background image

3

2

• Split - Sky Air • FAQ-C

3

• Indoor Unit • FAQ-C

2

Specifications

Standard Accessories : Installation and operation manual; Quantity : 1;
Standard Accessories : Installation panel;
Standard Accessories : Insulation tape;
Standard Accessories : Screws;
Standard Accessories : Clamps;
Standard Accessories : Screw cover;

2-1 Technical Specifications

FAQ71C

FAQ100C

*FAQ125C

Power input

Cooling

Nom.

kW

0.051

0.061

-

Heating

Nom.

kW

0.068

0.061

-

Casing

Colour

Fresh White

-

Material

Resin

-

Dimensions

Unit

Height/Width/
Depth

mm

290/1,050/238

340/1,200/240

340/1,200/240

Packed unit

Height/Width/
Depth

mm

366/1,147/337

429/1,310/325

-/-/-

Weight

Unit

kg

13

17

17

Packed unit

kg

19

24

-

Heat exchanger

Length

mm

863

963

-

Rows

Quantity

2

-

Fin pitch

mm

1.2

-

Passes

Quantity

4

6

-

Face area

0.279

0.347

-

Stages

Quantity

18

20

-

Empty tubeplate 
hole

Quantity

0

-

Fin

Type

Cross fin coil (Multi slit fins and Hi-XB tubes)

-

Fan

Type

Cross flow fan

-

Quantity

1

-

Air flow rate

Cooling High

m³/min

18

26

-

Nom.

m³/min

16

23

-

Low

m³/min

14

19

-

Heating High

m³/min

18

26

-

Nom.

m³/min

16

23

-

Low

m³/min

14

19

-

Fan motor

Model

QCL9663MA

QCL1096M

-

Speed

Steps

3

-

Output

High

W

48

64

-

Phase x Voltage

V

DC310

DC325

-

Full load amps 
(FLA)

Cooling

A

0.3

0.4

-

Heating

A

0.4

-

Sound power level

Cooling

dBA

61

65

-

Heating

dBA

61

65

-

Sound pressure level

Cooling

High/Nom./Low

dBA

45/42/40

49/45/41

-/-/-

Heating

High/Nom./Low

dBA

45/42/40

49/45/41

-/-/-

Control systems

Infrared remote control

BRC7EB518

-

Wired remote control

BRC1D52 / BRC1E52A/B

-

Refrigerant

Type

R-410A

-

Piping connections

Liquid

Type/OD

mm

Flare connection/9.52

/-

Gas

Type/OD

mm

Flare connection/15.9

/-

Drain

VP13 (I.D. 13/O.D. 18)

-

Heat insulation

Foamed polystyrene / Foamed polyethylene

-

2-2 Electrical Specifications

FAQ71C

FAQ100C

*FAQ125C

Power supply

Phase

1~

1~

Frequency

Hz

50/60

50/60

Voltage

V

220-240/220

220-240/220

Summary of Contents for FAQ-C Series

Page 1: ...Air Conditioning Technical Data Wall mounted unit EEDEN15 100 FAQ C...

Page 2: ......

Page 3: ...ecifications 3 Technical Specifications 3 Electrical Specifications 3 3 Safety device settings 5 4 Options 6 5 Dimensional drawings 7 6 Piping diagrams 8 7 Wiring diagrams 9 Wiring Diagrams Single Pha...

Page 4: ...r The air is comfortably spread up and downwards thanks to 5 different discharge angles that can be programmed via the remote control Maintenance operations can be performed easily from the front of t...

Page 5: ...beplate hole Quantity 0 Fin Type Cross fin coil Multi slit fins and Hi XB tubes Fan Type Cross flow fan Quantity 1 Air flow rate Cooling High m min 18 26 Nom m min 16 23 Low m min 14 19 Heating High m...

Page 6: ...3 3 Split Sky Air FAQ C 5 Indoor Unit FAQ C 3 Safety device settings 3 1 Safety Device Settings...

Page 7: ...Indoor Unit FAQ C 4 Split Sky Air FAQ C 6 4 Options 4 1 Options...

Page 8: ...3 5 Split Sky Air FAQ C 7 Indoor Unit FAQ C 5 Dimensional drawings 5 1 Dimensional Drawings...

Page 9: ...Indoor Unit FAQ C 6 Split Sky Air FAQ C 8 6 Piping diagrams 6 1 Piping Diagrams...

Page 10: ...3 7 Split Sky Air FAQ C 9 Indoor Unit FAQ C 7 Wiring diagrams 7 1 Wiring Diagrams Single Phase...

Page 11: ...Indoor Unit FAQ C 8 Split Sky Air FAQ C 10 8 External connection diagrams 8 1 External Connection Diagrams...

Page 12: ...3 9 Split Sky Air FAQ C 11 Indoor Unit FAQ C 9 Sound data 9 1 Sound Pressure Spectrum...

Page 13: ......

Page 14: ...in Europe N V has compiled the content of this leaflet to the best of its knowledge No express or implied warranty is given for the completeness accuracy re liability or fitness for particular purpose...

Reviews: