Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

Drain piping work

Installation of drain piping

Install the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

Install the drain pipes.
- Keep piping as short as possible and slope it downwards at a 

gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

- Keep pipe size equal to or greater than that of the connecting 

pipe (vinyl pipe of 20 mm nominal diameter and 26 mm outer 
diameter).

- Push the supplied drain hose as far as possible over the 

drain socket.

- Tighten the metal clamp as indicated in the illustration.

- After the testing of drain piping is finished, attach the drain 

sealing pad (4) supplied with the unit over the uncovered part 
of the drain socket (= between drain hose and unit body).

- Wrap the supplied large sealing pad over the metal clamp 

and drain hose to insulate and fix it with clamps.

- Insulate the complete drain piping inside the building (field 

supply).

- If the drain hose cannot be sufficiently set on a slope, fit the 

hose with drain raising piping (field supply).

How to perform piping 

(See figure 6)

- Connect the drain hose to the drain raising pipes, and 

insulate them.

- Connect the drain hose to the drain outlet on the indoor unit, 

and tighten it with the clamp.

Precautions
- Install the drain raising pipes at a height of less than H2.
- Install the drain raising pipes at a right angle to the indoor 

unit and no more than 300 mm from the unit.

- To prevent air bubbles, install the drain hose level or slightly 

tilted up (

75 mm).

- Drain pump mounted in this unit is high lift type. 

Characteristic of this pump is that the higher pump is the 
lower drainage sound becomes. Therefore drain pump height 
of 300mm is recommended.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

2

3

4

5

6

6

2

1

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)
NOTE: Bend the tip of the metal clamp without tearing 
the sealing.

4

Large sealing pad (supplied with the unit)

5

Drain piping (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)

5

Drain hose (supplied with the unit)

6

Metal clamp (supplied with the unit)

Decoration panel

H2

BYFQ60C

645 mm

BYFQ60B

630 mm

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 8

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

5

2

3

4

3

4

2

A

A'

A-A'

1

Summary of Contents for FFQ25C2VEB

Page 1: ...INSTALLATION MANUAL FFQ25C2VEB FFQ35C2VEB FFQ50C2VEB FFQ60C2VEB Split System air conditioners...

Page 2: ...4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 BYFQ60C BYFQ60B PP H2 PP PP PP BYFQ60C BYFQ60B PP H1 H2 PP 2 1 5 4 3 8 8 2 4 7 1 9 10 5 5 2 7 4 3 a 2 3 4 2 5 6 575 a 700 700 a 575 8 7 3 2 1 4 1 5 6 575 a 62...

Page 3: ...y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pa...

Page 4: ...t Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting th...

Page 5: ...er it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher tha...

Page 6: ...ing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult t...

Page 7: ...ng exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Fina...

Page 8: ...et on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the d...

Page 9: ...the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit...

Page 10: ...hen attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insulation material field supply thus...

Page 11: ...de No First code No and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according t...

Page 12: ...uction and check after installation is finished on page 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit...

Page 13: ...uit board A5P Printed circuit board Wired remote controller R4T Thermistor air Connector for optional parts X24A Connector wiring remote controller X33A Connector adaptor for wiring X35A Connector pow...

Page 14: ......

Page 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Page 16: ...4P341094 1B 2013 04 Copyright 2013 Daikin...

Reviews: