background image

8

OPERATION PROCEDURE

 Refer to figure 1 on page 3 

• Operation procedure

Read the operation manual attached to the remote control-
ler.

• To protect the unit, turn on the main power supply switch 6 

hours before operation.

• If the main power supply switch is turned off during opera-

tion, operation will restart automatically after the power 
turns back on again.

COOLING · HEATING · AUTOMATIC · FAN AND 
PROGRAM DRY Operation
Operate in the following order.

1. Press OPERATION MODE SELECTOR button several 

times and select the OPERATION MODE of your choice 
as follows.

„

COOLING Operation ................................ “

„

HEATING Operation ................................. “

„

AUTOMATIC Operation ............................ “

• In this operation mode, COOL/HEAT changeover is 

automatically conducted.

„

FAN Operation ...........................................“

„

DRY Operation ..........................................“

• The function of this program is to decrease the 

humidity in your room with the minimum temperature 
decrease.

• Micro computer automatically determines TEMPER-

ATURE and FAN SPEED.

• This system does not go into operation if the room 

temperature is below 16°C.

 Refer to figure 3 on page 3 

2. Press ON/OFF button.

OPERATION lamp lights up and the system starts 
OPERATION.

ADJUSTMENT

3. Press TEMPERATURE SETTING button and program 

the setting temperature.

Each time this button is pressed, setting temper-
ature rises 1°C.
Each time this button is pressed, setting temper-
ature lowers 1°C.

NOTE

• Set the temperature within the operation range shown in 

the table on page 6.

• The temperature cannot be set in the fan operation.

4. Press FAN SPEED CONTROL button.

High or Low fan speed can be selected.

NOTE

• In the heating operation, the fan stops during defrosting or 

at startup.  It does not indicate any abnormality.

5. Press AIR FLOW DIRECTION ADJUST button.

Refer to page 8 for details.

STOPPING THE SYSTEM

6. Press ON/OFF button once again.

• OPERATION lamp goes off, and the system stops 

OPERATION.

• The fan may keep on running for about 1 minute after 

the heating operation stops.
(To start the next operation smoothly.)

ATTENTION:

• Do not turn OFF power immediately after the unit stops.

Then, wait no less than 5 minutes. Water is leaking or 
there is something else wrong with the unit.

• When the operation is started again immediately after being 

stopped, when the operation mode is changed over, or when 
the TEMPERATURE SETTING button is pressed then 
returned soon, the air conditioner will start the operation 
automatically about 5 minutes later (because the air condi-
tioner is controlled so that excessive load is not applied).

Characteristics of the heating operation

(1) DEFROST OPERATION

• As the frost on the coil of an outdoor unit increase, 

heating effect decreases and the system goes into 
DEFROST OPERATION.

• The indoor unit fan stops and the remote controller dis-

plays shows “

” (DEFROST/HOT START).

• After 6 to 8 minutes (maximum 10 minutes) of 

DEFROST OPERATION, the system returns to HEAT-
ING OPERATION.

(2) HOT START

• In order to prevent cold air from blowing out of an 

indoor unit at the start of heating operation, the indoor 
fan is automatically stopped. The display of the remote 
controller shows “

” (DEFROST/HOT START).

(3) OPERATION START

• For ordinary heating, it will take longer for the room 

temperature to reach the set temperature than with 
cooling. We therefore recommend starting the unit 
ahead of time using the timer operation.

ADJUSTING THE AIR FLOW DIRECTION

• Press the AIR FLOW DIRECTION button to adjust the air 

flow angle.

1. Press the AIR FLOW DIRECTION ADJUST button to 

select the air direction as shown below.

The AIR FLOW FLAP display swings 
as shown left and the air flow direction 
continuously varies. 
(Automatic swing setting)

Press AIR FLOW DIRECTION 
ADJUST button to select the air 
direction of your choice.

The AIR FLOW FLAP display stops 
swinging and the air flow direction is 
fixed. 
(Fixed air flow direction setting)

Up and down adjustment

swing

01_EN_3P177429-9S.fm  Page 8  Saturday, October 16, 2010  2:24 PM

Summary of Contents for FCQ50KVEA

Page 1: ...for purchasing this Daikin air conditioner Carefully read this operation manual before using the air conditioner It will tell you how to use the unit properly and help you if any trouble occurs This m...

Page 2: ...EST C hr hr TEST NOT AVAILABLE L H 2 9 10 3 1 4 5 6 7 13 14 15 16 17 18 19 20 21 11 8 12 a c d e l m g f h i k j e b d n RZQ100 125 140 RZQ 50 60 71 C hr H 3 figure 1 00_CV_3P177429 9S fm Page 2 Satur...

Page 3: ...N They both contain important information regarding safety Be sure to observe all precautions without fail WARNING Failure to follow these instructions properly may result in personal injury or loss o...

Page 4: ...ve oily smoke such as cooking rooms or in places with flammable gas corrosive gas or metal dust Using the product in such places may cause fire or prod uct failures Do not use flammable materials e g...

Page 5: ...ing If water gets into the remote controller there is a risk of electrical leakage and damage to electronic compo nents Watch your steps at the time of air filter cleaning or inspection High place wor...

Page 6: ...button Press the button and the system will start Press the button again and the system will stop 2 OPERATION lamp RED The lamp lights up during operation 3 DISPLAY UNDER CENTRALIZED CONTROL When thi...

Page 7: ...on running for about 1 minute after the heating operation stops To start the next operation smoothly ATTENTION Do not turn OFF power immediately after the unit stops Then wait no less than 5 minutes W...

Page 8: ...mfortable environment Avoid excessive heating or cooling Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds Ventilate the room regularly Using the unit f...

Page 9: ...shade NOTE Do not wash the air conditioner with hot water of more than 50 C as doing so may result in discoloration and or defor mation Do not expose it to fire as doing so may result in burning 4 Fi...

Page 10: ...h is connected Might there be a broken wire somewhere Contact your dealer if there are any problems Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on...

Page 11: ...ntinuous low Shah sound is heard when the system is in COOLING OPERATION or at a stop The noise is heard when the drain pump is in operation A Pishi pishi squeaking sound is heard when the system is i...

Page 12: ...it well ventilated Check if the air filter is clogged Ask a qualified service person to clean the air filters Refer to MAINTENANCE 3 The system operates but it does not sufficiently cool or heat If th...

Page 13: ...3P177429 9S EM10A035 1011 HT 00_CV_3P177429 9S fm Page 3 Saturday October 16 2010 2 12 PM...

Reviews: