Application Information
Refrigerant Piping
If the pipe length is too long, both the capacity and the reliability of the unit will decrease. As the number
of bends increases, resistance of the piping system to the refrigerant
fl
ow increases and thus lowering the
capacity, as a result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated as below
Model
Indoor
FL(Y)15EXV1
FL(Y)20EXV1
FL(Y)25EXV1
FL(Y)28EXV1
Outdoor
R(Y)15CXV1
R(Y)20CXV1 /
RY18CXV1
R(Y)25CXV1
R(Y)28CXV1
Max. Length, m
12
15
Max. Elevation, m
5
8
Model
Indoor
FL(Y)28EXV1
FL(Y)40EXV1
FL(Y)40/50EXV1
FH(Y)62CXV1
Outdoor
R(Y)30DXV1
R(Y)40DXV1
R(Y)40/50DXY1
R(Y)61DXY1
Max. Length, m
45
35
Max. Elevation, m
25
15
Piping sizes (
fl
are connection type) are as follows:
R22
Model
R(Y)15CXV1
R(Y)20CXV1
R(Y)25/28CXV1 /
R(Y)30DXV1
R(Y)35/40DXV1 /
R(Y)40/50DXY1
R(Y)61DXY1
Liquid, mm / in
6.35 / 1/4
6.35 / 1/4
9.52 / 3/8
9.52 / 3/8
12.7 / 1/2
Suction, mm / in
12.70 / 1/2
15.88 / 5/8
15.88 / 5/8
19.05 / 3/4
19.05 / 3/4
Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.6m, then additional
charge after vacuuming is not necessary. If the piping length is more than 7.6m, then use the additional
charge (g) per additional 1m length as tabulated:
R22 – Cooling Only
Indoor
FL15EXV1 FL20EXV1 FL25EXV1
FL28EXV1
FL35EXV1
FL40EXV1
FL50EXV1 FH62CXV1
Outdoor
R15CXV1 R20CXV1 R25CXV1 R28CXV1 R30DXV1 R35DXV1
R40DXV1
(1PH)
R40DXY1
(3PH)
R50DXY1 R61DXY1
Add. Charge, g/m
15
16
39
40
55
56
55
55
55
102
R22 – Heatpump
Indoor
FLY15EXV1 FLY20EXV1 FLY25EXV1
FLY28EXV1
FLY35EXV1
FLY40EXV1
FLY50EXV1 FHY62CXV1
Outdoor
RY15CXV1 RY20CXV1 RY25CXV1 RY28CXV1 RY30DXV1 RY35DXV1
RY40DXV1
(1PH)
RY40DXY1
(3PH)
RY50DXY1 RY61DXY1
Add. Charge, g/m
25
22
56
55
55
54
54
55
55
101
Note: Installation and maintenance are to be performed only by quali
fi
ed personnel who
are familiar with local codes and regulations, and experienced with this type of
equipment.
DAIKIN_FL(Y).indb 13
DAIKIN_FL(Y).indb 13
9/27/2012 12:13:19 PM
9/27/2012 12:13:19 PM
Summary of Contents for FHY62CXV1
Page 2: ......
Page 58: ...55 Wiring Diagrams Indoor Unit Model FL35EXV1 Outdoor Unit Model R35DXV1 ...
Page 59: ...56 Wiring Diagrams Indoor Unit Model FL40EXV1 Outdoor Unit Model R40DXV1 ...
Page 63: ...60 Wiring Diagrams Heatpump Indoor Unit Model FLY15EXV1 Outdoor Unit Model RY15CXV1 ...
Page 64: ...61 Wiring Diagrams Indoor Unit Model FLY20 25EXV1 Outdoor Unit Model RY18 20 25CXV1 ...
Page 66: ...63 Wiring Diagrams Indoor Unit Model FLY28EXV1 Outdoor Unit Model RY30DXV1 ...
Page 67: ...64 Wiring Diagrams Indoor Unit Model FLY35EXV1 Outdoor Unit Model RY35DXV1 ...
Page 68: ...65 Wiring Diagrams Indoor Unit Model FLY40EXV1 Outdoor Unit Model RY40DXV1 ...
Page 69: ...66 Wiring Diagrams Indoor Unit Model FLY40EXV1 Outdoor Unit Model RY40DXY1 ...
Page 78: ......