Field Setting from Remote Controller
ESIE15-13C
66
Field Setting
2.2
Wireless Remote Controller
Setting
To set the field settings, you have to change:
“Mode No.”
“First code No.”
“Second code No.”.
To change the field settings, proceed as follows:
RESERVE button
INSPECTION/TEST button
Mode No.
Field setting mode
UP button
DOWN button
First code No.
Second code No.
MODE button
Step
Action
1
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the “Field setting mode”.
2
Press the MODE button to select the desired “Mode No.”.
3
Press the UP button to select the “First code No.”.
4
Press the DOWN button to select the “Second code No.”
5
Press the RESERVE button to set the present settings.
6
Press the INSPECTION/TEST button to return to the “Normal mode”.