5 Installation

Installation manual

8

FBA35~14FBA35~7ADEA35~125A2VEB

Split system air conditioners

4P456962-1D – 2018.08

a1

Nut (field supply)

a2

Double nut (field supply)

b1

Washer (accessories)

c1

Hanger bracket (attached to the unit)

a

Indoor unit

b

Pipe

c

Hanger bracket pitch (suspension)

d

Suspension bolt spacing

INFORMATION

▪ The fan speed of the indoor unit is preset to ensure the

standard external static pressure.

▪ To set a higher or lower external static pressure, reset

the initial setting with the user interface.

Installation example:

b

a

c

e

d

a

Anchor

b

Ceiling slab

c

Long nut or turn-buckle

d

Suspension bolt

e

Indoor unit

Install the unit temporarily.

5

Attach the hanger bracket to the suspension bolt.

6

Fix it securely.

Level

. Make sure the unit is level at all four corners using a level

or a water-filled vinyl tube.

b

a

a

Water level

b

Vinyl tube

7

Tighten the upper nut.

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

5.1.2

Guidelines when installing the ducting

WARNING

If  one  or  more  rooms  are  connected  to  the  unit  using  a
duct system, make sure:

▪ there are no operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  case  the  floor  area  is  less  than  A

min

specified in the General safety precautions;

▪ no  auxiliary  devices,  which  may  be  a  potential  ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  the  manufacturer

are used in the duct work;

▪ an air inlet or outlet is connected directly with a room by

ducting. Do NOT use spaces such as a false ceiling as
a duct for the air inlet or outlet.

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

The ducting is to be field supplied.

Air  inlet  side.

  Attach  the  duct  and  intake-side  flange  (field

supply). For connecting the flange, use 7 accessory screws.

a b

b a

e

e

d

d

c

a

Connection screw (accessory)

b

Flange (field supply)

c

Main unit

d

Insulation (field supply)

e

Aluminium tape (field supply)

Filter. 

Be sure to attach an air filter inside the air passage on the

intake  side.  Use  an  air  filter  with  dust  collecting  efficiency  ≥50%
(gravimetric  method).  The  included  filter  is  not  used  when  the
intake duct is attached.

Air  outlet  side.

  Connect  the  duct  according  to  the  inside

dimension of the outlet-side flange.

Air leaks.

 Wind aluminium tape around the intake side flange and

duct  connection.  Make  sure  there  are  no  air  leaks  at  any  other
connection.

Insulation.

  Insulate  the  duct  to  prevent  condensation  from

forming. Use glass wool or polyethylene foam 25 mm thick.

5.1.3

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Drain pump.

 For this "high lift type", the drainage sounds will be

reduced  when  the  drain  pump  is  installed  in  a  higher  location.
Recommended height is 300 mm.

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  25  mm  nominal  diameter  and
32 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Summary of Contents for FBA35A2VEB9

Page 1: ...sh Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB FBA35A2VEB9 FBA50A2VEB9 FBA60A2VEB9 FBA71A2VEB9 ADEA35A2VEB ADEA50A...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 4: ...condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses...

Page 5: ...users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General saf...

Page 6: ...ny place where flammable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound p...

Page 7: ...he flange c Fixing screw Ceiling strength Check whether the ceiling is strong enough to support the weight of the unit If there is a risk reinforce the ceiling before installing the unit Installation...

Page 8: ...oom by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an op...

Page 9: ...insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5...

Page 10: ...tly resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifica...

Page 11: ...electrical wiring does NOT obstruct proper reattachment of the service cover It is important to keep the power supply and the transmission wiring separated from each other In order to avoid any elect...

Page 12: ...the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to the minimum Ssc value Ensure that equipment is connected only to a supply with a short circuit powe...

Page 13: ...CE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 7 1 Checklist before commissioning After the installation of the unit first check...

Page 14: ...oor unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wir...

Page 15: ...D H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHu...

Page 16: ...4P456962 1D 2018 08 Copyright 2017 Daikin...

Reviews: