Field Settings
SiUS091628EA
125
Trial Operation and Field Settings
After Setting
Affix corresponding unit number labels onto both air outlet of the decoration panel and onto back of
the wireless remote controller.
Note:
Set the unit No. of the receiver and the wireless remote controller to be the equal. If the settings
differ, the signal from the remote controller cannot be transmitted.
4.5
Facility Setting (cooling at low outdoor temperature)
Outline
This function is limited only for facilities (the target of air conditioning is equipment such as
computers). Never use it in a residence or office (the space where there is a human).
Details
Cutting jumper 6 (J6) on the circuit board will extend the operation range to –10°C (14°F).
Installing an air direction adjustment grille (sold separately) will further extend the operation
range to –20°C (–4°F). In these cases, the unit will stop operating if the outdoor temperature
falls below –20°C (–4°F), restarting once the temperature rises above this level.
1. Remove the top plate of the outdoor unit. (09/12 class: 3 screws, 15/18 class: 6 screws)
2. Remove the front plate. (09/12 class: 4 screws, 15/18 class: 8 screws)
3. Cut the jumper (J6) of the PCB inside.
For the location of the jumper, refer to pages 10, 11.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Caution
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off
when using facility settings.
Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
(R24066)
Summary of Contents for FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU
Page 12: ...SiUS091628EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiUS091628EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 120: ...Check SiUS091628EA 109 Service Diagnosis 15 18 class R20701 1 2 3 4 Multimeter...
Page 122: ...Check SiUS091628EA 111 Service Diagnosis 15 18 class R20704 W V U DC_P1 DC_N1...