜRKİYE Factory Kargalıhanbaba OSB Mahallesi Organize Sanayi 1 Sokak No 28 54300 Hendek Sakarya TÜRKİYE 3P482320 15Z 2021 10 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...

Reviews: