![background image](http://html1.mh-extra.com/html/daikin/fhy35bve-x-2/fhy35bve-x-2_operation-manual_2459272011.webp)
English
8
Operate in the following order.
•
The timer is operated in the following two ways.
•
Programming the stop time (
)
.... The system stops
operating after the set time has elapsed.
•
Programming the start time (
)
.... The system starts
operating after the set time has elapsed.
•
The timer can be programmed a maximum of 72 hours.
•
The start and the stop time can be simultaneously
programmed.
TIMER MODE START/STOP
Press the TIMER MODE START/STOP button
several times and select the mode on the
display.
The display flashes.
For setting the timer stop .... “
”
For setting the timer start .... “
”
PROGRAMMING TIME
Press the PROGRAMMING TIME button and set
the time for stopping or starting the system.
When this button is pressed, the time
advances by 1 hour.
When this button is pressed, the time
goes backward by 1 hour.
TIMER ON/OFF
Press the TIMER ON/OFF button.
The timer setting procedure ends.
The display “
or
” changes from flash-
ing light to a constant light.
Refer to figure 4 on page [1]
NOTE
•
When setting the timer Off and On at the same
time, repeat the above procedure from
to
once again.
When the timer is programmed to stop the system
after 3 hours and start the system after 4 hours, the
system will stop after 3 hours and then 1 hour later
the system will start.
•
After the timer is programmed, the display shows
the remaining time.
•
Press the TIMER ON/OFF button once again to
cancel programming. The display vanishes.
PROGRAM TIMER OPERATION
1
2
3
1
3
Observe the following precautions to ensure the
system operates.
•
Adjust the room temperature properly for a com-
fortable environment. Avoid excessive heating or
cooling.
•
Prevent direct sunlight from entering a room dur-
ing cooling operation by using curtains or blinds.
•
Ventilate the room regularly.
Using the unit for long periods of time requires
attentive ventilation of the room.
•
Keep doors and windows closed. If the doors and
windows remain open, room air will flow out and
cause to decrease the effect of cooling and heat-
ing.
•
Do not place other heaters directly below the
indoor unit.
They may deform due to the heat.
•
Never place objects near the air inlet and the air
outlet of the unit. It may cause deterioration in the
effect or stop in the operation.
•
Turn off the main power supply switch when it is
not used for long periods of time. When the main
power switch is turned on, some watts of electricity
is being used even if the system is not operating.
Turn off the main power supply switch for saving
energy. When reoperating, turn on the main power
supply switch 6hours before operation for smooth
running (Refer to MAINTENANCE).
•
When the display shows “
”
(TIME TO CLEAN
AIR FILTER), ask a qualified service person to
clean the filters (Refer to MAINTENANCE).
•
Fully use the function of air flow direction adjust.
Cold air gathers on the floor, and warm air gathers
in the ceiling.
Set the air flow direction parallel during cooling or
dry operation, and set it downwards during heat-
ing operation.
Do not let the air blow directly to a person.
•
It takes time for the room temperature to reach the
set temperature.
We recommend starting the operation in advance
using timer operation.
7. OPTIMUM OPERATION
01_en_3P170549-4C.fm Page 8 Tuesday, November 6, 2007 9:36 AM
Summary of Contents for FHY35BVE x 2
Page 17: ...3P170549 4C EM00A035B 0712 HT ...