![background image](http://html1.mh-extra.com/html/daikin/fayp100bv1/fayp100bv1_technical-data-manual_2460333005.webp)
2
Specifications
NOMINAL CAPACITY and NOMINAL INPUT
For indoor units only:
INDOOR UNITS
FAYP71BV1
FAYP100BV1
NOMINAL INPUT
Cooling
kW
0.086
0.101
For combination indoor units + outdoor units:
INDOOR UNITS
FAYP71BV1
FAYP100BV1
OUTDOOR UNITS
RP71B7V1/W1/T1
RP100B7V1/W1/T1
NOMINAL CAPACITY
(2)
Cooling (1)
kW
7.1
10.0
NOMINAL INPUT
Cooling
kW
2.66/2.65/2.65
3.53/3.51/3.51
TECHNICAL SPECIFICATIONS
INDOOR UNITS
FAYP71BV1
FAYP100BV1
DIMENSIONS
Unit
H
mm
360
360
W
mm
1,570
1,570
D
mm
200
200
WEIGHT
Unit
kg
26
26
MATERIAL
Unit
Resin
COLOUR
Unit
White
SOUND LEVEL
Sound pressure (3)
high
dBA
41
45
low
dBA
37
41
Sound power (4)
high
dBA
57
61
low
dBA
53
57
FAN
Air flow rate
high
m
3
/min
19
23
medium
m
3
/min
low
m
3
/min
16
19
Speed
steps
2 steps
high
rpm
low
rpm
Type
Cross flow fan
Qty x model
1 x (QCQCL1163MB)
Qty x motor output
W
1 x 46
1 x 49
HEAT EXCHANGER
Type
Cross fin coil (Multi louver fins and N-hiX tubes)
Rows x stages x fin pitch
mm
2 x 12 x 1.4
2 x 12 x 1.4
Face area
m
2
0.332
0.332
AIR FILTER
AIR DIRECTION CONTROL
TEMPERATURE CONTROL
PIPING CONNECTIONS
liquid
mm
φ
9.5(flare)
φ
9.5(flare)
gas
mm
φ
15.9(flare)
φ
19.1(flare)
drain
mm
VP20, I.D.
φ
20
VP20, I.D.
φ
20
drain
mm
VP20, O.D.
φ
26
VP20, O.D.
φ
26
INSULATION
MATERIAL
Heat insulation
Foamed polystyrene/foamed polyethylene
Sound absorbing insulation
For outdoor units
Pair application
See chapter R-GZ7/RP-B7
•
Wall Mounted Unit
•
R-407C
•
FAYP71-100BV1
3
2
3
•
Split - Sky Air
•
Indoor Units