SiUS071735EA
Field Settings
Trial Operation and Field Settings
118
4. Field Settings
4.1
How to Change the Field Settings
Outline
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
Note:
When using 2 remote controllers for 1 indoor unit, change the field settings from MAIN remote
controller. Note that the field settings can not be set from SUB remote controller.
Wired Remote
Controller
(BRC1E73)
a
Unit No.
b
First code No.
c
Second code No.
d
Mode
1. Press and hold
Cancel
button for 4 seconds or longer.
Service settings menu is displayed.
2. Select
in the Service Settings menu, and press
Menu/OK
button.
Field settings screen is displayed.
a
b
c
d
(R18831)
<Basic screen>
1
Set temperature
28
˚C
Fan
Return
Press the menu button
Press and hold
Cancel
button for 4 seconds or
longer during backlight lit.
Field Settings
<Service settings menu screen>
2
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Press
Menu/OK
button.
Summary of Contents for FDMQ09RVJU
Page 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A ...