background image

10

English

7.

DRAIN PIPING WORK

(1) Carry out drain piping.

• Carry out drain piping so that drainage is ensured.
• Drain piping can be connected from the following direc-

tions: For right rear/right side, refer to Fig. 18 of ‘‘6. 
REFRIGERANT PIPING WORK’’, and for left rear/left 
side, refer to Fig. 21.

• When conducting left rear/left side drain piping, remove 

the protection net. Then, remove the drain socket cap 
and insulation material applied to left side drain socket 
and apply them to the right side drain socket. When doing 
this, insert the drain socket cap all the way in to prevent a 
water leakage.
After the drain hose (1) (accessory) installing, attach the 
protection net by reversing the steps taken to remove it. 
(Refer to Fig. 22)

• Select the piping diameter equal to or larger than that of 

the drain hose (1) (accessory) (polyvinyl chloride piping, 
nominal diameter 20mm, outside diameter 26mm).

• Install the drain piping as short as possible with down-

ward inclination of 1/100 or more by avoiding air stagna-
tion. (Refer to Fig. 23 and Fig. 24)
(It may cause abnormal sound such as bubbling noise.)

CAUTION

If drain stagnates in the drain piping, the piping may be 
clogged.

• Make sure to use the attached drain hose (1) and metal 

clamp (2). Also, insert the drain hose (1) into the root of 
the drain socket, and tighten the metal clamp (2) at the 
root of the drain socket tightly. 
(Refer to Fig. 25 and Fig. 26)
(Install the metal clamp (2) so that the tightening part is in 
the range of about 45°as shown in the Fig. 26.)
(Do not bond the drain socket and drain hose. If so, main-
tenance and inspection for the heat exchanger and oth-
ers cannot be conducted.)

CAUTION

If an old drain hose or an elbow or a clamp is used, it may 
cause water leakage.

• Bend the tip of the metal clamp (2) so that the sealing 

material does not bulge. (Refer to Fig. 26)

• When performing insulation, wind the large sealing mate-

rial (Large) (8) attached starting from the base of the 
metal clamp (2) and drain hose (1) in the direction of the 
arrow. (Refer to Fig. 25 and Fig. 26)

• Be sure to insulate all drain piping running indoors.

Back side (sheet metal)
Detach parts

Putty or insulation

(field supply)

Left side
Drain piping

Left side
Detach parts

Left rear side
Drain piping

Fig. 21

Protection net

Fixing 
screw for
protection net

Fig. 22

Good

Wrong

Supports

1-1.5m

Downward inclination of 1/100 or more

Do not lift

Make sure there is no slack

Make sure it is not in the water

Fig. 23

Fig. 24

Sealing material (Large) (8)
(accessory)

Metal clamp (2)
 (accessory)

Drain hose (1)
 (accessory)

Fig. 25

Do not make a gap to avoid 
dew condensation.

Sealing 
material 
(Large) (8)
(accessory)

Sealing material 
(Large) (8)
(accessory)

Metal clamp (2)

(accessory)

Metal clamp (2)
(accessory)

Drain hose (1)

(accessory)

Drain hose (1)
(accessory)

(For left rear/
left side)

(For right 
back / right side)

Inserting direction 
for the screw driver

approx. 45°

approx. 45°

Sealing material 
(Large) (8)
Applying direction

Fig. 26

Tightening part

Metal clamp (2) (accessory)

Drain hose (1) (accessory)

approx. 45°

Bend the tip without 
tearing the sealing 
material (Large) (8)

4PEN469440-1B.book  Page 10  Tuesday, April 4, 2017  11:06 AM

Summary of Contents for FHA100AVEB

Page 1: ...INSTALLATION MANUAL FHA35AVEB FHA50AVEB FHA60AVEB FHA71AVEB FHA100AVEB FHA125AVEB FHA140AVEB Split System air conditioners ...

Page 2: ... em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C 13 Huom...

Page 3: ...nt does not exceed the concentration limit in the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installation work Failure to use the specified parts may result in the air condi tioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand i...

Page 4: ...re 2 BEFORE INSTALLATION When unpacking and moving the indoor unit after unpacked do not apply force to the piping refrigerant and drain and resin parts Make sure to check in advance that the refrigerant to be used for installation work is according to the Outdoor Unit specifi cation The air conditioner will not properly operate if a wrong refrig erant is used For installation of the outdoor unit ...

Page 5: ...nual Installation manual Declaration of confor mity Quantity 2 pcs 2 pcs Shape M4 12 Items to be checked In case of defec tive Check column Are the indoor and outdoor units rigidly fixed Drop vibration noise Are the installation work of the outdoor and indoor units com plete Does not operate burnout Have you carried out a leakage test with the test pressure specified in the outdoor unit installati...

Page 6: ...ter in a room where an electronic light ing type inverter or rapid start type fluorescent lamp is installed The sound pressure level is less than 70 dBA 2 Use hanging bolts for installation Investigate if the installation place can withstand the mass of the indoor unit and if necessary hang the indoor unit with bolts after it is reinforced by beams etc Refer to the installation pattern paper for t...

Page 7: ...ing inlet And make the hole How to use the pattern see the picture bellow For pattern layout overview see 14 PATTERN LAYOUT OVERVIEW a reinforced plate a reinforced plate a a Model name FHA A B C D E F G H J Class 35 50 960 920 378 324 270 375 398 377 260 Class 60 71 1270 1230 533 479 425 530 553 532 415 Class 100 125 140 1590 1550 693 639 585 690 713 692 575 G H J 5 175 200 View from the front Le...

Page 8: ... direction to remove Refer to Fig 8 CAUTION Do not remove the tape milky white applied to the outside of the indoor unit It may cause electric shocks or a fire 6 Install the hanging bolts Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foundation bolts...

Page 9: ...installed on a place that can withstand the mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulat...

Page 10: ... prevent the piping from getting exposed Then tighten the both ends of insulating material with the clamp 4 Wrap the sealing material Small 9 around the joint insulat ing material 6 flare nut section only the gas piping side Make sure to bring the seam of joint insulating material 6 and 7 to the top Piping size mm Tightening torque N m Dimension for processing flare A mm Flare shape ø 6 4 15 7 1 5...

Page 11: ...hen brazing refrigerant piping Use phos phor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 that does not require flux If chlorinated flux is used the piping will be corroded and in addition if fluorine is contained the refrigerant oil will be deteriorated and the refrigerant circuit will be affected badly 3 When carrying out leakage test of refrigerant piping and the indoo...

Page 12: ...o that the tightening part is in the range of about 45 as shown in the Fig 26 Do not bond the drain socket and drain hose If so main tenance and inspection for the heat exchanger and oth ers cannot be conducted CAUTION If an old drain hose or an elbow or a clamp is used it may cause water leakage Bend the tip of the metal clamp 2 so that the sealing material does not bulge Refer to Fig 26 When per...

Page 13: ...ING WORK 8 1 GENERAL INSTRUCTIONS Make certain that all electric wiring work is carried out by qualified personnel according to the applicable legislation and this installation manual using a separate circuit Insuffi cient capacity of the power supply circuit or improper electri cal construction may lead to electric shocks or a fire Make sure to install an earth leakage breaker in accordance with ...

Page 14: ...e the screw head and a proper tightening cannot be carried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals Conduct wiring so that the earth lead comes out from the notched part of the cup washer Otherwise earth lead con tact will be insufficient and grounding effect may be lost Do not carry out soldering finish when stranded w...

Page 15: ...gether they may be affected by electric noise outside noise and cause malfunction or failure Remote controller wiring R10 or more Terminal block X2M R10 or more Transmission and earth wiring connection method R10 or more Earth terminal Outdoor unit Indoor unit Terminal block Terminal block Terminal numbers of outdoor and indoor units must be matched Transmission wiring connection method Remote con...

Page 16: ...cal documents NOTE NOTE NOTE NOTE Terminal numbers of outdoor and indoor units must be matched When implementing group control When using as a pair unit or as a master unit for simultane ous operation system you may carry out simultaneous start stop group control up to 16 units with the remote controller Refer to Fig 34 In this case all the indoor units in the group will operate in accordance with...

Page 17: ...ttings shown by in the table indicate those when shipped from the factory The method of setting procedure and operation is shown in the installation manual attached to the remote controller Note Though setting of Mode No is carried out as a group if you intend to carry out individual setting by each indoor unit or confirmation after setting carry out set ting with the Mode No shown in the parenthe...

Page 18: ...e SECOND CODE No to 02 individual setting so that the slave unit can be individually set Table 7 2 Perform field setting Refer to 11 1 to 11 5 for the master unit 3 Turn off the main power supply switch after 2 is finished 4 Detach remote controller from the master unit and connect it to the slave unit 5 Turn on the main power supply switch again and as in 1 change the SECOND CODE No to 02 individ...

Page 19: ... 4 On the user interface set the unit to cooling operation mode P1P2 P1P2 1 2 3 P1P2 1 2 3 P1P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 1 2 3 Outdoor unit Outdoor unit NOTE NOTE Indoor unit Master Indoor unit Master Indoor unit Slave Indoor unit Slave Remote controller Remote controller 3 7 1 2 4 9 5 6 Earth leakage breaker Earth leakage breaker Fig 39 Power supply 220 240V 50Hz Power supply 220 240V 50Hz A...

Page 20: ...door and indoor unit are incompatible Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Malfunc tion code Descriptions and mea sures Remarks A1 Indoor Printed Circuit Board failure A3 Drain level abnormal A5 Freeze up protector or stopped by high pressure control NOTE 1 A6 Indoor fan motor over load over current lo...

Page 21: ...rcur rent Outdoor unit The compressor engines and turbines may be experiencing a ground fault or short circuit L8 Electric thermal Outdoor unit The compressor engines and turbines may be overloaded and disconnected L9 Stall prevention Outdoor unit The compressor may be locked LC Transmission malfunc tion between inverter and outdoor control unit Out door unit P1 Open phase Outdoor unit P3 DCL sens...

Page 22: ...r until the interior finish work is completed If the air conditioner is operated the inside of the indoor units may be polluted by substances generated from the coating and adhesives used for the interior finish work and cause water splash and leakage To the operator carrying out test operation After test operation is completed before delivering the air con ditioner to the customer confirm that th...

Page 23: ...DEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL ...

Page 24: ...22 English 14 PATTERN LAYOUT OVERVIEW ...

Page 25: ......

Page 26: ...4P469440 1B 2017 04 Copyright 2017 Daikin ...

Reviews: