Daikin FTXF20E5V1B Installation Manual Download Page 6

3 About the box

Installation manual

6

FTXF20~42E5V1B

Daikin room air conditioner

3P650253-7H – 2022.10

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  extension  cords,  or

connections  from  a  star  system.  They  can  cause
overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

Finishing indoor unit installation (see Finishing the outdoor unit
installation)

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn OFF the power supply before servicing.

▪ Install  the  switch  box  cover  before  turning  ON  the

power supply.

Commissioning (see 

"10 Commissioning"

 [

4

 14])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

3

About the box

3.1

Indoor unit

INFORMATION

The  following  figures  are  just  examples  and  may  NOT
completely match your system layout.

3.1.1

To remove the accessories from the
indoor unit

1

Remove:

▪ the accessory bag located at the bottom of the package,

▪ the mounting plate attached to the back of the indoor unit.

d

b

a

c

e

f

g

h

a

Installation manual

b

Operation manual

c

General safety precautions

d

Indoor unit fixing screw (M4×12L). Refer to 

"8.3 To fix the

unit on the mounting plate"

 [

4

 13].

e

Dry battery AAA.LR03 (alkaline) for user interface

f

User interface holder

g

User interface

h

Mounting plate

4

About the unit

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

4.1

System layout

NOTICE

Design  of  the  system  must  not  be  done  at  temperatures
below –15°C.

Summary of Contents for FTXF20E5V1B

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXF20E5V1B FTXF25E5V1B FTXF35E5V1B FTXF42E5V1B ...

Page 2: ...тива и или регламент и при условие че продуктите се използват в съответствие с нашите инструкции atitinka toliau nurodytas direktyvas arba reglamentus su sąlyga kad gaminiai bus eksploatuojami laikantis mūsų instrukcijų atbilst šādām direktīvām vai regulām ja vien šie izstrādājumi tiek lietoti saskaņā ar mūsu instrukcijām sú v zhode s nasledujúcou imi smernicou ami alebo predpisom mi za predpoklad...

Page 3: ...s are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 following the provisions of BS EN 60335 2 40 A B C TCF032E25 as set out in A and judged positively by B according to the Certificate C Daikin Europe N V is authoris...

Page 4: ...run 15 10 2 1 To perform a test run in winter season 15 11 Disposal 15 12 Technical data 16 12 1 Wiring diagram 16 12 1 1 Unified wiring diagram legend 16 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin including all documents listed in Documentation set and in addition comply wi...

Page 5: ... sucked in This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves befo...

Page 6: ... them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the location of the terminals see the wiring diagram Finishing indoor unit installation see Finishing...

Page 7: ...in and with applicable legislation and are executed ONLY by authorised persons 5 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Air flow Make sure nothing blocks the air flow Drainage Make sure condensation water can be evacuated properly Wall insulation When conditions in the wall exceed 30 C and a relative humidity of 80 or when fre...

Page 8: ... and firmly engage the 3 upper hooks 2 Install 2 screws back on the front grille 3 Install the air filter and then mount the front panel 5 2 5 To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring box 3 Open the electrical wiring box cover by pulling the protruding part on the top of the cover 4 Unhook the tab on the bottom and remove the e...

Page 9: ...cover INFORMATION To connect the piping on right side right bottom left side or left bottom the pipe port cover MUST be removed 1 Cut off the pipe port cover from inside the front grille using a coping saw 2 Remove any burrs along the cut section using a half round needle file NOTICE Do NOT use nippers to remove the pipe port cover as this would damage the front grille 5 3 4 To provide drainage Ma...

Page 10: ...ht side and install it on the left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug 3 Insert the drain hose on the left side and do n...

Page 11: ...S use a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm Ø6 4 15 17 8 7 9 1 R 0 4 0 8 2 45 90 2 ØA Ø9 5 33 39 12 8 13 2 6 2 2 To connect the refrigerant piping to the indoor unit WARNING M...

Page 12: ...ithout thermal insulation as such pipes will be very hot 7 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used twist the conductor to consolidate the end or twist the conductor to consolidate the end in combination with the usage of a round crimp style terminal on the end of the conductor Details are described in Guidelines wh...

Page 13: ...a Drain hose b Interconnection cable c Mounting plate accessory d Refrigerant piping e Indoor unit fixing screw M4 12L accessory f Bottom frame 8 2 To pass the pipes through the wall hole 1 Shape the refrigerant pipes along the pipe path marking on the mounting plate a b c c d e a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate ...

Page 14: ...mistors and or pressure sensors switches If NOT burning of the compressor might be the result 10 1 Checklist before commissioning 1 After the installation of the unit check the items listed below 2 Close the unit 3 Power up the unit You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted The outdoor unit is properly mounte...

Page 15: ...The system stops operating 3 minutes after the unit is turned OFF 10 2 1 To perform a test run in winter season When operating the air conditioner in Cooling mode in winter set it to test run operation using the following method For FTXF and ATXF units 1 Press to switch the system on 2 Press the centre of and simultaneously 3 Press twice Result will appear on the display Test run operation is sele...

Page 16: ... Meaning A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H O Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse Symbol Meaning FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode HAP Light emitt...

Page 17: ...r 3P650253 7H 2022 10 Symbol Meaning V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter ...

Page 18: ......

Page 19: ......

Page 20: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P650253 7H 2022 10 Copyright 2022 Daikin Verantwortung für Energie und Umwelt ...

Reviews: