1 General safety precautions
Installer reference guide
4
(A)(F)TXP20~3 FTXF20~71A2V1B
Daikin room air conditioner
4P513661-1 – 2017.10
WARNING
If appliances contain R32 refrigerant, the floor area of the
room in which the appliances are installed, operated and
stored MUST be larger than the minimum floor area
defined in table below A (m
2
). This applies to:
▪ Indoor units
without
a refrigerant leakage sensor; in
case of indoor units
with
refrigerant leakage sensor,
consult the installation manual
▪ Outdoor units installed or stored indoors (e.g. winter
garden, garage, machinery room)
▪ Pipework in unventilated spaces
To determine the minimum floor area
1
Determine the total refrigerant charge in the system (= factory
refrigerant charge
+
additional refrigerant amount
charged).
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
2
Determine which graph or table to use.
▪ For indoor units: Is the unit ceiling-mounted, wall-mounted or
floor-standing?
▪ For outdoor units installed or stored indoors, and field piping
in unventilated spaces, this depends on the installation
height:
If the installation height is…
Then use the graph or table for…
<1.8 m
Floor-standing units
1.8≤x<2.2 m
Wall-mounted units
≥2.2 m
Ceiling-mounted units
3
Use the graph or table to determine the minimum floor area.
m (kg)
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
2.8
3
3.2
3.4
3.6
3.8
4
4.2
4.4
4.6
4.8
5
5.2
5.4
5.6
5.8
6
6.2
6.4
6.6
6.8
7
7.2
7.4
7.6
7.8
7.956
A
min
(m
2
)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
Ceiling-mounted
unit
(a)
—
4.6
13.5
<1.224
<1.224
—
4.6
182
1.225
0.956
4.8
14.7
1.225
12.9
4.8
198
1.4
1.25
5.0
16.0
1.4
16.8
5.0
215
1.6
1.63
5.2
17.3
1.6
22.0
5.2
232
1.8
2.07
5.4
18.6
1.8
27.8
5.4
250
2.0
2.55
5.6
20.0
2.0
34.3
5.6
269
2.2
3.09
5.8
21.5
2.2
41.5
5.8
289
2.4
3.68
6.0
23.0
2.4
49.4
6.0
309
2.6
4.31
6.2
24.5
2.6
58.0
6.2
330
2.8
5.00
6.4
26.1
2.8
67.3
6.4
351
3.0
5.74
6.6
27.8
3.0
77.2
6.6
374
3.2
6.54
6.8
29.5
3.2
87.9
6.8
397
3.4
7.38
7.0
31.3
3.4
99.2
7.0
420
3.6
8.27
7.2
33.1
3.6
111
7.2
445
3.8
9.22
7.4
34.9
3.8
124
7.4
470
4.0
10.2
7.6
36.9
4.0
137
7.6
496
4.2
11.3
7.8
38.8
4.2
151
7.8
522
4.4
12.4
7.956
40.8
4.4
166
7.956
549
m (kg)
A
min
(m
2
)
<1.224
—
4.6
20.2
1.225
1.43
4.8
22.0
1.4
1.87
5.0
23.8
1.6
2.44
5.2
25.8
1.8
3.09
5.4
27.8
2.0
3.81
5.6
29.9
2.2
4.61
5.8
32.1
2.4
5.49
6.0
34.3
2.6
6.44
6.2
36.6
2.8
7.47
6.4
39.1
3.0
8.58
6.6
41.5
3.2
9.76
6.8
44.1
3.4
11.0
7.0
46.7
3.6
12.4
7.2
49.4
3.8
13.8
7.4
52.2
4.0
15.3
7.6
55.1
4.2
16.8
7.8
58.0
4.4
18.5
7.956
61.0
Wall-mounted
unit
(b)
m (kg)
A
min
(m
2
)
Floor-standing
unit
(c)
m (kg)
A
min
(m
2
)
m
Total refrigerant charge in the system