8. DUST FROM THE INDOOR UNITS

A “Pishi-pishi” squeaking sound is heard when 

Draining water or motor rotation sound after 
the indoor unit stop.
This sound is heard when cooling operation stop, 
the drain pump operates and then stop.
Wait approximately 5 minutes.

the air conditioner is in operation or after the 

stop of operation.
Expansion and contraction of resin parts caused by 

temperature change makes this noise.

Dust may blow out from the unit after starting 

operation from long resting time.
Dust absorbed by the unit blows out.

9. THE INDOOR UNITS GIVE OFF ODOURS

During operation
The unit absorbs the smell of rooms, furniture, 

cigarettes, etc., and then emits them.

If odour is a concern, you can set to zero fan speed 

when the indoor temperature reaches the set 

temperature.

For details, contact your local dealer.

Check if fuse has blown.

Turn off the power supply.

Contact your local dealer.
Check if the power circuit breaker is blown.

If the tab of power circuit breaker is in the OFF position, 

turn the power on with the power circuit breaker switch.

If the tab of power circuit breaker is in the trip position 

do not turn the power on with the power circuit breaker 

switch.

Contact your local dealer.

Check if there is a power failure.

Wait until power is restored. If power failure occurs 

during operation, the air conditioner automatically 

restarts immediately after the power supply recovers.

10. THE AIR CONDITIONER DOES NOT COOL 

      EFFECTIVELY

Read the operation manual that attached to the 

outdoor unit.

The air conditioner is operating in the PROGRAM 

DRY OPERATION.
This is because program dry mode operates so that 

the indoor temperature decreases as little as possible.

Lower the indoor temperature using the COOLING 

OPERATION, and then use the PROGRAM DRY 

OPERATION.

(Refer to “

CHARACTERISTICS OF THE PROGRAM 

DRY OPERATION” on page 5.)
Read through characteristics of the COOLING 

OPERATION, characteristics of the HEATING 

OPERATION, and characteristics of the PROGRAM 

DRY OPERATION on page 5.

11

Please check before requesting a service.

1. If the air conditioner does not operate at all.

Check if the air inlet or outlet of outdoor or indoor unit 

is blocked by obstacles. 

Remove the obstacle and make it well-ventilated.

The horizontal blades at the air outlet are closed while 

the indoor stops.
Check if the air filter is clogged. Ask a qualified service 

person to clean the air filters. 

A decrease in the airflow volume of the air conditioner 

will result and the performance of the air conditioner will 

be degraded and power consumption will increase if the 

air filter is clogged with dust or dirt.

In addition, this may cause dew condensation at the air 

outlet.

(Refer to “

8. MAINTENANCE” on page 7.)

2. If the air conditioner stops after operating the 

air conditioner.


Check if the air inlet or outlet of outdoor or indoor unit is 

blocked by obstacles. Remove the obstacle and make 

it well-ventilated.

The horizontal blades at the air outlet are closed while 

the unit stops.

Obstacles decrease the fan speed, and cause 

performance decrease and breakage when discharged 

air is suctioned.

They cause a waste of electricity, increase operating 

noise, or that may stop the devices. 
Check if the air filter is clogged. Ask a qualified service 

person to clean the air filters.

A decrease in the airflow volume of the air conditioner 

will result and the performance of the air conditioner 

will be degraded and power consumption will increase 

if the air filter is clogged with dust or dirt.

In addition, this may cause dew condensation at the air 

outlet.

(Refer to “

8. MAINTENANCE” on page 7.)

Check if the set temperature is not proper.

Set to an appropriate temperature, fan speed, and 

discharge direction.
Check if the FAN SPEED button is set to LOW SPEED.

Set to an appropriate temperature, fan speed, and 

discharge direction.
Check if the airflow direction is not proper. 

Set to an appropriate temperature, fan speed, and 

discharge direction.
Check if the doors or the windows are open.

Shut doors or windows to prevent wind from coming in.
Check if the ventilation fan is in operation.
Check if direct sunlight enters the room (when cooling).

Use curtains or blinds.
When there are too many inhabitants in the room

(when cooling).
Check if the heat source of the room is excessive 

(when cooling).

3. The air conditioner operates but it does not 

sufficiently cool or heat.

Tab

Trip position

Power circuit breaker

(Earth leakage breaker)

ON

OFF

Are you sure that the ON/OFF timer operation is not 

used?

Turn off the ON/OFF timer.

Please refer to operation manual attached to the 

remote controller.
Are you sure that any remote control device is not 

connected?

Contact the central control room that directed the stop.
Are you sure that the display for centralized control is 

not lit?

Contact the central control room that directed the stop.

4. Operation was performed or stopped although the 

ON/OFF button was not pressed.

10. TROUBLE SHOOTING

Summary of Contents for FCA50CVMA

Page 1: ...dipasang di langit langit Model aliran deteksi baru FCA50CVMA FCA60CVMA FCA71CVMA FCA85CVMA FCA100CVMA FCA125CVMA FCA140CVMA FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM FCF50CVM4 FCF60CVM...

Page 2: ......

Page 3: ...an bersama panduan pengoperasian untuk unit luar ruang Setelah membaca panduan simpanlah untuk referensi kelak Thank you for purchasing this Daikin air conditioner Carefully read this operation manual...

Page 4: ...keluarkan dari remote control dan dibuang terpisah sesuai dengan peraturan daerah dan nasional yang terkait DISPOSAL REQUIREMENTS Disposal requirements Your air conditioning product is marked with thi...

Page 5: ...SAFETY PRECAUTIONS The appliance must be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pier...

Page 6: ...conditioner is not operating Therefore switch off the main power switch to save energy When resuming operation to ensure smooth running turn on the main power switch 6 hours before operating the air...

Page 7: ...ol and two remote controller control systems Please do not change the combination and settings for the group operation and two remote controllers control systems by yourself but be sure to ask your lo...

Page 8: ...of the air conditioner consult your dealer Regarding drainage of drain pipe Is the drain pipe executed to perform complete drainage If Operation procedure Read the operation manual attached to the re...

Page 9: ...unit turn on The remote controller displays the fan speed that is set After maximum 10 minutes of the DEFROST OPERATION the air conditioner returns to the HEATING OPERATION The airflow direction becom...

Page 10: ...oid excessive heating or cooling Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds Keep doors and windows closed If the doors and windows remain open ro...

Page 11: ...or rods in the air inlet air outlet or air blade The fan is rotating at high speed so you would get injured Do not wash the air conditioner with water It may cause electric shocks or a fire due to lea...

Page 12: ...may cause discoloration and deformation When drying the filter do not heat it with fire It may cause burning Do not use such as gasoline benzine thinner polishing powder and liquid insecticide sold i...

Page 13: ...moothly and to protect air conditioner The display on the remote controller will be shown when the power circuit breaker is turned on HEATING OPERATION within 6 hours after the power is supplied to th...

Page 14: ...door unit starts This sound is generated when the motors for driving the horizontal blades are working It will quiet down after about a minute A low continuous flow Shuh sound which is heard when the...

Page 15: ...ice person to clean the air filters A decrease in the airflow volume of the air conditioner will result and the performance of the air conditioner will be degraded and power consumption will increase...

Page 16: ...h If the ON OFF switch does not properly work Measure Turn off the main power switch If water leaks from the indoor unit Measure Stop the operation If a malfunction occurs either one of the following...

Page 17: ...gakibatkan kerusakan sengatan listrik atau bahaya kebakaran Tanyakan kepada dealer di daerah Anda tentang pekerjaan pemasangan Mengerjakannya sendiri dapat mengakibatkan kebocoran air sengatan listrik...

Page 18: ...n hewan atau karya seni karena dapat menyebabkan efek samping yang merugikan pada kinerja kualitas dan atau ketahanan benda tersebut Jangan melepas pelindung kipas pada unit dalam ruang Pelindung ters...

Page 19: ...ang lemah atau anak anak tanpa pengawasan Dapat mengakibatkan kerusakan fungsi tubuh dan membahayakan kesehatan Anak anak harus diawasi untuk memastikan bahwa mereka tidak bermain dengan unit atau rem...

Page 20: ...luaran pembuangan terpasang Membuang embun dalam ruang yang dihilangkan Selama operasi pendinginan Pipa pembuangan Nama model pelat nama model Bilah horizontal di saluran keluar udara Pemipaan refrige...

Page 21: ...ian tanyakan kepada dealer Anda tentang tudung pelindung salja dll Mengenai pengkabelan Semua pengkabelan harus dilakukan oleh teknisi listrik resmi Untuk pengkabelan mintalah dealer Anda melakukannya...

Page 22: ...urangi kelembapan tanpa menurunkan suhu dalam ruang Suhu dalam ruang bila tombol pengoperasian ditekan akan menjadi suhu yang diatur Pada saat ini kecepatan kipas dan suhu diatur secara otomatis sehin...

Page 23: ...ngsung ke arah orang Suhu ruangan perlu waktu untuk mencapai suhu yang telah diatur Kami menyarankan memulai pengoperasian sebelum mengoperasikan pengatur waktu PERINGATAN Jangan menggunakan gas yang...

Page 24: ...dan perubahan bentuk Pasang filter udara Lihat item No 2 Tutuplah jeruji penghisap Pelan pelan dorong ke atas jeruji penghisap kemudian kaitkan dengan erat ke panel dekorasi sambil menekan kedua kenop...

Page 25: ...50 C atau lebih Ini dapat menyebabkan warnanya luntur dan perubahan bentuk Saat mengeringkan jeruji penghisap jangan memanaskannya dengan api Ini dapat menyebabkan hangus Jangan gunakan bensin benzena...

Page 26: ...m setelah listrik mengalir ke AC Beberapa model melakukan pengoperasian berikut untuk melindungi perangkat Jika OPERASI PEMANASAN dilakukan dalam waktu 6 jam setelah listrik mengalir ke AC kipas dalam...

Page 27: ...dalam ruang akan menggunakan angin lembut Butuh waktu hingga kecepatan kipas berubah Naikkan suhu yang telah diatur Beberapa saat kemudian kecepatan kipas akan berubah 7 KEBISINGAN PENDINGIN UDARA Ad...

Page 28: ...tau kotoran Selain itu hal ini dapat menyebabkan pengembunan pada saluran keluar udara Lihat 8 PEMELIHARAAN pada halaman 7 Periksa apakah suhu yang telah diatur tidak sesuai Aturlah ke suhu kecepatan...

Page 29: ...ikut akan muncul di layar Basic pada remote control berkabel selama pengoperasian Error Push Menu button Kesalahan Tekan tombol Menu Lampu pengoperasian akan berkedip Warning Push Menu button Kesalaha...

Page 30: ...14 CATATAN...

Page 31: ......

Page 32: ...3P459579 1D M16N053C 1902 HT The two dimensional bar code is a manufacturing code...

Reviews: