17 Maintenance and service

Installer and user reference guide

28

FCAHG71~140FVEB

Split system air conditioners

4P429475-1 – 2015.12

3

Clean the air filter. Use a vacuum cleaner or wash with water. If
the air filter is very dirty, use a soft brush and neutral detergent.

4

Dry the air filter in the shadow.

5

Reattach the air filter, and close the suction grille.

6

Turn ON the power.

7

Press the 

FILTER SIGN RESET

 button.

Result: 

The 

TIME  TO  CLEAN  AIR  FILTER

  notification

disappears from the user interface.

17.1.2

To clean the suction grille

NOTICE

Do  NOT  use  water  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

1

Open the suction grille.

1

2

Remove the suction grille.

45°

1

2

3

Remove the air filter.

1

2

3

4

Clean  the  suction  grille.  Wash  with  a  soft  bristle  brush,  and
water or neutral detergent. If the suction grille is very dirty, use
a  typical  kitchen  cleaner,  leave  it  on  for  10  min,  then  wash  it
with water.

5

Reattach  the  air  filter  and  suction  grille,  and  close  the  suction
grille.

17.1.3

To clean the air outlet and outside panels

WARNING

Do  NOT  let  the  indoor  unit  get  wet. 

Possible

consequence: 

Electric shock or fire.

NOTICE

▪ Do  NOT  use  gasoline,  benzene,  thinner  polishing

powder  or  liquid  insecticide. 

Possible  consequence:

Discoloration and deformation.

▪ Do  NOT  use  water  or  air  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

▪ Do  NOT  scrub  firmly  when  washing  the  blade  with

water. 

Possible  consequence: 

The  surface  sealing

peels off.

Clean with a soft cloth. If it is difficult to remove stains, use water or
neutral detergent.

17.2

Maintenance after a long stop
period

E.g., at the beginning of the season.

▪ Check  and  remove  everything  that  might  be  blocking  inlet  and

outlet vents of indoor units and outdoor units.

▪ Clean air filters and casings of indoor units (see 

"17.1.1 To clean

the  air  filter"  on  page  27

  and 

"17.1.3  To  clean  the  air  outlet  and

outside panels" on page 28

).

▪ Turn  on  the  power  at  least  6  hours  before  operating  the  unit  in

order  to  ensure  smoother  operation.  As  soon  as  the  power  is
turned on, the user interface display appears.

17.3

Maintenance before a long stop
period

E.g., at the end of the season.

▪ Let the indoor units run in fan only operation for about half a day in

order  to  dry  the  interior  of  the  units.  Refer  to 

"15.2.2  About

cooling,  heating,  fan  only,  and  automatic  operation"  on  page  26

for details on fan only operation.

▪ Turn off the power. The user interface display disappears.

▪ Clean air filters and casings of indoor units (see 

"17.1.1 To clean

the  air  filter"  on  page  27

  and 

"17.1.3  To  clean  the  air  outlet  and

outside panels" on page 28

).

17.4

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential value: 675

Periodical  inspections  for  refrigerant  leaks  may  be  required
depending on the applicable legislation. Please contact your installer
for more information.

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

Summary of Contents for FCAHG100FVEB

Page 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71FVEB FCAHG100FVEB FCAHG125FVEB FCAHG140FVEB...

Page 2: ...lectrical wiring 15 6 4 3 Guidelines when connecting the electrical wiring 15 6 4 4 Specifications of standard wiring components 15 6 4 5 To connect the electrical wiring on the indoor unit 15 7 Confi...

Page 3: ...ilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play...

Page 4: ...here there is machinery that emits electromagnetic waves Electromagnetic waves may disturb the control system and cause malfunction of the equipment In places where there is a risk of fire due to the...

Page 5: ...3 EC 1 3 6 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical parts Disconnect the power supply...

Page 6: ...s or for commercial use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read bef...

Page 7: ...or and indoor units Combining the indoor unit with options INFORMATION For year round cooling applications with low indoor humidity conditions such as Electronic Data Processing rooms contact your dea...

Page 8: ...g the unit in and out of the site 5 2 1 Installation site requirements of the indoor unit INFORMATION Also read the following requirements General installation site requirements See the General safety...

Page 9: ...epends on the air flow directions towards the wall 1500 500 200 a A A A b c a Air outlet and corners open b Air outlet closed corners open optional blocking pad kit required c Air outlet and corners c...

Page 10: ...ng Checking the refrigerant piping Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFORMATION This chapter only describes in...

Page 11: ...d e f a b a Drain piping b Refrigerant piping c Hanger bracket pitch suspension d Unit e Ceiling opening f Decoration panel If A Then B C A C B 860 mm min 20 mm 35 mm 910 mm max 35 mm 20 mm A Ceiling...

Page 12: ...installation space and surroundings 1 Push the drain hose as far as possible over the drain pipe connection 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part...

Page 13: ...Do NOT use mineral oil on flared part NEVER install a drier to this R32 unit to guarantee its lifetime The drying material may dissolve and damage the system NOTICE Take the following precautions on...

Page 14: ...prevent creation of large quantities of oxidised film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the n...

Page 15: ...c Flat washer Tightening torques Wiring Screw size Tightening torque N m Interconnection cable indoor outdoor M4 1 18 1 44 User interface cable M3 5 0 79 0 97 6 4 4 Specifications of standard wiring c...

Page 16: ...round air flow use the table below If the distance to the floor is m Then1 FCAHG71 FCAHG100 140 M C1 C2 2 7 3 2 13 23 0 01 2 7 x 3 0 3 2 x 3 6 02 3 0 x 3 5 3 6 x 4 2 03 Setting Air flow direction This...

Page 17: ...valves failing to open can be detected Even if the user interface was set to heating operation mode the unit will run in cooling operation mode during 2 3 minutes although the user interface will disp...

Page 18: ...within 10 seconds Test run starts 3 Check operation for 3 minutes 4 Check operation of the airflow direction Action Result 1 Press Return Setting Return Setting Air Volume direction Air Volume Directi...

Page 19: ...nit are incompatible 9 Hand over to the user Once the test run is finished and the unit operates properly please make sure the following is clear for the user Make sure that the user has the printed d...

Page 20: ...0 55 55 35 35 125 130 112 153 298 840 55 55 10 40 175 340 0 675 280 330 75 180 213 A c b i g a j d h a e f b c d j e f In case of installation with self cleaning decoration panel 75 210 420 420 710 86...

Page 21: ...wall 1500 500 200 a A A A b c a Air outlet and corners open b Air outlet closed corners open optional blocking pad kit required c Air outlet and corners closed optional blocking pad kit required B Mi...

Page 22: ...side forced off or on off control operation can be selected by the remote controller See installation manual for more details 5 Connect power of adapter for wiring to terminal block X2M of indoor unit...

Page 23: ...staller and user reference guide 23 FCAHG71 140FVEB Split system air conditioners 4P429475 1 2015 12 X A PCB connector X M Terminal strip X Y Connector Z C Noise filter ferrit core Z F Noise filter Op...

Page 24: ...o fan Number of fans 1 Number of motors output 48 W 106 W Fan speed 5 steps Piping connections Liquid outer diameter 9 52 mm flare Gas outer diameter 15 9 mm flare Drain outer diameter Vinyl pipe 25 m...

Page 25: ...ARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is not good for your health to e...

Page 26: ...r Contact your dealer for details 15 2 4 To operate the system 1 Press the operation mode selector button on the user interface several times and select the operation mode of your choice Cooling opera...

Page 27: ...s blocked 17 Maintenance and service NOTICE Never inspect or service the unit by yourself Ask a qualified service person to perform this work However as end user you may clean the air filter suction g...

Page 28: ...move stains use water or neutral detergent 17 2 Maintenance after a long stop period E g at the beginning of the season Check and remove everything that might be blocking inlet and outlet vents of ind...

Page 29: ...leaks into a room where combustible air from fan heaters gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before res...

Page 30: ...or indoor unit is not blocked by obstacles Remove any obstacle and make it well ventilated Check if the air filter is not clogged see 17 1 1 To clean the air filter on page 27 Check the temperature s...

Page 31: ...frost operation This is the noise of refrigerant caused by flow stop or flow change 18 1 9 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused...

Page 32: ...015 12 Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation Field supply Equipment not made by...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P429475 1 2015 12 Copyright 2015 Daikin...

Reviews: