background image

Safety Precautions 

• The precautions described herein are classified as WARNING  and CAUTION. They both contain important 

information regarding safety.  Be sure to observe all precautions without fail. 

•  Meaning of WARNING  and CAUTION notices 

� WARNING 

Failure to follow these instructions properly may result in personal injury or loss of life. 

� CAUTION 

Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances. 

• The safety  marks shown in this manual have the following meanings: 

I  Be sure to follow the instructions. 

Be sure to establish an earth connection. 

(S) 

Never attempt. 

• After completing installation,  conduct a trial operation to check for faults and explain to the customer how to 

operate the air conditioner and take care of it with the aid of the operation manual. 

�  WARNING 

• Ask your dealer or qualified  personnel to carry out installation work. 

Do not  attempt  to  install the air  conditioner  yourself.  Improper installation may  result in water  leakage,  electric  shocks  or fire. 

•  Install the air conditioner in accordance with the instructions in this  installation manual.  Improper instanation may result in water leakage, electric shocks or fire. 
•  Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of •sufficient streng� may result in �e equipment falling and causing •��-
• Electrical work must be perfonmed in accordance with relevant local and national regulations and with instructions in this installation manual. 

Be sure to use a dedicated power supply circuit only.  Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire. 

•  Use a  cable of suitable  length.  Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire. 

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 

connections  or  wires.  Improper connections  or securing of wires may result in abnormal heat  build-up or fire. 

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the 

control box lid can  be securely fastened. Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals. 

• If refrigerant gas leaks  during  installation,  ventilate the area immediately. 

0

Toxic gas may be produced if the refrigerant comes into contact with fire. 

• After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant gas 

0

leaks into the room and comes into contact with a source of fire, such as a fan heater,  stove or cooker. 

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, and use only the specified 

refrigerant (R32). The presence of air or other foreign matter in the refrigerant circutt causes abnormal  pressure rise, which may result in equipment  damage and even injury. 

• During installation, attach the refrigerant  piping securely before running the compressor. If the refrigerant pipes are not attached and the stop 

valve is open when the compressor is run, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is stil running and the stop valve is open during pump-down, 

air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• Be sure to earth the air conditioner. 

0

Do not earth the unit to a utility pipe,  lightning conductor or telephone earth lead.  Imperfect earthing may result in electric shocks. 

•  Be sure  to  install an earth leakage  circuit breaker.  Failure to install an earth leakage circuit breaker may result in electric shocks or fire. 

• Do not pump down when the refrigerant has leaked, otherwise the compressor may be damaged. 

�  CAUTION 

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

(S) 

In the event of a gas leakage,  build-up of gas near the air conditioner may cause a fire to  break out. 

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate 

piping to  prevent  condensation.  Improper drain piping may result in indoor water leakage and property damage. 

• Tighten the flare nut according to the specified method such as with a torque wrench. If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage. 
• Take adequate steps to  prevent the outdoor unit being used  as a shelter by small animals. 

Small animals making contact with electrical parts can cause  malfunctions,  smoke or fire. Please instruct the customer to keep the area around the unit clean. 

• The temperature of refrigerant circuit will be high, please keep the inter-unit wires away from copper pipes that are not thenmally insulated. 

Summary of Contents for FTKM35UV16W

Page 1: ...ERATION MANUAL MODELS F G MTKM35UV16W F G MTKM50UV16U F G MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T F G MTKM50UV16VA 3P665364 1W M21P075D ...

Page 2: ...quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that producenaked flames in places exposed to the airflow from the unit as this may impair combustion of the burner Do not block the air inlets or outlets Impaired airflow may result in insufficient performance or trouble D...

Page 3: ...ver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop long beep 13 Inverter output and temperature display 14 OPERATION lamp green 15 TIMER lamp orange 16 lndoor unit ON OFF switch Press this switch once to start operation Press once again to stop it For the operation...

Page 4: ...DEW CLEAN button NOTE Notes on remote controller 7 9 10 14 13 S NO 1 2 3 4 5 6 7 10 Never expose the remote controller to direct sunlight DAIKIN 011 II POWER LL 11 DEjaR I II T P BIi 11COANDA HP 11 El I STREAMER DIS j LAY ll CE I1 L__TIMER__J 1 1 1 DEWCL AN MODEL NO A D F MTKL35 50UV1SWN U A D FTKL60UV16U FTKT35 50 60UV16WN U F MTKM35 50 60UV16W U U FTKL71UV1BT GTKL71UV16T GTKL35 50 60UV16WN U U G...

Page 5: ...controller Do not get it wet The maximum transmission distance is about 7m To attach the accessory filters i Receiver Set the accessory filters under the tabs of the filter Ac esso yfUte i n h 0 Y u f rs refer to Care Ji 1 and Cleaning and pull out the air filters Accessoryfilter Turn on the circuit breaker After the power is turned on the flaps of the indoor unit open and close once to set the re...

Page 6: ... the accessory filter and the decomposition power of the streamer discharge combine to reduce unpleasant odours and viruses cleaning the air in the room To start operation 1 Press I c I STREAMER When long press duration defined a 5sec the COANDA STREAMER KEY then STREAMER function will be enabled and respective symbol glow on remote LCD To stop operation 1 Press I c I STREAMER Again long press dur...

Page 7: ...ILD LOCK disables all the buttons except when ECONO and POWERFULL button press together for about 5 seconds To set the CHILD LOCK Press and o_WE_R_c 1L together for about 5 seconds e will be displayed on the remote LCD If a button is pressed while CHILD LOCK is on e blinks To CANCEL the CHILD LOCK Press and owERC together for about 5 seconds again e Disappears from the LCD NOTE Note on airflow rat...

Page 8: ...lades will begin to swing The 3 D airflow direction 1 Press 1SWIN and SWING and e are displayed on the LCD The flap and louvres move in turn To cancel 3 D airflow press either 4swiNaj or sw1NG again The flap or louvres will stop moving I II l _ ry _ ___ To set the flap or louvres at desired position 7 This function is effective while flap or louvres are in auto swing mode 1 Press c1swiNaJ and swiN...

Page 9: ...auses the settings to be cancelled and disappears from the LCD ECONO operation functions in COOL and DRY operation POWER CHILL and ECONO operation cannot be used at the same time is displayed on the LCD To cancel POWER CHILL operation 2 Press POWER again Priority is given to the function of whichever button is pressed last disappears from the LCD This operation is performed with lowerpower and the...

Page 10: ... time default 2HR are displayed on the LCD IC O ON OFF c J The TIMER lamp lights Display orange TEMP 2 Press v while C is blinking Each pressing of the button changes tempera ture shift value by 1 c You can specify a temperature shift value between 1 C and S C 3 Press cij while C is blinking Each pressing of the button changes the time setting The time can be set between 1 and 9 hours 1 hour 9 hou...

Page 11: ... Set temperature does not display when the unit is in DRY operation or FAN operation Inverter output and set temperature may not display depending on the operation mode that is active The display turns off when the unit is turned off Checking current indoor temperature when the air conditioner is off 1 Press foi 1 1 when the air conditioner is OFF and remote is ON DISPLAY The current indoor temper...

Page 12: ...n Dry mode OFF Cooling operation To cancel DEW CLEAN operation Turn OFF the machine from Remote Controller Wi Fi Control NOTE Note on LED 7 Segment Brightness Control Ld indicates for the brightness Light feature which is appeared on set temperature area Remote will be in High Brightness Intensity by default whenever batteries inserted Keep this in mind that If user sets LEDlights to be in OFF sta...

Page 13: ...gage the front panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward yourself and remove it 3 Clean the front panel Wipe it with a soft damp cloth Only neutral detergent may be used D In case of washing the panel with water wipe it with a dry soft cloth and let it dry in the shade after washing 4 Attach the front panel Align the fron...

Page 14: ... with a vacuum cleaner If the dust does not come off easily wash them with neutral detergent thinned with lukewarm water then let them dry in the shade Be sure to remove the accessory filter optional part It is recommended to clean the air filters every 2 weeks 3 Reattach the filters and close the front panel Insert the filters into slots of the front grille Close the front panel slowly and push t...

Page 15: ...em Titanium apatite deodorizing air purifying filter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Micro filter PM2 5 for streamer unit 1 set Micro filter PM 1 0 for streamer unit 1 set Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Prior to a long period of non use Part No KAF970A45 KAF057A41 KAF500A504 KAF250A502 KAF250A505 KAF1...

Page 16: ...mes operation in about 3 minutes Voltage range protection 130V 285V Voltage range protection 130V 265V for F GTKL71UV16T Models A sound is heard A sound like flowing water This sound is generated because the refrigerant in the air conditioner is flowing This is a pumping sound of the water in the air conditioner and can be heard when the water is pumped out from the air conditioner during COOL or ...

Page 17: ...r been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflow rate setting appropriate If the airflow rate setting is too low increase it Is the set temperature appropriate Is the adjustment of the airflow direction appropriate Are the air filters dirty Is th...

Page 18: ... air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood stop operation and turn off the circuit breaker to protect the system Disposal requirements Your air conditioning product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted hou...

Page 19: ... E7 DC FAN MOTOR FAULT E8 OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING F8 OPERATION HALT DUE TO COMPRESSOR INTERNAL TEMPERATURE ABNORMALITY OUTDOOR HO SENSOR FAULT UNIT H6 OPERATION HALT DUE TO FAULTY POSITION DETECTION SENSOR H8 DC CURRENT SENSOR FAULT H9 FAULTY SUCTION AIR TEMPERATURE SENSOR J3 FAULTY DISCHARGE PIPE TEMPERATURE SENSOR J6 FAULTY...

Page 20: ......

Page 21: ...NUAL l MODELS F G MTKM35UV16W F G MTKM50UV16U F G MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T F G MTKM50UV16VA J tC _JNVERTER 3P665364 1W M22P096B ...

Page 22: ...erant gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leakage Toxic gas may be produced if the refrigerant gas 0 leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker When installing orrelocating the air con...

Page 23: ...omany television orradio set theunit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby The outdoor unit should be positioned in a place where 1 the restrictions on the installationrequirements specified in Indoor Outdoor Installation Diagram are met 2 drain water causes no trouble or problem in particular 3...

Page 24: ...order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of ODU installation leg Type Applicabel unit size A B C H X W X D CD 418x695x244 467 119 5 287 j 550 X 675 X 284 470 97 308 550 X 765 X 285 573 5 131 326 595 X 845 X 300 574 105 5 311 695 X 930 X 350 610 175 367 ...

Page 25: ...shing up pull it toward you Installation method 1 Push up 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and then mount the front panel Opening the service lid I The service lid is opening closing type 0 Opening method _ 3 1 Remove the service lid screws 2 2 2 Pull out the service lid diagonally 7 down in the...

Page 26: ...ipeend Drainhose position Type H X W X D A B C CD 298 X 800 X 229 800 116 5 116 5 0 298 X 821 X 235 821 128 126 5 298 X 885 X 229 885 116 5 116 5 298 X 906 X 235 906 127 127 5 Unit size available on name plate Table No 4 Applicable Unit Size Type I H X W X D I 310 X 1100 X 239 Unit size available on name plate Table No 5 All dimensions are in mm Drilling A Wall Hole And Installing Wall Embedded Pi...

Page 27: ... to set it on the A mounting plate hooks Make sure the wire lead do not catch on the edgeofthe indoor unit 9 Securethe indoor unit to the A mounting plate with the E indoor unit fixing screws M4 x 12L 10 Caulk the gap between the pipe and thefront grille with putty 11 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty Left Side Left Back or Left Bottom Pipin...

Page 28: ...s not included with the unit TableNo 6 6 WARNING Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock ...

Page 29: ... Heat insulationpipe cover Slit __ 7 Z_J r I I I I 1 I I I I I J Slit Vinyl1ape _ This illustration shows the case of the left rear piping Sectional view wire Insulation tape Overwrap more than half of heat insulation tape Wrap the heat insulation tape around all the pipes from the right side to theleft side of the pipe that pass through the back side of indoor unit Seal with putty or caulking mat...

Page 30: ... m 21 6 27 4N m 0 D 9 5mm 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 505 615 kgf cm 48 1 59 7N m 0 D 15 9mm 61 8 75 4N m 490 610 kgf cm 10 8 14 7N m 110 150 kgf cm 630 770 kgf cm 14 2 17 2N m 21 6 27 4N m Liquid side 0 D 6 4mm 144 175 kgf cm 220 280 kgf cm Cautions on Pipe Handling 1 Protect the open end of the pipe against dust and moisture 2 All pipe bends should be as gentle...

Page 31: ...lve s service port thenfullyopenliquidandgas stop valves Do not attempt to tum valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques 1 Pipe length vs vacuum pump run time Pipe length Up to 15m More than 15m Run time Not less than 10 min Not less than 15 min 2 If the compound pressure gauge pointer swing...

Page 32: ...are installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Draining line is properly installed Water leakage System is properly earthed Electrical leakage Only specified wires are used for all wiring and all No operation or burn damage wires are connected cor...

Reviews: