SiUS091628EA
Outdoor Unit
Printed Circuit Board Connector Wiring Diagram
10
4. Outdoor Unit
4.1
RX09/12QMVJU
Main PCB (PCB1)
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
1) S20
Connector for electronic expansion valve coil
2) S30
Connector for compressor
3) S40
Connector for overload protector
4) S71
Connector for DC fan motor
5) S80
Connector for four way valve coil
6) S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
7) HL1, HN1, S
Connector for terminal block
8) E1, E2
Terminal for ground wire
9) HR1, HR2
Connector for reactor
10)FU1, FU2
Fuse (3.15 A, 250 V)
11)FU3
Fuse (20 A, 250 V)
12)J6
Jumper for facility setting
∗
Refer to page 125 for details.
12)LED A
LED for service monitor (green)
13)V2, V3, V150
Varistor
E1, E2
FU3
V150
V2
V3
FU1
FU2
HR1
HR2
S20
LED A
S90
S30
J6
S40
2P415459-46
HL1, HN1, S
S80
S71