![background image](http://html1.mh-extra.com/html/daikin/ftks18sl216/ftks18sl216_service-manual_4699156064.webp)
61
Installation and Maintenance
Service Manual
2.IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (AP1 below is control board
of outdoor unit)
Main detection point:
● If control board AP1 and compressor COMP is well connected? If they are loosened? If the connection sequence is correct?
● Is voltage input in the normal range (Test the voltage between L, N of wiring board XT by DC voltage meter)?
● If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
● If the work load of unit is heavy? If radiating of unit is well?
● If the refrigerant charging is appropriate?
Malfunction diagnosis process:
Summary of Contents for FTKS18SL216
Page 22: ...19 Technical Information Service Manual...
Page 87: ...84 Installation and Maintenance Service Manual...
Page 98: ...JF00303650...