Application Information
Installation Guideline
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
Installation Diagram
Front panel
50mm or more from walls
(on both sides)
Indoor unit
Air filter
M4 x 12L
30mm or more from ceiling
Caulk pipe hole
gap with putty.
Cut thermal insulation pipe
to an appropriate length and
wrap it with tape, making
sure that no gap is left in the
insulation pipe’s cut line.
Wrap the insulation pipe with the
finishing tape from bottom to top.
Outdoor Unit
Opening service lid
Service lid is opening/closing
type.
Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.
Service lid
Outdoor Clearance
If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil re
fi
nery plant), such as
substances may lead to failure of the unit.
A
AIR INLET
AIR DISCHARGE
B
OBST
ACLE
OBST
ACLE
C
AIR INLET
SERVICE SPACE
D
OBST
ACLE
OBST
ACLE
ALL MODELS
Minimum Distance
A
300 mm
B
1000 mm
C
300 mm
D
500 mm