3 About the units and options

Installation manual

5

FNA25~60A2VEB(9)
Split system air conditioners
4P456958-1D – 2018.11

3

About the units and options

3.1

System layout

INFORMATION

The  following  illustration  is  an  example  and  might  NOT
match your system layout.

a

b

c

f

d

e

a

Indoor unit

b

Outdoor unit

c

User interface

d

Refrigerant interconnection cable

e

Drain pipe

f

Earth wiring

4

Preparation

4.1

Preparing the installation site

▪ Provide  sufficient  space  around  the  unit  for  servicing  and  air

circulation.

▪ Choose  the  installation  location  with  sufficient  space  for  carrying

the unit in and out of the site.

CAUTION

Do  NOT  install  or  use  in  places  filled  with  smoke,  gas,
chemicals  etc.  Sensors  inside  the  indoor  unit  may  detect
these  substances,  and  display  a  refrigerant  leak
abnormality.

1

WARNING

Do  NOT  install  the  air  conditioner  at  any  place  where
flammable gas may leak out. If the gas leaks out and stays
around the air conditioner, a fire may break out.

CAUTION

Do  NOT  install  or  use  in  highly  airtight  spaces,  e.g.
soundproof chambers or rooms with sealed doors.

1

CAUTION

This  unit  is  equipped  with  electrically  powered  safety
measures,  such  as  a  refrigerant  leak  detector.  In  order  to
be  effective,  the  unit  must  be  electrically  powered  at  all
times after installation, except for short service periods.

1

4.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

▪ Use

 suspension bolts

 for installation.

▪ Mind the following requirements:

Wall-mounted type

Floor-standing type

a

a

a

1750

100

a

a

Minimum clearance

Top view

300

300

1000

(mm)

20

a

a

Indoor unit

▪ Install the unit with a prebuilt fully enclosed casing with removable

access  panel,  suction  air  grille  and  discharge  grille.  These
removable parts shall prevent access to the unit and can ONLY be
removed using a removal tool.

▪ In case of installation under a window sill, make sure that there is

no short-circuit of air.

5

Installation

5.1

Mounting the indoor unit

5.1.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Wall  or  floor  strength.

  Check  whether  the  wall  or  the  floor  is

strong enough to support the weight of the unit. If there is a risk,
reinforce the wall or the floor before installing the unit.

Suspension  bolts.

  Use  W3/8  M10  suspension  bolts  for

installation. Attach the hanger bracket to the suspension bolt. Fix it
securely  using  a  nut  and  washer  from  the  upper  and  lower  sides
of the hanger bracket.

(1)

Only for units using R32 refrigerant. Refer to the outdoor unit specifications for the type of refrigerant to be used.

Summary of Contents for FNA25A2VEB9

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FNA25A2VEB FNA35A2VEB FNA50A2VEB FNA60A2VEB FNA25A2VEB9 FNA35A2VEB9 FNA50A2VEB9 FNA60A2VEB9 ...

Page 2: ...itate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka...

Page 3: ...ate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka ž...

Page 4: ...commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the indoor unit Indoor unit installation manual Installation instructions Format Paper in the box of the indoor unit Installer reference guide Preparatio...

Page 5: ...xcept for short service periods 1 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Mind the following requirements Wall mounted type Floor standing type a a a 1750 100 a a Minimum clearance Top view 300 300 1000 mm 20 a a Indoor unit Install the unit with a prebuilt fully enclosed casing with remo...

Page 6: ...0 660 50 60 1750 1060 A Maintenance area width B Air inlet grille width a Air outlet direction b Air inlet grille height c Air inlet direction External static pressure Refer to technical documentation to ensure that the unit s external static pressure is not exceeded Removing the legs If it is necessary to remove the legs follow these instructions b a 2 1 b A B A Bottom view B Side view a Protecti...

Page 7: ...or more rooms are connected to the unit using a duct system make sure there are no operating ignition sources example open flames an operating gas appliance or an operating electric heater in case the floor area is less than Amin specified in the General safety precautions no auxiliary devices which may be a potential ignition source are installed in the duct work example hot surfaces with a tempe...

Page 8: ... large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f Drain piping field supply NOTICE Do NOT r...

Page 9: ...system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitrogen gas 5 3 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables WARNING If the s...

Page 10: ...e NO missing phases or reversed phases The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box The ins...

Page 11: ... interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown A0 Refrigerant leak detected 1 CH Abnormality of refrigerant leakage sensor ...

Page 12: ... HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M P DRAI...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...4P456958 1D 2018 11 Copyright 2017 Daikin ...

Reviews: