Installation and operation manual

3

FMCQ50~125A8VEB

Air conditioning system

4PW56204-1

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1.

Relation of ceiling opening to unit and suspension bolt
position. 

(See figure 3)

Use the installation guide (delivered with the unit) for exact
vertical positioning of the unit. 

Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. 

(See figure 4)

2.

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

Refer to the paper pattern for installation for the ceiling opening
dimensions.

Create the ceiling opening required for installation. From the side
of the opening to the casing outlet, implement the refrigerant and
drain piping and wiring for remote controller (unnecessary for
wireless type) and indoor-outdoor unit casing outlet. Refer to
each piping or wiring section.

After making an opening in the ceiling, it may be necessary to
reinforce ceiling beams to keep the ceiling level and to prevent it
from vibrating. Consult the builder for details.

3.

Install the suspension bolts. (use either a W3/8 or M10 size
bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce the
ceiling in order to bear the weight of the unit. Adjust clearance from
the ceiling before proceeding further.

Installation example see 

figure 5

.

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories (except for the decoration
panel), read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed. However, for existing
ceilings, install fresh air intake kit before installing the unit.

1.

Install the indoor unit temporarily. 

Attach the hanger bracket to the suspension bolt. Be sure to fix it
securely by using a nut and washer from the upper and lower
sides of the hanger bracket.

Securing the hanger bracket see 

figure 6

.

2.

Fix the paper pattern for installation. (For new ceilings
only.)

The paper pattern for installation corresponds with the measure-
ments of the ceiling opening. Consult the builder for details.

The centre of the ceiling opening is indicated on the paper
pattern for installation. The centre of the unit is indicated on the
unit casing and on the paper pattern for installation.

After removing the packaging material from the paper pattern for
installation, attach the paper pattern for installation to the unit
with the attached screws as shown in 

figure 8

.

Adjust the height of the unit until it matches the indication in

figure 8

.

3.

Adjust the unit to the right position for installation.

(Refer to 

"Preparations before installation" on page 3

.)

1

Refrigerant piping

2

Suspension bolt (x4)

3

Hanger bracket

4

False ceiling

5

Suspension bolt pitch

6

Indoor unit

7

Ceiling opening

8

Decoration panel

Apply the short side of the 
installation guide in case of 
normal installation

Apply the long side of the 
installation guide in case of 
installation with fresh air 
intake kit

Apply the long side of the 
installation guide after removal 
of the tear-off tab in case of 
installation with self 
cleaning decoration panel

1

Lower ceiling surface

2

Underside of the unit

1

Dimensions inside frame

2

Opening dimension inside the frame for ceiling

3

Frame

4

Ceiling material

5

Ceiling opening dimension

6

Ceiling-panel overlapping dimension

NOTE

Installation is possible with a ceiling dimension of
910 mm (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.

1

2

1

2

1

2

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation, contact
your dealer for details.

1

Nut (field supplied)

2

Washer (supplied with the unit)

3

Hanger bracket

4

Double nut (field supply, tighten)

1

Paper pattern for installation

2

Centre of the ceiling opening

3

Centre of the unit

4

Screws (supplied with the unit)

Summary of Contents for FMCQ50A8VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMCQ50A8VEB FMCQ60A8VEB FMCQ71A8VEB FMCQ100A8VEB FMCQ125A8VEB Air conditioning system...

Page 2: ...0 860 910 840 780 710 840 860 910 950 4 125 130 3 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 90 mm 7 mm 80...

Page 3: ...lecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B...

Page 4: ...lastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines gene...

Page 5: ...t the distance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as...

Page 6: ...see figure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measure ments of the ceiling opening Consult the builder for details...

Page 7: ...tightening torque Overtightening may damage the flare and cause leaks Table 1 When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns...

Page 8: ...ose to insulate and fix it with clamps Insulate the complete drain piping inside the building field supply If the drain hose cannot be sufficiently set on a slope fit the hose with drain raising pipin...

Page 9: ...nit A unit B and be sure the terminal block wiring to the outdoor unit is matching properly If wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfu...

Page 10: ...es according to the table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insu...

Page 11: ...the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter...

Page 12: ...ining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and inju...

Page 13: ...panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How...

Page 14: ...H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector ada...

Page 15: ...1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1...

Page 16: ...4PW56204 1 Copyright Daikin...

Reviews: