background image

 

FMCQ50~125A7VEB
Air conditioning system
4PW47629-1

Installation and operation manual

6

-

Confirm the drain operation looking at the drain socket.

-

After checking the drainage flow, turn off the power,
remove the control box lid and disconnect the power
supply from the terminal again.

-

Reattach the control box lid.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

Attach the earth leakage circuit breaker and fuse to the power
supply line.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit is matching properly. If wiring and piping
between the outdoor unit and an indoor unit are mismatched,
the system may cause a malfunction.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
-

gas pipes: might cause explosions or fire if gas leaks.

-

telephone ground wires or lightning rods: might cause 
abnormally high electric potential in the ground during 
lightning storms.

-

plumbing pipes: no grounding effect if hard vinyl piping is 
used.

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring 

(See figure 10)

Power supply wiring
Remove the control box lid (1) and connect the wires to the
power supply terminal block inside (L, N) and connect the
ground wire to the grounding terminal. While doing this, pull the
wires inside through the hole in the casing and clamp the wires
along with other wires using a clamp as indicated in the figure.

Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the terminal block for unit
transmission wiring (F1, 

F2) and remote controller wiring

(P1, P2). Securely fix the wiring using a clamp as indicated in
the figure.

After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.

Attach the control box lid.

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal block.

-

Use a round crimp-style terminal for insulation sleeve for 
connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When clamping wiring, use the clamps (delivered with the 
unit) to prevent outside pressure being exerted on the wiring 
connections. Tie up firmly. When doing the wiring, make sure 
the wiring is neat and does not cause the control box to stick 
up. Close the cover firmly.

Inter unit wiring terminal block (3)

Model

Hz

Volts

Voltage range

FMCQ50~125

50

220-240

min. 198-max. 264

power supply

Fan motor

Model

MCA

MFA

KW

FLA

FMCQ50

0.6

16 A

0.056

0.5

FMCQ60

0.9

16 A

0.056

0.7

FMCQ71

0.9

16 A

0.120

0.7

FMCQ100

1.4

16 A

0.120

1.1

FMCQ125

1.9

16 A

0.120

1.5

NOTE

For details, refer to "Electrical data".

L

N

Power supply wiring

Model

Field fuses

Wire

Size

FMCQ50~125

16 A

H05VV-U3G

Local codes

Transmission wiring

Model

Wire

Size

FMCQ50~125

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to 

"Wiring example" on page 7

.

Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:

Outdoor unit - indoor unit: max. 1000 m 
(total wiring length: 2000 m)

Indoor unit - remote controller: max 500 m

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

Summary of Contents for FMCQ50A7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMCQ50A7VEB FMCQ60A7VEB FMCQ71A7VEB FMCQ100A7VEB FMCQ125A7VEB Air conditioning system...

Page 2: ...0 860 910 840 780 710 840 860 910 950 4 125 130 3 1 840 910 840 910 1 4 2 5 6 3 860 860 910 20 20 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 90 mm 7 mm 80...

Page 3: ...2 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tev...

Page 4: ...ntrol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the in...

Page 5: ...controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent lights...

Page 6: ...er for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing and on the paper pattern for installation Aft...

Page 7: ...ing stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing...

Page 8: ...f drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water See figure 11 Check the drainage flow In case electric wiring work is finishe...

Page 9: ...ground wire to the grounding terminal While doing this pull the wires inside through the hole in the casing and clamp the wires along with other wires using a clamp as indicated in the figure Unit tra...

Page 10: ...Make sure the cover closes tight Incomplete connections could result in overheating and in the worse case electric shock or fire WIRING EXAMPLE Fit the power supply wiring of each unit with a switch a...

Page 11: ...Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by 10 2 0X or 10 6 0X 6 Thermostat sensor in group control...

Page 12: ...utral detergent 4 Remove water and dry in the shade 5 Install the air filter back in place perform actions 2 to 4 in the illustration in reverse order Attach the air filter to the suction grille by ha...

Page 13: ...of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation NOTES NOTE Do not use gasoline benzene thinner polishing powder liquid insecticide...

Page 14: ...H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector ada...

Page 15: ...1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1...

Page 16: ...4PW47629 1 Copyright Daikin...

Reviews: